SPLUSS_8147_MOD_LCD

SPLUSS_8147_MOD_LCD (FB)

FUNCTION_BLOCK SPLUSS_8147_MOD_LCD

Representation

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enabled)

Input

byUnitId

BYTE

0

Address of the device

Input

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge )

Input

xUpdateSetp

BOOL

FALSE

Update of setpoints (on every rising edge )

Input

xUpdateConfig

BOOL

FALSE

Update of the configuration ( on every rising edge )

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

rDifPressure

REAL

Differential pressure unfiltered in XXXX Pa

Output

rDifPressure_1s

REAL

Differential pressure filtered 1s in XXXX Pa

Output

rDifPressure_10s

REAL

Differential pressure filtered 10s in XXXX Pa

Output

xAutoZeroAct

BOOL

Display of execution of an auto-zero function ( TRUE = function active )

Output

rTemp_4s

REAL

Temperature filtered 4s in XX.X degrees Celsius

Output

rTemp_32s

REAL

Temperature filtered 32s in XX.X degrees Celsius

Output

rrH_4s

REAL

Relative humidity filtered 4s in XX.X % RH

Output

rrH_32s

REAL

Relative humidity filtered 32s in XX.X % RH

Output

rVolumeFlow

REAL

Volume flow calculated in XXXXX m3/h

Output

rDewpointTemp

REAL

Dew point temperature in XXX.X degrees Celsius

Output

rAbsH_M3

REAL

Absolute humidity in XX.X g/m3

Output

rMixRatio

REAL

Mixing ratio in XXX.X g water/kg dry air

Output

rEnthalpy

REAL

Enthalpy in XXX.X kJ/kg

Output

rairtight

REAL

Air density in XXX.X kg/m3

Output

xSensorOffsetInDevice

BOOL

Indicates whether sensor calibration must be performed in the device ( TRUE = calibration required in the device, FALSE = calibration required in the FB )

Output

xAlarm

BOOL

FALSE

Collective fault (TRUE = fault)

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication (TRUE = fault)

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

Output

eErrorCodeDev

SPLUSS_ERROR_CODE_TYPE_1

Error code - device (0 = no error)

Output

xBusy

BOOL

Communication indicator (TRUE = communication)

Input Const

rAltitude

REAL

500.0

Altitude above sea level ( range: -500 … 5000 meters )

Input Const

tTimeAutoZero

TIME

TIME#1440m0s0ms

Duration between two auto-zero operations ( range: 15 … 1440 min )

Input Const

rK_Type

REAL

2.0

Selection of the formula for calculating the air volume ( range: 1 … 3 )

Input Const

rK_Value

REAL

1.0

k-factor for calculating the air volume ( range: 1 … 2000 )

Input Const

xAutoZeroPress

BOOL

FALSE

Zeroing of the differential pressure measurement value ( on each rising edge )

Input Const

stDisplText

STRING(7)

'powerIO'

Arbitrary text with 7 characters ( fixed length ) in the bottom display line

Input Const

tTimeUpdateConfig

TIME

TIME#0ms

Update interval for the processes influenced by the input ‘xUpdateConfig’

Input Const

tTimeUpdateSetp

TIME

TIME#45s0ms

Update interval for the operations affected by the input 'xUpdateSetp'

Input Const

tTimeUpdateActual

TIME

TIME#3s0ms

Update interval for the operations affected by the input 'xUpdateActual'

Last updated