SPLUSS_RYMASKON_2XX_MOD

SPLUSS_RYMASKON_2XX_MOD (FB)

FUNCTION_BLOCK SPLUSS_RYMASKON_2XX_MOD

Short description

Control of the Rymaskon 2XX device series from S+S Regeltechnik Additional functions: Two operating modes for setpoint temperature generation Typical application: Room control unit in a zone\

Representation

Interfaces

Inputs

Name
Data type
Value range
Initial value
Function

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enabled)

byUnitId

BYTE

0

Address of the device ( 0 .. 255 )

xUpdateActual

BOOL

FALSE

Update of actual values ( on each rising edge )

xUpdateStates

BOOL

FALSE

Update of states ( on each rising edge )

xUpdateSetp

BOOL

FALSE

Update of setpoints ( on each rising edge )

xUpdateConfig

BOOL

FALSE

Update of configuration ( on each rising edge )

rSetpTempBase

REAL

22.0

Base setpoint temperature ( degrees Celsius )

rEnSetpTempOff

BOOL

FALSE

Enable / disable detection of changes of the room setpoint temperature ( FALSE = no detection, rSetpTempOff = 0.0 K )

rSetpDispFanLev

REAL

0.0

Setpoint for the display of the fan level ( bargraph - right )

rSetpDispHCLev

REAL

0.0

Setpoint for the display of heating/cooling power ( bargraph - left )

xDsplSymbPresen

BOOL

FALSE

Display of the symbols for presence ( = TRUE ) or absence ( = FALSE )

xDsplSymbHeat

BOOL

FALSE

Display of the symbol for heating operation ( TRUE = display )

xDsplSymbCool

BOOL

FALSE

Display of the symbol for cooling operation ( TRUE = display )

xDsplSymbFan

BOOL

FALSE

Display of the symbol for the fan ( TRUE = display )

xDsplSymbAlWindo

BOOL

FALSE

Display of the symbol for window - alarm ( TRUE = display )

xDsplSymbAlRainf

BOOL

FALSE

Display of the symbol for rain - alarm ( TRUE = display )

xDsplSymbAlStorm

BOOL

FALSE

Display of the symbol for wind - alarm ( TRUE = display )

xDsplSymbAlAlarm

BOOL

FALSE

Display of the symbol for alarm ( TRUE = display )

xDsplSymbNotDrop

BOOL

FALSE

Display of the symbol for the crossed-out drop ( TRUE = display )

xDsplSymbClock

BOOL

FALSE

Display of the symbol for the clock ( TRUE = display )

xBuzzer_Alarm

BOOL

FALSE

Enable / disable the alarm tone ( buzzer ) ( TRUE = enabled )

xResetDevice

BOOL

FALSE

Reset of the device ( on each rising edge )

Outputs

Name
Data type
Value range
Initial value
Function

rSetpTemp

REAL

Set temperature ( degrees Celsius ) ( corresponds to the room setpoint temperature shown on the RBG )

rSetpTempOff

REAL

Setpoint temperature offset ( Kelvin )

rRoomTemp

REAL

Room temperature in XXX.X degrees Celsius

rExtTemp

REAL

External temperature in XXX.X degrees Celsius

rRelHumidity

REAL

Relative room humidity in XXX.X %

rDewPointTemp

REAL

Dew point temperature in XXX.X degrees Celsius ( The temperature and relative humidity offsets are not considered )

rSupplyVolt

REAL

Supply voltage in XXX.X volts

rCpuTemp

REAL

CPU temperature in XXX.X degrees Celsius

rCpuVolt

REAL

CPU voltage in XXX.X volts

sSerialNum

STRING

Serial number of the device

sProductCode

STRING

Product code of the device ( e.g. ‘21X’ )

xConfig

BOOL

State of the device configuration [ TRUE = configuration active ]

xButtonPresence

BOOL

Actuation of the presence button ( RBG ( = room control unit ): RAW, pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

xButtonTempUp

BOOL

Actuation of the button to increase the setpoint temperature ( RBG: pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

xButtonTempDown

BOOL

Actuation of the button to decrease the setpoint temperature ( RBG: pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

xButtonFanUp

BOOL

Actuation of the button to increase the fan level ( RBG: RAW, pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

xButtonFanDown

BOOL

Actuation of the button to decrease the fan level ( RBG: RAW, pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

xButtonLightOn

BOOL

Actuation of the button to activate the lighting ( RBG: RAW, pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

xButtonLightOff

BOOL

Actuation of the button to deactivate the lighting ( RBG: RAW, pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

xButtonShadeUp

BOOL

Actuation of the button to open the shading ( RBG: RAW, pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

xButtonShadeDown

BOOL

Actuation of the button to close the shading ( RBG: RAW, pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

xStateExtBut0

BOOL

State of external input 0

xStateExtBut1

BOOL

State of external input 1

xStateExtBut2

BOOL

State of external input 2

xStateExtBut3

BOOL

State of external input 3

xAlarm

BOOL

Collective fault (TRUE = fault)

xAlarmCom

BOOL

Collective fault - communication (TRUE = fault)

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

eErrorCodeDev

SPLUSS_ERROR_CODE_TYPE_2

Error code - device (0 = no error)

xBusy

BOOL

Communication indicator (TRUE = communication)

Inputs and outputs

Name
Data type
Value range
Initial value
Function

ModbusClient

ModbusClientBase

Client of the device

Setpoints / parameters

Name
Data type
Value range
Initial value
Function

tTimeUpdateActual

TIME

T#3s

Update interval for the operations influenced by the input ‘xUpdateActual’ ( 0 = no automatic update, > 0 cyclical update )

tTimeUpdateStates

TIME

T#500ms

Update interval for the operations influenced by the input ‘xUpdateStates’ ( 0 = no automatic update, > 0 cyclical update )

tTimeUpdateSetp

TIME

T#0s

Update interval for the operations influenced by the input ‘xUpdateSetp’ ( 0 = no automatic update, > 0 cyclical update )

tTimeUpdateConfig

TIME

T#0s

Update interval for the operations influenced by the input ‘xUpdateConfig’ ( 0 = no automatic update, > 0 cyclical update )

tPCTimeLong

TIME

T#60s

Interval duration of the scan process to determine the product code ( long duration, device recognized )

tPCTimeShort

TIME

T#5s

Interval duration of the scan process to determine the product code ( short duration, device not yet recognized )

tTimeButtonPulse

TIME

T#1s

Duration of the pulse on the output if the associated button was pressed briefly

rSetpTempMin

REAL

18.0

Absolute minimum - setpoint temperature ( degrees Celsius )

rSetpTempMax

REAL

26.0

Absolute maximum - setpoint temperature ( degrees Celsius )

rSetpTempOffMin

REAL

-3.0

Absolute minimum value of the setpoint temperature offset ( Kelvin )

rSetpTempOffMax

REAL

3.0

Absolute maximum value of the setpoint temperature offset ( Kelvin )

rSetpTempVariat

REAL

0.5

Step size of the setpoint temperature offset ( Kelvin )

wPinCodeAdmin

WORD

7458

PIN code for the administrator level ( 0 = no code, 0001 - 9999 valid code )

wPinCodeEndUser

WORD

3333

PIN code for the user level ( 0 = no code, 0001 - 9999 valid code )

eColorScheme

SPLUSS_LCD_COLOR_SCHEME

SPLUSS_LCD_COLOR_SCHEME.WHITE

Number of the color scheme ( 1 = white, 1-7 = valid numbers )

xDispBargrFanLev

BOOL

FALSE

Enable / disable the display of the right bargraph ( FALSE = no display )

xDispBargrHCLev

BOOL

FALSE

Enable / disable the display of the left bargraph ( FALSE = no display )

ePresenceOutpMode

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE

Operating mode of the output ‘xButtonPresence’ ( RAW, PULSE )

eFanOutpMode

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE

Operating mode of the outputs ‘xButtonFanUp’ and ‘xButtonFanDwn’ ( RAW, PULSE )

eLightOutpMode

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE

Operating mode of the outputs ‘xButtonLightOn’ and ‘xButtonLightOff’ ( RAW, PULSE )

eShadeOutpMode

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.RAW

Operating mode of the outputs ‘xButtonShadeUp’ and ‘xButtonShadeDwn’ ( RAW, PULSE )

xVisuPresence

BOOL

FALSE

Actuation of the presence button in the visualization

xVisuTempUp

BOOL

FALSE

Actuation of the button to increase the setpoint temperature in the visualization

xVisuTempDown

BOOL

FALSE

Actuation of the button to decrease the setpoint temperature in the visualization

xVisuFanUp

BOOL

FALSE

Actuation of the button to increase the fan level in the visualization

xVisuFanDown

BOOL

FALSE

Actuation of the button to decrease the fan level in the visualization

xVisuLightOn

BOOL

FALSE

Actuation of the button to activate the lighting in the visualization

xVisuLightOff

BOOL

FALSE

Actuation of the button to deactivate the lighting in the visualization

xVisuShadeUp

BOOL

FALSE

Actuation of the button to open the shading in the visualization

xVisuShadeDown

BOOL

FALSE

Actuation of the button to close the shading in the visualization

Function description

General

This function block controls room control units of the Rymaskon 2XX device series from S+S Regeltechnik via Modbus communication. Alternatively, room control units from Loytec can also be used. The detection of the different types ( 21x - 26x ) of room control units is performed automatically. The room control units are automatically configured sensibly according to their type after detection. Two operating modes are provided for the generation of the room setpoint temperature ( MANUALLY, AUTOMATICALLY ). For various outputs ( xButtonXXX ) two operating modes are also provided ( RAW, PULSE ) ( valid only when operated via the room control unit ) \

Detection of the product code ( of the device type )

The Modbus address of the room control unit for communication with this function block is set at the input ‘byUnitId’ in the range 0 - 255. Immediately after switching on the controller, a request telegram for feedback of the product code and the serial number is sent to the room control unit at the interval ‘tPCTimeShort’ ( default: 5s ). After receiving a response telegram, the product code is checked and evaluated. A valid product code is output at the output ‘sProductCode’. Furthermore, the serial number of the room control unit is output at the output ‘sSerialNum’. The configuration of the room control unit is triggered if the serial number has changed ( directly after switching on the CPU or after replacing the room control unit ). After detection of a valid product code, the interval for sending a request telegram for feedback of the product code and the serial number is increased to ‘tPCTimeLong’ ( default: 60s ). If ten consecutive response telegrams with an incorrect product code or no response telegram at all are received within this interval, the detection cycle is executed again at the interval ‘tPCTimeShort’. \

Generation of the room setpoint temperature

The room setpoint temperature, which is displayed directly on the display of the room control unit and output at the output ‘rSetpTemp’, always corresponds to the state at input ‘rSetpTempBase’. It is limited by adjustable absolute minimum ( ‘rSetpTempMin’, default: 18.0 degrees Celsius ) and maximum values ( ‘rSetpTempMax’, default: 26.0 degrees Celsius ). No transfer of room setpoint temperatures outside these absolute limits takes place. \

Generation of the offset of the room setpoint temperature

The offset of the room setpoint temperature is influenced by the outputs ‘xButtonTempUp’ ( rising edge ) and ‘xButtonTempDown’ ( rising edge ). The current state is always shown at the output ‘rSetpTempOff’. The generation of the offset is enabled via the input ‘xEnSetpTempOff’ ( xEnSetpTempOff = TRUE ) and disabled ( xEnSetpTempOff = FALSE ). In the disabled state the value 0.0 is output at the output ‘rSetpTempOff’. In the enabled state the last set value is output at the output ‘rSetpTempOff’. In the enabled state the output ‘rSetpTempOff’ is increased by the parameter ‘rSetpTempOffVariat’ ( default: 0.5 K ) on each rising edge at the output ‘xButtonTempUp’. In the enabled state the output ‘rSetpTempOff’ is decreased by the parameter ‘rSetpTempOffVariat’ on each rising edge at the output ‘xButtonTempDown’. In the enabled state the output ‘rSetpTempOff’ is absolutely limited by the parameters ‘rSetpTempOffMin’ ( default: -3.0 K ) and ‘rSetpTempOffMax’ ( default: 3.0 K ). On any change of the parameters ‘rSetpTempOffVariat’, ‘rSetpTempOffMin’ and ‘rSetpTempOffMax’ the output ‘rSetpTempOff’ is reinitialized to 0.0. Outputs ‘xButtonTempUp’ and ‘xButtonTempDown’ The outputs are influenced by operating the buttons TBO and TB4 on the RBG and additionally by the inputs for the visualization ( ‘xVisuTempUp’ and ‘xVisuTempDown’ ) ( OR linkage ). Each short actuation of button TB0 ( increase temperature ) and TB4 ( decrease temperature ) triggers at the associated outputs ‘xButtonTempUp’ and ‘xButtonTempDown’ a pulse with duration ‘tTimeButtonPulse’ ( default: 1s ). \

Outputs ‘xButtonXXX’ ( not for ‘xButtonTempUp’ and ‘xButtonTempDown’ )

The outputs ‘xButtonXXX’ ( xButtonPresence, xButtonFanUp, xButtonFanDown, xButtonLightOn, xButtonLightOff, xButtonShadeUp and xButtonShadeDown ) are influenced by operating the corresponding buttons on the RBG and additionally by the inputs for the visualization ( ‘xVisuXXX’ ) ( OR linkage ). They can be operated on the RBG in two different operating modes ( selected via the parameters ‘ePresenceOutpMode’, ‘eFanOutpMode’, ‘eLightOutpMode’ and ‘eShadeOutpMode’ ). The selection of the operating mode is always made jointly for both outputs of a function. Operating modes RAW The outputs immediately take over the states of their assigned buttons ( button pressed >>> output = TRUE ). The arrangement of the buttons may differ depending on the type of the room control unit. If the buttons for the desired function are not present on the room control unit, the assigned outputs remain inactive ( = FALSE ). PULSE Each short actuation of the button triggers a pulse with duration ‘tTimeButtonPulse’ ( default: 1s ) at the associated output. \

Display of the fan level

The display of the fan level ( selected via the input ‘rSetpDispFanLev’ in the range 0.0 - 7.0 ) is shown by the right bargraph on the display of the room control unit, if the display is generally enabled ( parameter ‘xDispBargrFanLev’ = TRUE ).\

rSetpDispFanLev

Display

Notes

0

Level 0 - Manual

1

Level 1 - Manual

2

Level 2 - Manual

3

Level 3 - Manual

4

Level 0 - Automatic

5

Level 1 - Automatic

6

Level 2 - Automatic

7

Level 3 - Automatic

Display of heating/cooling power

The display of heating/cooling power ( selected via the input ‘rSetpDispHCLev’ in the range 0.0 - 7.0 ) is shown by the left bargraph on the display of the room control unit, if the display is generally enabled ( parameter ‘xDispBargrHCLev’ = TRUE ).\

rSetpDispHCLev

Display

Notes

0

Level 0 - Manual

1

Level 1 - Manual

2

Level 2 - Manual

3

Level 3 - Manual

4

Level 0 - Automatic

5

Level 1 - Automatic

6

Level 2 - Automatic

7

Level 3 - Automatic

Display of symbols

The display of the desired symbols on the display of the room control unit is triggered by the TRUE state at the assigned input. ( Example: xDsplSymbHeat = TRUE causes the static display of the ‘heating’ symbol on the display ). Inputs with the name suffix ‘–Al–’ cause a slowly blinking representation of the associated symbol. ( Example: xDsplSymbAlStorm = TRUE causes the slowly blinking display of the ‘windsock’ symbol on the display ).\

Resetting the room control unit

The room control unit is reset on each rising edge at the input ‘xResetDevice’. \

Control of the piezo buzzer in the room control unit

The static TRUE state at the input ‘xBuzzer_Alarm’ triggers an interrupted alarm tone with frequency 800 Hz in the room control unit. \

Display of faults

The display of faults is shown at the collective output ‘xAlarm’ ( = TRUE ). It includes communication faults ( time delay: gc_Parameters.gc_tOnDelayxAlarmCom, default = 60s ) and device faults ( immediate ). At the output ‘eErrorCodeCom’ an explanatory text for the cause is available in case of a communication error. It always shows the cause of the last communication error. At the output ‘eErrorCodeDev’ an explanatory text for the cause is available in case of a device error.\

Output ‘xConfig’

The output signals the configuration of the device ( = TRUE ) after it has been recognized ( see detection of the product code )\

Output ‘wDeviceMode’

The numeric value at this output indicates the current representation of the room control unit ( menu level, displayed content, password level, etc. ) It corresponds to the content of Modbus register 101, see the device documentation for this.\

Update of the outputs for button actuations ( 9 outputs )

The state of the output ‘xButtonXXX’ is formed from the OR linkage of the state due to operations on the room control unit ( ‘_xButtonXXX’ ) and due to operation in the visualization ( ‘xVisuXXX’ ).

Codesys

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enabled)

Input

byUnitId

BYTE

0

Address of the device ( 0 .. 255 )

Input

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge )

Input

xUpdateStates

BOOL

FALSE

Update of the states ( on every rising edge )

Input

xUpdateSetp

BOOL

FALSE

Update of setpoints (on every rising edge )

Input

xUpdateConfig

BOOL

FALSE

Update of the configuration ( on every rising edge )

Input

rSetpTempBase

REAL

22.0

Base setpoint temperature ( degrees Celsius )

Input

xEnSetpTempOff

BOOL

FALSE

Enable / disable detection of changes of the room setpoint temperature ( FALSE = no detection, rSetpTempOff = 0.0 K )

Input

rSetpDispFanLev

REAL

0.0

Setpoint for the display of the fan level ( bargraph - right )

Input

rSetpDispHCLev

REAL

0.0

Setpoint for the display of heating/cooling power ( bargraph - left )

Input

xDsplSymbPresen

BOOL

FALSE

Display of the symbols for presence ( = TRUE ) or absence ( = FALSE )

Input

xDsplSymbHeat

BOOL

FALSE

Display of the symbol for heating operation ( TRUE = display )

Input

xDsplSymbCool

BOOL

FALSE

Display of the symbol for cooling operation ( TRUE = display )

Input

xDsplSymbFan

BOOL

FALSE

Display of the symbol for the fan ( TRUE = display )

Input

xDsplSymbAlWindo

BOOL

FALSE

Display of the symbol for window - alarm ( TRUE = display )

Input

xDsplSymbAlRainf

BOOL

FALSE

Display of the symbol for rain - alarm ( TRUE = display )

Input

xDsplSymbAlStorm

BOOL

FALSE

Display of the symbol for wind - alarm ( TRUE = display )

Input

xDsplSymbAlAlarm

BOOL

FALSE

Display of the symbol for alarm ( TRUE = display )

Input

xDsplSymbNotDrop

BOOL

FALSE

Display of the symbol for the crossed-out drop ( TRUE = display )

Input

xDsplSymbClock

BOOL

FALSE

Display of the symbol for the clock ( TRUE = display )

Input

xBuzzer_Alarm

BOOL

FALSE

Enable / disable the alarm tone ( buzzer ) ( TRUE = enabled )

Input

xResetDevice

BOOL

FALSE

Reset of the device ( on each rising edge )

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

rSetpTemp

REAL

Set temperature ( degrees Celsius ) ( corresponds to the room setpoint temperature shown on the RBG )

Output

rSetpTempOff

REAL

Setpoint temperature offset ( Kelvin )( rSetpTempOff := rSetpTemp - rSetpTempBase )

Output

rRoomTemp

REAL

Room temperature in XXX.X degrees Celsius

Output

rExtTemp

REAL

External temperature in XXX.X degrees Celsius

Output

rRelHumidity

REAL

Relative room humidity in XXX.X %

Output

rDewPointTemp

REAL

Dew point temperature in XXX.X degrees Celsius ( The offsets of temperature and rel. humidity are not considered )

Output

xSensorOffsetInDevice

BOOL

Indicates whether sensor calibration must be performed in the device ( TRUE = calibration required in the device, FALSE = calibration required in the FB )

Output

rSupplyVolt

REAL

Supply voltage in XXX.X volts

Output

rCpuTemp

REAL

CPU temperature in XXX.X degrees Celsius

Output

rCpuVolt

REAL

CPU voltage in XXX.X volts

Output

sSerialNum

STRING

Serial number of the device

Output

sProductCode

STRING

Product code of the device ( e.g. ‘21X’ )

Output

wDeviceMode

WORD

Operating mode of the device

Output

xConfig

BOOL

FALSE

State of the device configuration [ TRUE = configuration active ]

Output

xButtonPresence

BOOL

FALSE

Actuation of the presence button ( RAW, pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

Output

xButtonTempUp

BOOL

FALSE

Actuation of the button to increase the setpoint temperature ( pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

Output

xButtonTempDown

BOOL

FALSE

Actuation of the button to decrease the setpoint temperature ( pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

Output

xButtonFanUp

BOOL

FALSE

Actuation of the button to increase the fan level ( RAW, pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

Output

xButtonFanDown

BOOL

FALSE

Actuation of the button to decrease the fan level ( RAW, pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

Output

xButtonLightOn

BOOL

FALSE

Actuation of the button to activate the lighting ( RAW, pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

Output

xButtonLightOff

BOOL

FALSE

Actuation of the button to deactivate the lighting ( RAW, pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

Output

xButtonShadeUp

BOOL

FALSE

Actuation of the button to open the shading ( RAW, pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

Output

xButtonShadeDown

BOOL

FALSE

Actuation of the button to close the shading ( RAW, pulse with duration ‘tTimeButtonPulse’ ) ( RBG and/or VISU )

Output

xStateExtBut0

BOOL

State of external input 0

Output

xStateExtBut1

BOOL

State of external input 1

Output

xStateExtBut2

BOOL

State of external input 2

Output

xStateExtBut3

BOOL

State of external input 3

Output

xAlarm

BOOL

FALSE

Collective fault (TRUE = fault)

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication (TRUE = fault)

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

Output

eErrorCodeDev

SPLUSS_ERROR_CODE_TYPE_2

Error code - device (0 = no error)

Output

xBusy

BOOL

Communication indicator (TRUE = communication)

Input Const

rRelHumidityOffset

REAL

0.0

Constant measurement offset for the transmitted relative humidity - actual value ( internal relative humidity )

Input Const

rExtTempOffset

REAL

0.0

Constant measurement offset for the transmitted temperature - actual value ( external temperature )

Input Const

rRoomTempOffset

REAL

0.0

Constant measurement offset for the transmitted temperature - actual value ( internal temperature )

Input Const

xVisuShadeDown

BOOL

FALSE

Actuation of the button to close the shading in the visualization

Input Const

xVisuShadeUp

BOOL

FALSE

Actuation of the button to open the shading in the visualization

Input Const

xVisuLightOff

BOOL

FALSE

Actuation of the button to deactivate the lighting in the visualization

Input Const

xVisuLightOn

BOOL

FALSE

Actuation of the button to activate the lighting in the visualization

Input Const

xVisuFanDown

BOOL

FALSE

Actuation of the button to decrease the fan level in the visualization

Input Const

xVisuFanUp

BOOL

FALSE

Actuation of the button to increase the fan level in the visualization

Input Const

xVisuTempDown

BOOL

FALSE

Actuation of the button to decrease the setpoint temperature in the visualization

Input Const

xVisuTempUp

BOOL

FALSE

Actuation of the button to increase the setpoint temperature in the visualization

Input Const

xVisuPresence

BOOL

FALSE

Actuation of the presence button in the visualization

Input Const

eShadeOutpMode

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.RAW

Operating mode of the outputs ‘xButtonShadeUp’ and ‘xButtonShadeDwn’ ( RAW, PULSE )

Input Const

eLightOutpMode

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE

Operating mode of the outputs ‘xButtonLightOn’ and ‘xButtonLightOff’ ( RAW, PULSE )

Input Const

eFanOutpMode

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE

Operating mode of the outputs ‘xButtonFanUp’ and ‘xButtonFanDwn’ ( RAW, PULSE )

Input Const

ePresenceOutpMode

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE

Operating mode of the output ‘xButtonPresence’ ( RAW, PULSE )

Input Const

xDispBargrHCLev

BOOL

FALSE

Enable / disable the display of the left bargraph ( FALSE = no display )

Input Const

xDispBargrFanLev

BOOL

FALSE

Enable / disable the display of the right bargraph ( FALSE = no display )

Input Const

eColorScheme

SPLUSS_LCD_COLOR_SCHEME

SPLUSS_LCD_COLOR_SCHEME.WHITE

Number of the color scheme ( 1 = white, 1-7 = valid numbers )

Input Const

wPinCodeEndUser

WORD

3333

PIN code for the user level ( 0 = no code, 0001 - 9999 valid code )

Input Const

wPinCodeAdmin

WORD

7458

PIN code for the administrator level ( 0 = no code, 0001 - 9999 valid code )

Input Const

rSetpTempOffVariat

REAL

0.5

Step size of the setpoint temperature offset ( Kelvin )

Input Const

rSetpTempOffMax

REAL

3.0

Absolute maximum value of the setpoint temperature offset ( Kelvin )

Input Const

rSetpTempOffMin

REAL

-3.0

Absolute minimum value of the setpoint temperature offset ( Kelvin )

Input Const

rSetpTempMax

REAL

26.0

Absolute maximum - setpoint temperature ( degrees Celsius )

Input Const

rSetpTempMin

REAL

18.0

Absolute minimum - setpoint temperature ( degrees Celsius )

Input Const

tTimeButtonPulse

TIME

TIME#1s0ms

Duration of the pulse on the output if the associated button was pressed briefly

Input Const

tPCTimeShort

TIME

TIME#5s0ms

Interval duration of the scan process to determine the product code ( short duration, device not yet recognized )

Input Const

tPCTimeLong

TIME

TIME#1m0s0ms

Interval duration of the scan process to determine the product code ( long duration, device recognized )

Input Const

tTimeUpdateConfig

TIME

TIME#0ms

Update interval for the processes influenced by the input ‘xUpdateConfig’

Input Const

tTimeUpdateSetp

TIME

TIME#45s0ms

Update interval for the operations affected by the input 'xUpdateSetp'

Input Const

tTimeUpdateStates

TIME

TIME#500ms

Update interval for the processes influenced by the input ‘xUpdateStates’

Input Const

tTimeUpdateActual

TIME

TIME#3s0ms

Update interval for the operations affected by the input 'xUpdateActual'

Last updated