SPLUSS_RYMASKON_2XX_MOD
SPLUSS_RYMASKON_2XX_MOD (FB)
SPLUSS_RYMASKON_2XX_MOD (FB)FUNCTION_BLOCK SPLUSS_RYMASKON_2XX_MOD
Short description
Control of the Rymaskon 2XX device series by S+S Regeltechnik Additional functions: Two operating modes for setpoint temperature formation Typical application: room control unit in one zone
Representation

Interfaces
Inputs
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
byUnitId
BYTE
0
Device address (0 .. 255)
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge)
xUpdateStates
BOOL
FALSE
Update of states (on every rising edge)
xUpdateSetp
BOOL
FALSE
Update of setpoints (on every rising edge)
xUpdateConfig
BOOL
FALSE
Update of configuration (on every rising edge)
rSetpTempBase
REAL
22.0
Base setpoint temperature (degrees Celsius)
rEnSetpTempOff
BOOL
FALSE
Enable / disable recording of changes to the room setpoint temperature (FALSE = no recording, rSetpTempOff = 0.0 K)
rSetpDispFanLev
REAL
0.0
Setpoint for the display of the fan stage (bar graph - right)
rSetpDispHCLev
REAL
0.0
Setpoint for the display of heating/cooling output (bar graph - left)
xDsplSymbPresen
BOOL
FALSE
Display of the symbols for presence (= TRUE) or absence (= FALSE)
xDsplSymbHeat
BOOL
FALSE
Display of the symbol for heating operation (TRUE = display)
xDsplSymbCool
BOOL
FALSE
Display of the symbol for cooling operation (TRUE = display)
xDsplSymbFan
BOOL
FALSE
Display of the symbol for the fan (TRUE = display)
xDsplSymbAlWindo
BOOL
FALSE
Display of the window alarm symbol (TRUE = display)
xDsplSymbAlRainf
BOOL
FALSE
Display of the rain alarm symbol (TRUE = display)
xDsplSymbAlStorm
BOOL
FALSE
Display of the wind alarm symbol (TRUE = display)
xDsplSymbAlAlarm
BOOL
FALSE
Display of the alarm symbol (TRUE = display)
xDsplSymbNotDrop
BOOL
FALSE
Display of the crossed-out drop symbol (TRUE = display)
xDsplSymbClock
BOOL
FALSE
Display of the clock symbol (TRUE = display)
xBuzzer_Alarm
BOOL
FALSE
Enable / disable the alarm tone (buzzer) (TRUE = enable)
xResetDevice
BOOL
FALSE
Reset of the device (on every rising edge)
Outputs
rSetpTemp
REAL
Set temperature (degrees Celsius) (corresponds to the room setpoint temperature shown on the RBG)
rSetpTempOff
REAL
Set temperature offset (Kelvin)
rRoomTemp
REAL
Room temperature in XXX.X degrees Celsius
rExtTemp
REAL
External temperature in XXX.X degrees Celsius
rRelHumidity
REAL
Relative room humidity in XXX.X %
rDewPointTemp
REAL
Dew point temperature in XXX.X degrees Celsius (the offsets of temperature and relative humidity are not taken into account)
rSupplyVolt
REAL
Supply voltage in XXX.X Volts
rCpuTemp
REAL
CPU temperature in XXX.X degrees Celsius
rCpuVolt
REAL
CPU voltage in XXX.X Volts
sSerialNum
STRING
Serial number of the device
sProductCode
STRING
Product code of the device (e.g. 21X)
xConfig
BOOL
State of the device configuration [ TRUE = configuration active ]
xButtonPresence
BOOL
Pressing the presence button (RBG (= room control unit): RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)
xButtonTempUp
BOOL
Pressing the button to increase the set temperature (RBG: pulse with duration tTimeButtonPulse) (RBG and/or VISU)
xButtonTempDown
BOOL
Pressing the button to decrease the set temperature (RBG: pulse with duration tTimeButtonPulse) (RBG and/or VISU)
xButtonFanUp
BOOL
Pressing the button to increase the fan stage (RBG: RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)
xButtonFanDown
BOOL
Pressing the button to decrease the fan stage (RBG: RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)
xButtonLightOn
BOOL
Pressing the button to activate the lighting (RBG: RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)
xButtonLightOff
BOOL
Pressing the button to deactivate the lighting (RBG: RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)
xButtonShadeUp
BOOL
Pressing the button to open the shading (RBG: RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)
xButtonShadeDown
BOOL
Pressing the button to close the shading (RBG: RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)
xStateExtBut0
BOOL
State of external input 0
xStateExtBut1
BOOL
State of external input 1
xStateExtBut2
BOOL
State of external input 2
xStateExtBut3
BOOL
State of external input 3
xAlarm
BOOL
Collective fault (TRUE = fault)
xAlarmCom
BOOL
Collective fault - communication (TRUE = fault)
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
eErrorCodeDev
SPLUSS_ERROR_CODE_TYPE_2
Error code - device (0 = no error)
xBusy
BOOL
Communication indicator (TRUE = communication)
Inputs and outputs
ModbusClient
ModbusClientBase
Client of the device
Setpoints / parameters
tTimeUpdateActual
TIME
T#3s
Update interval for the processes influenced by the input xUpdateActual are affected (0 = no automatic update, > 0 cyclical update)
tTimeUpdateStates
TIME
T#500ms
Update interval for the processes influenced by the input xUpdateStates are affected (0 = no automatic update, > 0 cyclical update)
tTimeUpdateSetp
TIME
T#0s
Update interval for the processes influenced by the input xUpdateSetp are affected (0 = no automatic update, > 0 cyclical update)
tTimeUpdateConfig
TIME
T#0s
Update interval for the processes influenced by the input xUpdateConfig are affected (0 = no automatic update, > 0 cyclical update)
tPCTimeLong
TIME
T#60s
Interval time of the scan process for determining the product code (long duration, device detected)
tPCTimeShort
TIME
T#5s
Interval time of the scan process for determining the product code (short duration, device not yet detected)
tTimeButtonPulse
TIME
T#1s
Duration of the pulse at the output if the assigned button was pressed briefly
rSetpTempMin
REAL
18.0
Absolute minimum value - setpoint temperature (degrees Celsius)
rSetpTempMax
REAL
26.0
Absolute maximum value - setpoint temperature (degrees Celsius)
rSetpTempOffMin
REAL
-3.0
Absolute minimum value of the set temperature offset (Kelvin)
rSetpTempOffMax
REAL
3.0
Absolute maximum value of the set temperature offset (Kelvin)
rSetpTempVariat
REAL
0.5
Step size of the set temperature offset (Kelvin)
wPinCodeAdmin
WORD
7458
PIN code for the administrator level (0 = no code, 0001 - 9999 valid code)
wPinCodeEndUser
WORD
3333
PIN code for the user level (0 = no code, 0001 - 9999 valid code)
eColorScheme
SPLUSS_LCD_COLOR_SCHEME
SPLUSS_LCD_COLOR_SCHEME.WHITE
Number of the color scheme (1 = white, 1-7 = valid numbers)
xDispBargrFanLev
BOOL
FALSE
Enable / disable the display of the right bar graph (FALSE = no display)
xDispBargrHCLev
BOOL
FALSE
Enable / disable the display of the left bar graph (FALSE = no display)
ePresenceOutpMode
SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE
SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE
Operating mode of the output xButtonPresence (RAW, PULSE)
eFanOutpMode
SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE
SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE
Operating mode of the outputs xButtonFanUp or xButtonFanDwn (RAW, PULSE)
eLightOutpMode
SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE
SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE
Operating mode of the outputs xButtonLightOn or xButtonLightOff (RAW, PULSE)
eShadeOutpMode
SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE
SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.RAW
Operating mode of the outputs xButtonShadeUp or xButtonShadeDwn (RAW, PULSE)
xVisuPresence
BOOL
FALSE
Pressing the presence button in the visualization
xVisuTempUp
BOOL
FALSE
Pressing the button to increase the set temperature in the visualization
xVisuTempDown
BOOL
FALSE
Pressing the button to decrease the set temperature in the visualization
xVisuFanUp
BOOL
FALSE
Pressing the button to increase the fan stage in the visualization
xVisuFanDown
BOOL
FALSE
Pressing the button to decrease the fan stage in the visualization
xVisuLightOn
BOOL
FALSE
Pressing the button to activate the lighting in the visualization
xVisuLightOff
BOOL
FALSE
Pressing the button to deactivate the lighting in the visualization
xVisuShadeUp
BOOL
FALSE
Pressing the button to open the shading in the visualization
xVisuShadeDown
BOOL
FALSE
Pressing the button to close the shading in the visualization
Function description
General
This function block controls room control units of the Rymaskon 2XX device series by S+S Regeltechnik via Modbus communication. Alternatively, room control units from Loytec can also be used. The different types (21x - 26x) of room control units are detected automatically. After detection, the room control units are automatically configured sensibly according to type. Two operating modes are provided for forming the room setpoint temperature (MANUALLY, AUTOMATICALLY). For different outputs (xButtonXXX), two operating modes are also provided (RAW, PULSE) (valid only when operated via the room control unit)
Detection of the product code (of the device type)
The Modbus address of the room control unit for communication with this function block is set at input byUnitId in the range 0 - 255. Immediately after the controller is switched on, at intervals tPCTimeShort (default: 5s) a request telegram is sent to the room control unit each time to return the product code and serial number. After receiving a response telegram, the product code is checked and evaluated. A valid product code is output at the output sProductCode . In addition, the serial number of the room control unit is output at the output sSerialNum . The configuration of the room control unit is triggered if the serial number has changed (directly after the CPU is switched on or after the room control unit has been replaced). After detection of a valid product code, the interval for sending a request telegram to return the product code and serial number is increased to tPCTimeLong (default: 60s). If ten consecutive response telegrams with an incorrect product code or no response telegrams at all are received within this interval, the detection cycle is executed again at interval tPCTimeShort .
Formation of the room setpoint temperature
The room setpoint temperature, which is displayed directly on the room control unit display and output at output rSetpTemp always corresponds to the state at input rSetpTempBase. It is limited by adjustable absolute minimum (rSetpTempMin, default: 18.0 degrees Celsius) and maximum values (rSetpTempMax, default: 26.0 degrees Celsius). No transfer of room setpoint temperatures outside these absolute limits takes place.
Formation of the offset of the room setpoint temperature
The offset of the room setpoint temperature is influenced by outputs xButtonTempUp (rising edge) and xButtonTempDown (rising edge). The current state is always displayed at output rSetpTempOff . The formation of the offset is enabled via input xEnSetpTempOff and disabled (xEnSetpTempOff = FALSE). In the disabled state, the value 0.0 is output at output rSetpTempOff . In the enabled state, the last set value is output at output rSetpTempOff . In the enabled state, output rSetpTempOff is increased by the parameter xButtonTempUp rSetpTempOffVariat (default: 0.5 K) on every rising edge at output . In the enabled state, output rSetpTempOff is increased by the parameter xButtonTempDown rSetpTempOffVariat (default: 0.5 K) on every rising edge at output is reduced. In the enabled state, output rSetpTempOff is limited in absolute terms by the parameters rSetpTempOffMin (default: -3.0 K) and rSetpTempOffMax (default: 3.0 K). Whenever the parameters (default: 0.5 K) on every rising edge at output, rSetpTempOffMin and rSetpTempOffMax change, output rSetpTempOff is reinitialized to 0.0.
Outputs xButtonTempUp and xButtonTempDown
The outputs are influenced by operating the TBO or TB4 buttons on the RBG and additionally by the inputs for the visualization (xVisuTempUp and xVisuTempDown) (OR linkage). Each brief press of button TB0 (increase temperature) and TB4 (decrease temperature) triggers a pulse of duration xButtonTempUp and xButtonTempDown at the associated outputs tTimeButtonPulse (default: 1s).
Outputs xButtonXXX (not for xButtonTempUp and xButtonTempDown)
xButtonXXX (not for xButtonTempUp and xButtonTempDown)The outputs xButtonXXX (xButtonPresence, xButtonFanUp, xButtonFanDown, xButtonLightOn, xButtonLightOff, xButtonShadeUp and xButtonShadeDown) are influenced by operating the corresponding buttons on the RBG and additionally by the inputs for the visualization (xVisuXXX) (OR linkage).
They can be operated on the RBG in two different operating modes (selection via parameters ePresenceOutpMode, eFanOutpMode, eLightOutpMode and eShadeOutpMode). The operating mode is always selected jointly for both outputs of a function.
Operating modes
RAW
The outputs immediately adopt the states of their assigned buttons (button pressed >>> output = TRUE). The arrangement of the buttons may differ depending on the type of room control unit. If the buttons for the desired function are not present on the room control unit, the assigned outputs remain inactive (= FALSE).
PULSE
Each brief press of the button triggers a pulse of duration at the associated output tTimeButtonPulse (default: 1s).
Display of fan stage
The display of the fan stage (selection via input rSetpDispFanLev in the range 0.0 - 7.0) is shown by the right bar graph on the display of the room control unit, if the display is generally enabled (parameter xDispBargrFanLev = TRUE).
rSetpDispFanLev
Display
Notes
0
Stage 0 - Manual
1
Stage 1 - Manual
2
Stage 2 - Manual
3
Stage 3 - Manual
4
Stage 0 - Automatic
5
Stage 1 - Automatic
6
Stage 2 - Automatic
7
Stage 3 - Automatic
Display of heating/cooling output
The display of the heating/cooling output (selection via input rSetpDispHCLev in the range 0.0 - 7.0) is shown by the left bar graph on the display of the room control unit, if the display is generally enabled (parameter xDispBargrHCLev = TRUE).
rSetpDispHCLev
Display
Notes
0
Stage 0 - Manual
1
Stage 1 - Manual
2
Stage 2 - Manual
3
Stage 3 - Manual
4
Stage 0 - Automatic
5
Stage 1 - Automatic
6
Stage 2 - Automatic
7
Stage 3 - Automatic
Display of symbols
The display of the desired symbols on the room control unit display is triggered by the TRUE state at the associated input. (Example: xDsplSymbHeat = TRUE causes the static display of the symbol Heating in the display). Inputs with the name suffix ‘-Al-’ cause a slowly blinking display of the associated symbol. (Example: xDsplSymbAlStorm = TRUE causes the slowly blinking display of the symbol windsock in the display).
Resetting the room control unit
The room control unit is reset on every rising edge at input xResetDevice .
Control of the piezo buzzer in the room control unit
The static TRUE state at input xBuzzer_Alarm triggers an intermittent alarm tone at a frequency of 800 Hz in the room control unit.
Display of faults
Faults are displayed at the collective output xAlarm (= TRUE). It includes communication faults (time delay: gc_Parameters.gc_tOnDelayxAlarmCom, default = 60s) and device faults (direct). At output eErrorCodeCom an explanatory text for the cause is available in the event of a communication error. It always shows the cause of the last communication error there. At output eErrorCodeDev an explanatory text for the cause is available in the event of a device error.
Output xConfig
xConfigThe output signals the configuration of the device (= TRUE) after it has been detected (see detection of the product code)
Output wDeviceMode
wDeviceModeThe numerical value at this output identifies the current display of the room control unit (menu level, display content, password level, etc.). It corresponds to the content of Modbus register 101, see the device documentation.
Update of the outputs for button presses (9 outputs)
The state of output xButtonXXX is formed from the OR linkage of the state based on operation on the room control unit (_xButtonXXX) and based on operation in the visualization (xVisuXXX).
Codesys
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
Input
byUnitId
BYTE
0
Device address (0 .. 255)
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
xUpdateStates
BOOL
FALSE
Update of the states (on each rising edge)
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints (on every rising edge )
Input
xUpdateConfig
BOOL
FALSE
Update of the configuration (on each rising edge)
Input
rSetpTempBase
REAL
22.0
Base setpoint temperature (degrees Celsius)
Input
xEnSetpTempOff
BOOL
FALSE
Enable / disable recording of changes to the room setpoint temperature (FALSE = no recording, rSetpTempOff = 0.0 K)
Input
rSetpDispFanLev
REAL
0.0
Setpoint for the display of the fan stage (bar graph - right)
Input
rSetpDispHCLev
REAL
0.0
Setpoint for the display of heating/cooling output (bar graph - left)
Input
xDsplSymbPresen
BOOL
FALSE
Display of the symbols for presence (= TRUE) or absence (= FALSE)
Input
xDsplSymbHeat
BOOL
FALSE
Display of the symbol for heating operation (TRUE = display)
Input
xDsplSymbCool
BOOL
FALSE
Display of the symbol for cooling operation (TRUE = display)
Input
xDsplSymbFan
BOOL
FALSE
Display of the symbol for the fan (TRUE = display)
Input
xDsplSymbAlWindo
BOOL
FALSE
Display of the window alarm symbol (TRUE = display)
Input
xDsplSymbAlRainf
BOOL
FALSE
Display of the rain alarm symbol (TRUE = display)
Input
xDsplSymbAlStorm
BOOL
FALSE
Display of the wind alarm symbol (TRUE = display)
Input
xDsplSymbAlAlarm
BOOL
FALSE
Display of the alarm symbol (TRUE = display)
Input
xDsplSymbNotDrop
BOOL
FALSE
Display of the crossed-out drop symbol (TRUE = display)
Input
xDsplSymbClock
BOOL
FALSE
Display of the clock symbol (TRUE = display)
Input
xBuzzer_Alarm
BOOL
FALSE
Enable / disable the alarm tone (buzzer) (TRUE = enable)
Input
xResetDevice
BOOL
FALSE
Reset of the device (on every rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rSetpTemp
REAL
Set temperature (degrees Celsius) (corresponds to the room setpoint temperature shown on the RBG)
Output
rSetpTempOff
REAL
Set temperature offset (Kelvin) (rSetpTempOff:= rSetpTemp - rSetpTempBase)
Output
rRoomTemp
REAL
Room temperature in XXX.X degrees Celsius
Output
rExtTemp
REAL
External temperature in XXX.X degrees Celsius
Output
rRelHumidity
REAL
Relative room humidity in XXX.X %
Output
rDewPointTemp
REAL
Dew point temperature in XXX.X degrees Celsius (the offsets of temperature and relative humidity are not taken into account)
Output
xSensorOffsetInDevice
BOOL
Indication of whether the sensors must be calibrated in the device (TRUE = calibration in the device required, FALSE = calibration in the FB required)
Output
rSupplyVolt
REAL
Supply voltage in XXX.X Volts
Output
rCpuTemp
REAL
CPU temperature in XXX.X degrees Celsius
Output
rCpuVolt
REAL
CPU voltage in XXX.X Volts
Output
sSerialNum
STRING
Serial number of the device
Output
sProductCode
STRING
Product code of the device (e.g. 21X)
Output
wDeviceMode
WORD
Operating mode of the device
Output
xConfig
BOOL
FALSE
State of the device configuration [ TRUE = configuration active ]
Output
xButtonPresence
BOOL
FALSE
Pressing the presence button (RAW, pulse with duration
tTimeButtonPulse) (RBG and/or VISU)
Output
xButtonTempUp
BOOL
FALSE
Pressing the button to increase the set temperature (pulse with duration tTimeButtonPulse) (RBG and/or VISU)
Output
xButtonTempDown
BOOL
FALSE
Pressing the button to decrease the set temperature (pulse with duration tTimeButtonPulse) (RBG and/or VISU)
Output
xButtonFanUp
BOOL
FALSE
Pressing the button to increase the fan stage (RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)
Output
xButtonFanDown
BOOL
FALSE
Pressing the button to decrease the fan stage (RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)
Output
xButtonLightOn
BOOL
FALSE
Pressing the button to activate the lighting (RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)
Output
xButtonLightOff
BOOL
FALSE
Pressing the button to deactivate the lighting (RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)
Output
xButtonShadeUp
BOOL
FALSE
Pressing the button to open the shading (RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)
Output
xButtonShadeDown
BOOL
FALSE
Pressing the button to close the shading (RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)
Output
xStateExtBut0
BOOL
State of external input 0
Output
xStateExtBut1
BOOL
State of external input 1
Output
xStateExtBut2
BOOL
State of external input 2
Output
xStateExtBut3
BOOL
State of external input 3
Output
xAlarm
BOOL
FALSE
Collective fault (TRUE = fault)
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication (TRUE = fault)
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
Output
eErrorCodeDev
SPLUSS_ERROR_CODE_TYPE_2
Error code - device (0 = no error)
Output
xBusy
BOOL
Communication indicator (TRUE = communication)
Input Const
rRelHumidityOffset
REAL
0.0
Constant measured-value offset for the transmitted relative humidity actual value (internal relative humidity)
Input Const
rExtTempOffset
REAL
0.0
Constant measured-value offset for the transmitted temperature actual value (external temperature)
Input Const
rRoomTempOffset
REAL
0.0
Constant measured-value offset for the transmitted temperature actual value (internal temperature)
Input Const
xVisuShadeDown
BOOL
FALSE
Pressing the button to close the shading in the visualization
Input Const
xVisuShadeUp
BOOL
FALSE
Pressing the button to open the shading in the visualization
Input Const
xVisuLightOff
BOOL
FALSE
Pressing the button to deactivate the lighting in the visualization
Input Const
xVisuLightOn
BOOL
FALSE
Pressing the button to activate the lighting in the visualization
Input Const
xVisuFanDown
BOOL
FALSE
Pressing the button to decrease the fan stage in the visualization
Input Const
xVisuFanUp
BOOL
FALSE
Pressing the button to increase the fan stage in the visualization
Input Const
xVisuTempDown
BOOL
FALSE
Pressing the button to decrease the set temperature in the visualization
Input Const
xVisuTempUp
BOOL
FALSE
Pressing the button to increase the set temperature in the visualization
Input Const
xVisuPresence
BOOL
FALSE
Pressing the presence button in the visualization
Input Const
eShadeOutpMode
SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE
SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.RAW
Operating mode of the outputs xButtonShadeUp or
xButtonShadeDwn (RAW, PULSE)
Input Const
eLightOutpMode
SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE
SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE
Operating mode of the outputs xButtonLightOn or
xButtonLightOff (RAW, PULSE)
Input Const
eFanOutpMode
SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE
SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE
Operating mode of the outputs xButtonFanUp or xButtonFanDwn
(RAW, PULSE)
Input Const
ePresenceOutpMode
SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE
SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE
Operating mode of the output xButtonPresence (RAW, PULSE)
Input Const
xDispBargrHCLev
BOOL
FALSE
Enable / disable the display of the left bar graph (FALSE = no display)
Input Const
xDispBargrFanLev
BOOL
FALSE
Enable / disable the display of the right bar graph (FALSE = no display)
Input Const
eColorScheme
SPLUSS_LCD_COLOR_SCHEME
SPLUSS_LCD_COLOR_SCHEME.WHITE
Number of the color scheme (1 = white, 1-7 = valid numbers)
Input Const
wPinCodeEndUser
WORD
3333
PIN code for the user level (0 = no code, 0001 - 9999 valid code)
Input Const
wPinCodeAdmin
WORD
7458
PIN code for the administrator level (0 = no code, 0001 - 9999 valid code)
Input Const
(default: 0.5 K) on every rising edge at output
REAL
0.5
Step size of the set temperature offset (Kelvin)
Input Const
rSetpTempOffMax
REAL
3.0
Absolute maximum value of the set temperature offset (Kelvin)
Input Const
rSetpTempOffMin
REAL
-3.0
Absolute minimum value of the set temperature offset (Kelvin)
Input Const
rSetpTempMax
REAL
26.0
Absolute maximum value - setpoint temperature (degrees Celsius)
Input Const
rSetpTempMin
REAL
18.0
Absolute minimum value - setpoint temperature (degrees Celsius)
Input Const
tTimeButtonPulse
TIME
TIME#1s0ms
Duration of the pulse at the output if the assigned button was pressed briefly
Input Const
tPCTimeShort
TIME
TIME#5s0ms
Interval time of the scan process for determining the product code (short duration, device not yet detected)
Input Const
tPCTimeLong
TIME
TIME#1m0s0ms
Interval time of the scan process for determining the product code (long duration, device detected)
Input Const
tTimeUpdateConfig
TIME
TIME#0ms
Update interval for the processes influenced by the input
xUpdateConfig influenced
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the processes influenced by the input
xUpdateSetp influenced
Input Const
tTimeUpdateStates
TIME
TIME#500ms
Update interval for the processes influenced by the input
xUpdateStates influenced
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes influenced by the input
xUpdateActual influenced
Last updated

