SPLUSS_RFTM_XXX_MOD
SPLUSS_RFTM_XXX_MOD (FB)
SPLUSS_RFTM_XXX_MOD (FB)FUNCTION_BLOCK SPLUSS_RFTM_XXX_MOD
InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Address of the device
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on each rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints ( on each rising edge )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rCO2_4s
REAL
CO2 concentration filtered 4s in XXXX ppm
Output
rCO2_32s
REAL
CO2 concentration filtered 32s in XXXX ppm
Output
rVOC_4s
REAL
Air quality filtered 4s in XXX.X % VOC
Output
rVOC_32s
REAL
Air quality filtered 32s in XXX.X % VOC
Output
rTemp_4s
REAL
Temperature filtered 4s in XX.X degrees Celsius
Output
rTemp_32s
REAL
Temperature filtered 32s in XX.X degrees Celsius
Output
rrH_4s
REAL
Relative humidity filtered 4s in XX.X % rH
Output
rrH_32s
REAL
Relative humidity filtered 32s in XX.X % rH
Output
rPM_4s
REAL
Particle concentration filtered 4s in µg/m3 ( 0 - 1000 µg/m3 )
Output
rPM_32s
REAL
Particle concentration filtered 32s in µg/m3 ( 0 - 1000 µg/m3 )
Output
xSensorOffsetInDevice
BOOL
Indicates whether sensor calibration must be performed in the device (TRUE = calibration required in device, FALSE = calibration in FB required)
Output
xAutoZeroAct
BOOL
Display of execution of an auto-zero function ( TRUE = function active )
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
eErrorCodeDev
SPLUSS_ERROR_CODE_TYPE_1
Error code - device (0 = no error)
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
rPMOffset
REAL
0.0
Constant measurement offset for the transmitted particle density - actual value
Input Const
rrHOffset
REAL
0.0
Constant sensor offset for the transmitted relative humidity - actual value
Input Const
rTempOffset
REAL
0.0
Constant measurement offset for the transmitted temperature - actual value
Input Const
rVOCOffset
REAL
0.0
Constant measurement offset for the transmitted air quality - actual value
Input Const
rCO2Offset
REAL
0.0
Constant measurement offset for the transmitted CO2 - actual value ( positive / negative integers )
Input Const
xDisplayAvailable
BOOL
FALSE
Option 'Display' ( TRUE = The device is equipped with a display )
Input Const
xAutoCalCO2
BOOL
FALSE
Enable automatic calibration of the CO2 measurement ( FALSE = no automatic calibration )
Input Const
xAutoZeroVOC
BOOL
FALSE
Reset of the VOC measurement ( on each rising edge )
Input Const
xAutoZeroCO2
BOOL
FALSE
Reset of the CO2 measurement ( on each rising edge )
Input Const
eSensVOC
SPLUSS_VOC_SENSIBILITY
Sensitivity of the VOC sensor ( 1 = low, 2 = medium, 3 = high )
Input Const
tTimeUpdateSetp
TIME
TIME#0ms
Update interval for the processes affected by the input ‘xUpdateSetp’
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes affected by the input ‘xUpdateActual’