SPLUSS_RFTM_LQ_PS_CO2_WITHOUT_POT_REV2022_MOD
SPLUSS_RFTM_LQ_PS_CO2_WITHOUT_POT_REV2022_MOD (FB)
SPLUSS_RFTM_LQ_PS_CO2_WITHOUT_POT_REV2022_MOD (FB)FUNCTION_BLOCK SPLUSS_RFTM_LQ_PS_CO2_WITHOUT_POT_REV2022_MOD
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Address of the device
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoint values (on every rising edge )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rCO2_4s
REAL
CO2 concentration filtered 4s in XXXX ppm (350 - 5000 ppm )
Output
rCO2_32s
REAL
CO2 concentration filtered 32s in XXXX ppm (350 - 5000 ppm )
Output
rVOC_4s
REAL
Air quality filtered 4s in XXX.X % VOC (0.0 - 100.0 %)
Output
rVOC_32s
REAL
Air quality filtered 32s in XXX.X % VOC (0.0 - 100.0 %)
Output
rTemp_4s
REAL
Temperature filtered 4s in XX.X degrees Celsius (0.0 - +50.0 °C )
Output
rTemp_32s
REAL
Temperature filtered 32s in XX.X degrees Celsius (0.0 - +50.0 °C )
Output
rrH_4s
REAL
Relative humidity filtered 4s in XX.X % RH (0.0 - 100.0 %)
Output
rrH_32s
REAL
Relative humidity filtered 32s in XX.X % RH (0.0 - 100.0 % )
Output
rPM_4s
REAL
Particle concentration filtered 4s in µg/m3 (0 - 1000 µg/m3 )
Output
rPM_32s
REAL
Particle concentration filtered 32s in µg/m3 (0 - 1000 µg/m3 )
Output
xSensorOffsetInDevice
BOOL
Indicator whether the calibration of the sensors must be performed in the device (TRUE = calibration in device required, FALSE = calibration in FB required)
Output
xAutoZeroAct
BOOL
Indication of execution of an auto-zero function ( TRUE = function active )
Output
xAlarm
BOOL
FALSE
General fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
General fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
eErrorCodeDev
SPLUSS_ERROR_CODE_TYPE_1
Error code - device (0 = no error)
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
rPMOffset
REAL
0.0
Constant measurement offset for the transmitted particle concentration actual value
Input Const
rrHOffset
REAL
0.0
Constant measurement offset for the transmitted relative humidity actual value
Input Const
rTempOffset
REAL
0.0
Constant measurement offset for the transmitted temperature - actual value
Input Const
rVOCOffset
REAL
0.0
Constant measurement offset for the transmitted air quality actual value
Input Const
rCO2Offset
REAL
0.0
Constant measurement offset for the transmitted CO2 actual value (positive / negative integers)
Input Const
xDisplayAvailable
BOOL
FALSE
Option 'Display' ( TRUE = The device is equipped with a display )
Input Const
xEn_VOC
BOOL
FALSE
Enable option 'VOC sensor present' (TRUE = VOC sensor is present)
Input Const
xEn_CO2
BOOL
FALSE
Enable option 'CO2 sensor present' (TRUE = CO2 sensor is present)
Input Const
xAutoCalCO2
BOOL
FALSE
Enable automatic calibration of the CO2 measurement value ( FALSE = no automatic calibration)
Input Const
xAutoZeroVOC
BOOL
FALSE
Reset of the VOC measurement value (on each rising edge)
Input Const
xAutoZeroCO2
BOOL
FALSE
Reset of the CO2 measurement value (on each rising edge)
Input Const
eSensVOC
SPLUSS_VOC_SENSIBILITY
SPLUSS_VOC_SENSIBILITY.MEDIUM
Sensitivity of the VOC sensor (1 = low, 2 = medium, 3 = high)
Input Const
tTimeUpdateSetp
TIME
TIME#0ms
Update interval for operations influenced by the input 'xUpdateSetp'
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for operations influenced by the input 'xUpdateActual'