SPLUSS_LCD_SHD_MODBUS_EASY
SPLUSS_LCD_SHD_MODBUS_EASY (FB)
SPLUSS_LCD_SHD_MODBUS_EASY (FB)FUNCTION_BLOCK SPLUSS_LCD_SHD_MODBUS_EASY
General
This is a display module (input: 0.0 - 10.0V, output: Modbus - RTU) for a pressure transmitter (e.g. PREMASGARD SHD-U / SHD-SD-U / SHD692-U) with DIN EN 175301-803-A connector
The configuration of the Modbus interface and other parameters is carried out by the display module version 1). The configuration of further parameters can alternatively be done via a function block
SPLUSS_LCD_SHD_MODBUS_FULL(Version 2).
The measured value offset cannot be adjusted either in the device or via Modbus.
A terminating resistor (120 ohms) can be activated / deactivated via DIP switch.
The Modbus interface is parameterized as follows without any further settings:
RTU 9600 baud 8 data bits No parity 1 stop bit Device address = 1
The following register ranges may be written with FC16: 21-24, 28-29 and 31-34
Neither in the device (hardware / display menu) nor via Modbus is compensation of the measured value offset предусмотрed. Therefore, no compensation may be provided here in the function block (program value <> display value).
Representation

InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
Input
byUnitId
BYTE
0
Device address (1 .. 247)
Input
xUpdateActual
BOOL
FALSE
Updating the actual values (at every rising edge ) (range: operation)
Input
xResError
BOOL
FALSE
Reinitialization of the output eErrorCodeCom (with every
rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rInputVolt
REAL
Input voltage from the pressure sensor in XX.XXX volts
Output
rPressure
REAL
Differential pressure in XX.XX bar
Output
rPressureAverage
REAL
Time-averaged differential pressure in XX.XX bar
Output
rPressureMinRamge
REAL
Minimum value of the range for the differential pressure in XX.XX bar (depending on the measuring range of the sensor)
Output
rPressureMaxRange
REAL
Maximum value of the range for the differential pressure in XX.XX bar (depending on the measuring range of the sensor)
Output
rPressureMinInterv
REAL
Absolute minimum value of the differential pressure in XX.XX bar in the set interval
Output
rPressureMaxInterv
REAL
Absolute maximum value of the differential pressure in XX.XX bar in the set interval
Output
rPressureDisplay
REAL
Display value on the display (depending on the unit set for the display)
Output
eUnitDisplay
SPLUSS_LCD_SHD_MODBUS_EASY_DISPLAY_UNIT
Unit of the display value on the display
Output
wDeviceCode
WORD
Device - code of the device
Output
xAlarm
BOOL
Collective fault (TRUE = fault)
Output
xAlarmCom
BOOL
Collective fault - communication (TRUE = fault)
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
Output
xBusy
BOOL
Communication indicator (TRUE = communication)
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes influenced by the input
xUpdateActual influenced
Last updated

