SPLUSS_8147_MOD_LCD

SPLUSS_8147_MOD_LCD (FB)

FUNCTION_BLOCK SPLUSS_8147_MOD_LCD

Representation

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enable)

Input

byUnitId

BYTE

0

Device address

Input

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge )

Input

xUpdateSetp

BOOL

FALSE

Update of setpoints (on every rising edge )

Input

xUpdateConfig

BOOL

FALSE

Update of the configuration (on each rising edge)

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

rDifPressure

REAL

Differential pressure unfiltered in XXXX Pa

Output

rDifPressure_1s

REAL

Differential pressure filtered 1s in XXXX Pa

Output

rDifPressure_10s

REAL

Differential pressure filtered 10s in XXXX Pa

Output

xAutoZeroAct

BOOL

Display of the execution of an auto-zero function (TRUE = function active)

Output

rTemp_4s

REAL

Temperature filtered 4s in XX.X degrees Celsius

Output

rTemp_32s

REAL

Temperature filtered 32s in XX.X degrees Celsius

Output

rrH_4s

REAL

Relative humidity filtered 4s in XX.X % rH

Output

rrH_32s

REAL

Relative humidity filtered 32s in XX.X % rH

Output

rVolumeFlow

REAL

Volumetric flow calculated in XXXXX m3/h

Output

rDewpointTemp

REAL

Dew point temperature in XXX.X degrees Celsius

Output

rAbsH_M3

REAL

Absolute humidity in XX.X g/m3

Output

rMixRatio

REAL

Mixing ratio in XXX.X g water/kg dry air

Output

rEnthalpy

REAL

Enthalpy in XXX.X kJ/kg

Output

rairtight

REAL

Air density in XXX.X kg/m3

Output

xSensorOffsetInDevice

BOOL

Indication of whether the sensors must be calibrated in the device (TRUE = calibration in the device required, FALSE = calibration in the FB required)

Output

xAlarm

BOOL

FALSE

Collective fault (TRUE = fault)

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication (TRUE = fault)

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

Output

eErrorCodeDev

SPLUSS_ERROR_CODE_TYPE_1

Error code - device (0 = no error)

Output

xBusy

BOOL

Communication indicator (TRUE = communication)

Input Const

rAltitude

REAL

500.0

Altitude above sea level (range: -500 … 5000 meters)

Input Const

tTimeAutoZero

TIME

TIME#1440m0s0ms

Time interval between two processes for automatic zero point adjustment (range: 15 … 1440 min)

Input Const

rK_Type

REAL

2.0

Selection of the formula for calculating the air volume (range: 1 … 3)

Input Const

rK_Value

REAL

1.0

k-factor for calculating the air volume (range: 1 … 2000 )

Input Const

xAutoZeroPress

BOOL

FALSE

Zero-point adjustment of the differential pressure measured value (at every rising edge)

Input Const

stDisplText

STRING(7)

powerIO

Any text with 7 characters (fixed length) in the bottom display line

Input Const

tTimeUpdateConfig

TIME

TIME#0ms

Update interval for the processes influenced by the input xUpdateConfig influenced

Input Const

tTimeUpdateSetp

TIME

TIME#45s0ms

Update interval for the processes influenced by the input xUpdateSetp influenced

Input Const

tTimeUpdateActual

TIME

TIME#3s0ms

Update interval for the processes influenced by the input xUpdateActual influenced