> For the complete documentation index, see [llms.txt](https://support.powerio.com/hub/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://support.powerio.com/hub/codesys-hvac/en/hvac-modbus-library/functionblocks/spluss/spluss_8147_mod_lcd.md).

# SPLUSS\_8147\_MOD\_LCD

## `SPLUSS_8147_MOD_LCD` (FB)

`FUNCTION_BLOCK` SPLUSS\_8147\_MOD\_LCD

### Representation

<figure><img src="https://2592874069-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FQR4vCFzt6ixgsqlR3pdR%2Fuploads%2FYX3ATYtmuRToVVJow2EF%2FHVACModbus.SPLUSS_8147_MOD_LCD.png?alt=media&amp;token=b7c3e410-aba1-42fe-afdd-e77edacb3bbf" alt=""><figcaption></figcaption></figure>

InOut:

| Scope       | Name                    | Type                         | Initial         | Comment                                                                                                                                                          |
| ----------- | ----------------------- | ---------------------------- | --------------- | ---------------------------------------------------------------------------------------------------------------------------------------------------------------- |
| Input       | `xEn`                   | `BOOL`                       | TRUE            | Enable / disable communication (TRUE = enable)                                                                                                                   |
| Input       | `byUnitId`              | `BYTE`                       | 0               | Address of the device                                                                                                                                            |
| Input       | `xUpdateActual`         | `BOOL`                       | FALSE           | <p>Update of actual values (on every rising edge<br>)</p>                                                                                                        |
| Input       | `xUpdateSetp`           | `BOOL`                       | FALSE           | <p>Update of setpoints (on every rising edge<br>)</p>                                                                                                            |
| Input       | `xUpdateConfig`         | `BOOL`                       | FALSE           | <p>Configuration update (on every rising<br>edge)</p>                                                                                                            |
| Inout       | `ModbusClient`          | `ModbusClientBase`           |                 | Client of the device                                                                                                                                             |
| Output      | `rDifPressure`          | `REAL`                       |                 | Differential pressure unfiltered in XXXX Pa                                                                                                                      |
| Output      | `rDifPressure_1s`       | `REAL`                       |                 | Differential pressure filtered 1 s in XXXX Pa                                                                                                                    |
| Output      | `rDifPressure_10s`      | `REAL`                       |                 | Differential pressure filtered 10 s in XXXX Pa                                                                                                                   |
| Output      | `xAutoZeroAct`          | `BOOL`                       |                 | <p>Display of execution of an Auto-Zero function (TRUE =<br>function active)</p>                                                                                 |
| Output      | `rTemp_4s`              | `REAL`                       |                 | Temperature filtered 4s in XX.X degrees Celsius                                                                                                                  |
| Output      | `rTemp_32s`             | `REAL`                       |                 | Temperature filtered 32s in XX.X degrees Celsius                                                                                                                 |
| Output      | `rrH_4s`                | `REAL`                       |                 | Relative humidity filtered 4s in XX.X % rF                                                                                                                       |
| Output      | `rrH_32s`               | `REAL`                       |                 | Relative humidity filtered 32s in XX.X % rF                                                                                                                      |
| Output      | `rVolumeFlow`           | `REAL`                       |                 | Volume flow calculated in XXXXX m3/h                                                                                                                             |
| Output      | `rDewpointTemp`         | `REAL`                       |                 | Dew point temperature in XXX.X degrees Celsius                                                                                                                   |
| Output      | `rAbsH_M3`              | `REAL`                       |                 | Absolute humidity in XX.X g/m3                                                                                                                                   |
| Output      | `rMixRatio`             | `REAL`                       |                 | Mixing ratio in XXX.X g water/kg dry air                                                                                                                         |
| Output      | `rEnthalpy`             | `REAL`                       |                 | Enthalpy in XXX.X kJ/kg                                                                                                                                          |
| Output      | `rairtight`             | `REAL`                       |                 | Air density in XXX.X kg/m3                                                                                                                                       |
| Output      | `xSensorOffsetInDevice` | `BOOL`                       |                 | <p>Indication whether the sensors must be calibrated in the device<br>(TRUE = calibration in the device required, FALSE = calibration in<br>the FB required)</p> |
| Output      | `xAlarm`                | `BOOL`                       | FALSE           | Collective fault (TRUE = fault)                                                                                                                                  |
| Output      | `xAlarmCom`             | `BOOL`                       | FALSE           | Collective fault - communication (TRUE = fault)                                                                                                                  |
| Output      | `eErrorCodeCom`         | ModbusErrorCode              |                 | Error code - communication (0 = no error)                                                                                                                        |
| Output      | `eErrorCodeDev`         | SPLUSS\_ERROR\_CODE\_TYPE\_1 |                 | Error code - device (0 = no error)                                                                                                                               |
| Output      | `xBusy`                 | `BOOL`                       |                 | Communication indicator (TRUE = communication)                                                                                                                   |
| Input Const | `rAltitude`             | `REAL`                       | 500.0           | Altitude above sea level (range: -500 … 5000 meters)                                                                                                             |
| Input Const | `tTimeAutoZero`         | `TIME`                       | TIME#1440m0s0ms | <p>Time interval between two processes for automatic<br>zero-point adjustment (range: 15 … 1440 min)</p>                                                         |
| Input Const | `rK_Type`               | `REAL`                       | 2.0             | <p>Selection of the formula for calculating the air quantity (range: 1<br>… 3)</p>                                                                               |
| Input Const | `rK_Value`              | `REAL`                       | 1.0             | <p>k-factor for calculating the air quantity (range: 1 … 2000<br>)</p>                                                                                           |
| Input Const | `xAutoZeroPress`        | `BOOL`                       | FALSE           | <p>Zero-point adjustment of the differential pressure measured value (at every<br>rising edge)</p>                                                               |
| Input Const | `stDisplText`           | `STRING(7)`                  | `powerIO`       | <p>Any text with 7 characters (fixed length) in the<br>lowest display line</p>                                                                                   |
| Input Const | `tTimeUpdateConfig`     | `TIME`                       | TIME#0ms        | <p>Update interval for the operations that are influenced by the input<br><code>xUpdateConfig</code> influenced</p>                                              |
| Input Const | `tTimeUpdateSetp`       | `TIME`                       | TIME#45s0ms     | <p>Update interval for the operations that are influenced by the input<br><code>xUpdateSetp</code> influenced</p>                                                |
| Input Const | `tTimeUpdateActual`     | `TIME`                       | TIME#3s0ms      | <p>Update interval for the operations that are influenced by the input<br><code>xUpdateActual</code> influenced</p>                                              |


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://support.powerio.com/hub/codesys-hvac/en/hvac-modbus-library/functionblocks/spluss/spluss_8147_mod_lcd.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.