SPLUSS_RYMASKON_2XX_MOD

SPLUSS_RYMASKON_2XX_MOD (FB)

FUNCTION_BLOCK SPLUSS_RYMASKON_2XX_MOD

Short description

Control of the Rymaskon 2XX device series by S+S Regeltechnik Additional functions: Two operating modes for setpoint temperature formation Typical application: room control unit in one zone

Representation

Interfaces

Inputs

Name
Data type
Value range
Initial value
Function

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enable)

byUnitId

BYTE

0

Device address (0 .. 255)

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge)

xUpdateStates

BOOL

FALSE

Update of states (on every rising edge)

xUpdateSetp

BOOL

FALSE

Update of setpoints (on every rising edge)

xUpdateConfig

BOOL

FALSE

Update of configuration (on every rising edge)

rSetpTempBase

REAL

22.0

Base setpoint temperature (degrees Celsius)

rEnSetpTempOff

BOOL

FALSE

Enable / disable recording of changes to the room setpoint temperature (FALSE = no recording, rSetpTempOff = 0.0 K)

rSetpDispFanLev

REAL

0.0

Setpoint for the display of the fan stage (bar graph - right)

rSetpDispHCLev

REAL

0.0

Setpoint for the display of heating/cooling output (bar graph - left)

xDsplSymbPresen

BOOL

FALSE

Display of the symbols for presence (= TRUE) or absence (= FALSE)

xDsplSymbHeat

BOOL

FALSE

Display of the symbol for heating operation (TRUE = display)

xDsplSymbCool

BOOL

FALSE

Display of the symbol for cooling operation (TRUE = display)

xDsplSymbFan

BOOL

FALSE

Display of the symbol for the fan (TRUE = display)

xDsplSymbAlWindo

BOOL

FALSE

Display of the window alarm symbol (TRUE = display)

xDsplSymbAlRainf

BOOL

FALSE

Display of the rain alarm symbol (TRUE = display)

xDsplSymbAlStorm

BOOL

FALSE

Display of the wind alarm symbol (TRUE = display)

xDsplSymbAlAlarm

BOOL

FALSE

Display of the alarm symbol (TRUE = display)

xDsplSymbNotDrop

BOOL

FALSE

Display of the crossed-out drop symbol (TRUE = display)

xDsplSymbClock

BOOL

FALSE

Display of the clock symbol (TRUE = display)

xBuzzer_Alarm

BOOL

FALSE

Enable / disable the alarm tone (buzzer) (TRUE = enable)

xResetDevice

BOOL

FALSE

Reset of the device (on every rising edge)

Outputs

Name
Data type
Value range
Initial value
Function

rSetpTemp

REAL

Set temperature (degrees Celsius) (corresponds to the room setpoint temperature shown on the RBG)

rSetpTempOff

REAL

Set temperature offset (Kelvin)

rRoomTemp

REAL

Room temperature in XXX.X degrees Celsius

rExtTemp

REAL

External temperature in XXX.X degrees Celsius

rRelHumidity

REAL

Relative room humidity in XXX.X %

rDewPointTemp

REAL

Dew point temperature in XXX.X degrees Celsius (the offsets of temperature and relative humidity are not taken into account)

rSupplyVolt

REAL

Supply voltage in XXX.X Volts

rCpuTemp

REAL

CPU temperature in XXX.X degrees Celsius

rCpuVolt

REAL

CPU voltage in XXX.X Volts

sSerialNum

STRING

Serial number of the device

sProductCode

STRING

Product code of the device (e.g. 21X)

xConfig

BOOL

State of the device configuration [ TRUE = configuration active ]

xButtonPresence

BOOL

Pressing the presence button (RBG (= room control unit): RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)

xButtonTempUp

BOOL

Pressing the button to increase the set temperature (RBG: pulse with duration tTimeButtonPulse) (RBG and/or VISU)

xButtonTempDown

BOOL

Pressing the button to decrease the set temperature (RBG: pulse with duration tTimeButtonPulse) (RBG and/or VISU)

xButtonFanUp

BOOL

Pressing the button to increase the fan stage (RBG: RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)

xButtonFanDown

BOOL

Pressing the button to decrease the fan stage (RBG: RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)

xButtonLightOn

BOOL

Pressing the button to activate the lighting (RBG: RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)

xButtonLightOff

BOOL

Pressing the button to deactivate the lighting (RBG: RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)

xButtonShadeUp

BOOL

Pressing the button to open the shading (RBG: RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)

xButtonShadeDown

BOOL

Pressing the button to close the shading (RBG: RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)

xStateExtBut0

BOOL

State of external input 0

xStateExtBut1

BOOL

State of external input 1

xStateExtBut2

BOOL

State of external input 2

xStateExtBut3

BOOL

State of external input 3

xAlarm

BOOL

Collective fault (TRUE = fault)

xAlarmCom

BOOL

Collective fault - communication (TRUE = fault)

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

eErrorCodeDev

SPLUSS_ERROR_CODE_TYPE_2

Error code - device (0 = no error)

xBusy

BOOL

Communication indicator (TRUE = communication)

Inputs and outputs

Name
Data type
Value range
Initial value
Function

ModbusClient

ModbusClientBase

Client of the device

Setpoints / parameters

Name
Data type
Value range
Initial value
Function

tTimeUpdateActual

TIME

T#3s

Update interval for the processes influenced by the input xUpdateActual are affected (0 = no automatic update, > 0 cyclical update)

tTimeUpdateStates

TIME

T#500ms

Update interval for the processes influenced by the input xUpdateStates are affected (0 = no automatic update, > 0 cyclical update)

tTimeUpdateSetp

TIME

T#0s

Update interval for the processes influenced by the input xUpdateSetp are affected (0 = no automatic update, > 0 cyclical update)

tTimeUpdateConfig

TIME

T#0s

Update interval for the processes influenced by the input xUpdateConfig are affected (0 = no automatic update, > 0 cyclical update)

tPCTimeLong

TIME

T#60s

Interval time of the scan process for determining the product code (long duration, device detected)

tPCTimeShort

TIME

T#5s

Interval time of the scan process for determining the product code (short duration, device not yet detected)

tTimeButtonPulse

TIME

T#1s

Duration of the pulse at the output if the assigned button was pressed briefly

rSetpTempMin

REAL

18.0

Absolute minimum value - setpoint temperature (degrees Celsius)

rSetpTempMax

REAL

26.0

Absolute maximum value - setpoint temperature (degrees Celsius)

rSetpTempOffMin

REAL

-3.0

Absolute minimum value of the set temperature offset (Kelvin)

rSetpTempOffMax

REAL

3.0

Absolute maximum value of the set temperature offset (Kelvin)

rSetpTempVariat

REAL

0.5

Step size of the set temperature offset (Kelvin)

wPinCodeAdmin

WORD

7458

PIN code for the administrator level (0 = no code, 0001 - 9999 valid code)

wPinCodeEndUser

WORD

3333

PIN code for the user level (0 = no code, 0001 - 9999 valid code)

eColorScheme

SPLUSS_LCD_COLOR_SCHEME

SPLUSS_LCD_COLOR_SCHEME.WHITE

Number of the color scheme (1 = white, 1-7 = valid numbers)

xDispBargrFanLev

BOOL

FALSE

Enable / disable the display of the right bar graph (FALSE = no display)

xDispBargrHCLev

BOOL

FALSE

Enable / disable the display of the left bar graph (FALSE = no display)

ePresenceOutpMode

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE

Operating mode of the output xButtonPresence (RAW, PULSE)

eFanOutpMode

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE

Operating mode of the outputs xButtonFanUp or xButtonFanDwn (RAW, PULSE)

eLightOutpMode

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE

Operating mode of the outputs xButtonLightOn or xButtonLightOff (RAW, PULSE)

eShadeOutpMode

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.RAW

Operating mode of the outputs xButtonShadeUp or xButtonShadeDwn (RAW, PULSE)

xVisuPresence

BOOL

FALSE

Pressing the presence button in the visualization

xVisuTempUp

BOOL

FALSE

Pressing the button to increase the set temperature in the visualization

xVisuTempDown

BOOL

FALSE

Pressing the button to decrease the set temperature in the visualization

xVisuFanUp

BOOL

FALSE

Pressing the button to increase the fan stage in the visualization

xVisuFanDown

BOOL

FALSE

Pressing the button to decrease the fan stage in the visualization

xVisuLightOn

BOOL

FALSE

Pressing the button to activate the lighting in the visualization

xVisuLightOff

BOOL

FALSE

Pressing the button to deactivate the lighting in the visualization

xVisuShadeUp

BOOL

FALSE

Pressing the button to open the shading in the visualization

xVisuShadeDown

BOOL

FALSE

Pressing the button to close the shading in the visualization

Function description

General

This function block controls room control units of the Rymaskon 2XX device series by S+S Regeltechnik via Modbus communication. Alternatively, room control units from Loytec can also be used. The different types (21x - 26x) of room control units are detected automatically. After detection, the room control units are automatically configured sensibly according to type. Two operating modes are provided for forming the room setpoint temperature (MANUALLY, AUTOMATICALLY). For different outputs (xButtonXXX), two operating modes are also provided (RAW, PULSE) (valid only when operated via the room control unit)

Detection of the product code (of the device type)

The Modbus address of the room control unit for communication with this function block is set at input byUnitId in the range 0 - 255. Immediately after the controller is switched on, at intervals tPCTimeShort (default: 5s) a request telegram is sent to the room control unit each time to return the product code and serial number. After receiving a response telegram, the product code is checked and evaluated. A valid product code is output at the output sProductCode . In addition, the serial number of the room control unit is output at the output sSerialNum . The configuration of the room control unit is triggered if the serial number has changed (directly after the CPU is switched on or after the room control unit has been replaced). After detection of a valid product code, the interval for sending a request telegram to return the product code and serial number is increased to tPCTimeLong (default: 60s). If ten consecutive response telegrams with an incorrect product code or no response telegrams at all are received within this interval, the detection cycle is executed again at interval tPCTimeShort .

Formation of the room setpoint temperature

The room setpoint temperature, which is displayed directly on the room control unit display and output at output rSetpTemp always corresponds to the state at input rSetpTempBase. It is limited by adjustable absolute minimum (rSetpTempMin, default: 18.0 degrees Celsius) and maximum values (rSetpTempMax, default: 26.0 degrees Celsius). No transfer of room setpoint temperatures outside these absolute limits takes place.

Formation of the offset of the room setpoint temperature

The offset of the room setpoint temperature is influenced by outputs xButtonTempUp (rising edge) and xButtonTempDown (rising edge). The current state is always displayed at output rSetpTempOff . The formation of the offset is enabled via input xEnSetpTempOff and disabled (xEnSetpTempOff = FALSE). In the disabled state, the value 0.0 is output at output rSetpTempOff . In the enabled state, the last set value is output at output rSetpTempOff . In the enabled state, output rSetpTempOff is increased by the parameter xButtonTempUp rSetpTempOffVariat (default: 0.5 K) on every rising edge at output . In the enabled state, output rSetpTempOff is increased by the parameter xButtonTempDown rSetpTempOffVariat (default: 0.5 K) on every rising edge at output is reduced. In the enabled state, output rSetpTempOff is limited in absolute terms by the parameters rSetpTempOffMin (default: -3.0 K) and rSetpTempOffMax (default: 3.0 K). Whenever the parameters (default: 0.5 K) on every rising edge at output, rSetpTempOffMin and rSetpTempOffMax change, output rSetpTempOff is reinitialized to 0.0.

Outputs xButtonTempUp and xButtonTempDown

The outputs are influenced by operating the TBO or TB4 buttons on the RBG and additionally by the inputs for the visualization (xVisuTempUp and xVisuTempDown) (OR linkage). Each brief press of button TB0 (increase temperature) and TB4 (decrease temperature) triggers a pulse of duration xButtonTempUp and xButtonTempDown at the associated outputs tTimeButtonPulse (default: 1s).

Outputs xButtonXXX (not for xButtonTempUp and xButtonTempDown)

The outputs xButtonXXX (xButtonPresence, xButtonFanUp, xButtonFanDown, xButtonLightOn, xButtonLightOff, xButtonShadeUp and xButtonShadeDown) are influenced by operating the corresponding buttons on the RBG and additionally by the inputs for the visualization (xVisuXXX) (OR linkage).

They can be operated on the RBG in two different operating modes (selection via parameters ePresenceOutpMode, eFanOutpMode, eLightOutpMode and eShadeOutpMode). The operating mode is always selected jointly for both outputs of a function.

Operating modes

RAW

The outputs immediately adopt the states of their assigned buttons (button pressed >>> output = TRUE). The arrangement of the buttons may differ depending on the type of room control unit. If the buttons for the desired function are not present on the room control unit, the assigned outputs remain inactive (= FALSE).

PULSE

Each brief press of the button triggers a pulse of duration at the associated output tTimeButtonPulse (default: 1s).

Display of fan stage

The display of the fan stage (selection via input rSetpDispFanLev in the range 0.0 - 7.0) is shown by the right bar graph on the display of the room control unit, if the display is generally enabled (parameter xDispBargrFanLev = TRUE).

rSetpDispFanLev

Display

Notes

0

Stage 0 - Manual

1

Stage 1 - Manual

2

Stage 2 - Manual

3

Stage 3 - Manual

4

Stage 0 - Automatic

5

Stage 1 - Automatic

6

Stage 2 - Automatic

7

Stage 3 - Automatic

Display of heating/cooling output

The display of the heating/cooling output (selection via input rSetpDispHCLev in the range 0.0 - 7.0) is shown by the left bar graph on the display of the room control unit, if the display is generally enabled (parameter xDispBargrHCLev = TRUE).

rSetpDispHCLev

Display

Notes

0

Stage 0 - Manual

1

Stage 1 - Manual

2

Stage 2 - Manual

3

Stage 3 - Manual

4

Stage 0 - Automatic

5

Stage 1 - Automatic

6

Stage 2 - Automatic

7

Stage 3 - Automatic

Display of symbols

The display of the desired symbols on the room control unit display is triggered by the TRUE state at the associated input. (Example: xDsplSymbHeat = TRUE causes the static display of the symbol Heating in the display). Inputs with the name suffix ‘-Al-’ cause a slowly blinking display of the associated symbol. (Example: xDsplSymbAlStorm = TRUE causes the slowly blinking display of the symbol windsock in the display).

Resetting the room control unit

The room control unit is reset on every rising edge at input xResetDevice .

Control of the piezo buzzer in the room control unit

The static TRUE state at input xBuzzer_Alarm triggers an intermittent alarm tone at a frequency of 800 Hz in the room control unit.

Display of faults

Faults are displayed at the collective output xAlarm (= TRUE). It includes communication faults (time delay: gc_Parameters.gc_tOnDelayxAlarmCom, default = 60s) and device faults (direct). At output eErrorCodeCom an explanatory text for the cause is available in the event of a communication error. It always shows the cause of the last communication error there. At output eErrorCodeDev an explanatory text for the cause is available in the event of a device error.

Output xConfig

The output signals the configuration of the device (= TRUE) after it has been detected (see detection of the product code)

Output wDeviceMode

The numerical value at this output identifies the current display of the room control unit (menu level, display content, password level, etc.). It corresponds to the content of Modbus register 101, see the device documentation.

Update of the outputs for button presses (9 outputs)

The state of output xButtonXXX is formed from the OR linkage of the state based on operation on the room control unit (_xButtonXXX) and based on operation in the visualization (xVisuXXX).

Codesys

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enable)

Input

byUnitId

BYTE

0

Device address (0 .. 255)

Input

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge )

Input

xUpdateStates

BOOL

FALSE

Update of the states (on each rising edge)

Input

xUpdateSetp

BOOL

FALSE

Update of setpoints (on every rising edge )

Input

xUpdateConfig

BOOL

FALSE

Update of the configuration (on each rising edge)

Input

rSetpTempBase

REAL

22.0

Base setpoint temperature (degrees Celsius)

Input

xEnSetpTempOff

BOOL

FALSE

Enable / disable recording of changes to the room setpoint temperature (FALSE = no recording, rSetpTempOff = 0.0 K)

Input

rSetpDispFanLev

REAL

0.0

Setpoint for the display of the fan stage (bar graph - right)

Input

rSetpDispHCLev

REAL

0.0

Setpoint for the display of heating/cooling output (bar graph - left)

Input

xDsplSymbPresen

BOOL

FALSE

Display of the symbols for presence (= TRUE) or absence (= FALSE)

Input

xDsplSymbHeat

BOOL

FALSE

Display of the symbol for heating operation (TRUE = display)

Input

xDsplSymbCool

BOOL

FALSE

Display of the symbol for cooling operation (TRUE = display)

Input

xDsplSymbFan

BOOL

FALSE

Display of the symbol for the fan (TRUE = display)

Input

xDsplSymbAlWindo

BOOL

FALSE

Display of the window alarm symbol (TRUE = display)

Input

xDsplSymbAlRainf

BOOL

FALSE

Display of the rain alarm symbol (TRUE = display)

Input

xDsplSymbAlStorm

BOOL

FALSE

Display of the wind alarm symbol (TRUE = display)

Input

xDsplSymbAlAlarm

BOOL

FALSE

Display of the alarm symbol (TRUE = display)

Input

xDsplSymbNotDrop

BOOL

FALSE

Display of the crossed-out drop symbol (TRUE = display)

Input

xDsplSymbClock

BOOL

FALSE

Display of the clock symbol (TRUE = display)

Input

xBuzzer_Alarm

BOOL

FALSE

Enable / disable the alarm tone (buzzer) (TRUE = enable)

Input

xResetDevice

BOOL

FALSE

Reset of the device (on every rising edge)

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

rSetpTemp

REAL

Set temperature (degrees Celsius) (corresponds to the room setpoint temperature shown on the RBG)

Output

rSetpTempOff

REAL

Set temperature offset (Kelvin) (rSetpTempOff:= rSetpTemp - rSetpTempBase)

Output

rRoomTemp

REAL

Room temperature in XXX.X degrees Celsius

Output

rExtTemp

REAL

External temperature in XXX.X degrees Celsius

Output

rRelHumidity

REAL

Relative room humidity in XXX.X %

Output

rDewPointTemp

REAL

Dew point temperature in XXX.X degrees Celsius (the offsets of temperature and relative humidity are not taken into account)

Output

xSensorOffsetInDevice

BOOL

Indication of whether the sensors must be calibrated in the device (TRUE = calibration in the device required, FALSE = calibration in the FB required)

Output

rSupplyVolt

REAL

Supply voltage in XXX.X Volts

Output

rCpuTemp

REAL

CPU temperature in XXX.X degrees Celsius

Output

rCpuVolt

REAL

CPU voltage in XXX.X Volts

Output

sSerialNum

STRING

Serial number of the device

Output

sProductCode

STRING

Product code of the device (e.g. 21X)

Output

wDeviceMode

WORD

Operating mode of the device

Output

xConfig

BOOL

FALSE

State of the device configuration [ TRUE = configuration active ]

Output

xButtonPresence

BOOL

FALSE

Pressing the presence button (RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)

Output

xButtonTempUp

BOOL

FALSE

Pressing the button to increase the set temperature (pulse with duration tTimeButtonPulse) (RBG and/or VISU)

Output

xButtonTempDown

BOOL

FALSE

Pressing the button to decrease the set temperature (pulse with duration tTimeButtonPulse) (RBG and/or VISU)

Output

xButtonFanUp

BOOL

FALSE

Pressing the button to increase the fan stage (RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)

Output

xButtonFanDown

BOOL

FALSE

Pressing the button to decrease the fan stage (RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)

Output

xButtonLightOn

BOOL

FALSE

Pressing the button to activate the lighting (RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)

Output

xButtonLightOff

BOOL

FALSE

Pressing the button to deactivate the lighting (RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)

Output

xButtonShadeUp

BOOL

FALSE

Pressing the button to open the shading (RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)

Output

xButtonShadeDown

BOOL

FALSE

Pressing the button to close the shading (RAW, pulse with duration tTimeButtonPulse) (RBG and/or VISU)

Output

xStateExtBut0

BOOL

State of external input 0

Output

xStateExtBut1

BOOL

State of external input 1

Output

xStateExtBut2

BOOL

State of external input 2

Output

xStateExtBut3

BOOL

State of external input 3

Output

xAlarm

BOOL

FALSE

Collective fault (TRUE = fault)

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication (TRUE = fault)

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

Output

eErrorCodeDev

SPLUSS_ERROR_CODE_TYPE_2

Error code - device (0 = no error)

Output

xBusy

BOOL

Communication indicator (TRUE = communication)

Input Const

rRelHumidityOffset

REAL

0.0

Constant measured-value offset for the transmitted relative humidity actual value (internal relative humidity)

Input Const

rExtTempOffset

REAL

0.0

Constant measured-value offset for the transmitted temperature actual value (external temperature)

Input Const

rRoomTempOffset

REAL

0.0

Constant measured-value offset for the transmitted temperature actual value (internal temperature)

Input Const

xVisuShadeDown

BOOL

FALSE

Pressing the button to close the shading in the visualization

Input Const

xVisuShadeUp

BOOL

FALSE

Pressing the button to open the shading in the visualization

Input Const

xVisuLightOff

BOOL

FALSE

Pressing the button to deactivate the lighting in the visualization

Input Const

xVisuLightOn

BOOL

FALSE

Pressing the button to activate the lighting in the visualization

Input Const

xVisuFanDown

BOOL

FALSE

Pressing the button to decrease the fan stage in the visualization

Input Const

xVisuFanUp

BOOL

FALSE

Pressing the button to increase the fan stage in the visualization

Input Const

xVisuTempDown

BOOL

FALSE

Pressing the button to decrease the set temperature in the visualization

Input Const

xVisuTempUp

BOOL

FALSE

Pressing the button to increase the set temperature in the visualization

Input Const

xVisuPresence

BOOL

FALSE

Pressing the presence button in the visualization

Input Const

eShadeOutpMode

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.RAW

Operating mode of the outputs xButtonShadeUp or xButtonShadeDwn (RAW, PULSE)

Input Const

eLightOutpMode

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE

Operating mode of the outputs xButtonLightOn or xButtonLightOff (RAW, PULSE)

Input Const

eFanOutpMode

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE

Operating mode of the outputs xButtonFanUp or xButtonFanDwn (RAW, PULSE)

Input Const

ePresenceOutpMode

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE

SPLUSS_RYMASKON_2XX_BUTTON_OUTP_MODE.PULSE

Operating mode of the output xButtonPresence (RAW, PULSE)

Input Const

xDispBargrHCLev

BOOL

FALSE

Enable / disable the display of the left bar graph (FALSE = no display)

Input Const

xDispBargrFanLev

BOOL

FALSE

Enable / disable the display of the right bar graph (FALSE = no display)

Input Const

eColorScheme

SPLUSS_LCD_COLOR_SCHEME

SPLUSS_LCD_COLOR_SCHEME.WHITE

Number of the color scheme (1 = white, 1-7 = valid numbers)

Input Const

wPinCodeEndUser

WORD

3333

PIN code for the user level (0 = no code, 0001 - 9999 valid code)

Input Const

wPinCodeAdmin

WORD

7458

PIN code for the administrator level (0 = no code, 0001 - 9999 valid code)

Input Const

(default: 0.5 K) on every rising edge at output

REAL

0.5

Step size of the set temperature offset (Kelvin)

Input Const

rSetpTempOffMax

REAL

3.0

Absolute maximum value of the set temperature offset (Kelvin)

Input Const

rSetpTempOffMin

REAL

-3.0

Absolute minimum value of the set temperature offset (Kelvin)

Input Const

rSetpTempMax

REAL

26.0

Absolute maximum value - setpoint temperature (degrees Celsius)

Input Const

rSetpTempMin

REAL

18.0

Absolute minimum value - setpoint temperature (degrees Celsius)

Input Const

tTimeButtonPulse

TIME

TIME#1s0ms

Duration of the pulse at the output if the assigned button was pressed briefly

Input Const

tPCTimeShort

TIME

TIME#5s0ms

Interval time of the scan process for determining the product code (short duration, device not yet detected)

Input Const

tPCTimeLong

TIME

TIME#1m0s0ms

Interval time of the scan process for determining the product code (long duration, device detected)

Input Const

tTimeUpdateConfig

TIME

TIME#0ms

Update interval for the processes influenced by the input xUpdateConfig influenced

Input Const

tTimeUpdateSetp

TIME

TIME#45s0ms

Update interval for the processes influenced by the input xUpdateSetp influenced

Input Const

tTimeUpdateStates

TIME

TIME#500ms

Update interval for the processes influenced by the input xUpdateStates influenced

Input Const

tTimeUpdateActual

TIME

TIME#3s0ms

Update interval for the processes influenced by the input xUpdateActual influenced

Last updated