SPLUSS_LCD_SHD_MODBUS_EASY
SPLUSS_LCD_SHD_MODBUS_EASY (FB)
SPLUSS_LCD_SHD_MODBUS_EASY (FB)FUNCTION_BLOCK SPLUSS_LCD_SHD_MODBUS_EASY
General
This is a display module (Input: 0.0 - 10.0V, Output: Modbus - RTU) for a pressure transmitter (e.g. PREMASGARD SHD-U / SHD-SD-U / SHD692-U) with connector DIN EN 175301-803-A
The configuration of the Modbus interface and other parameters is done on the display module (variant 1). The configuration of further parameters is alternatively done via a function block 'SPLUSS_LCD_SHD_MODBUS_FULL' (variant 2).
The measurement value offset cannot be adjusted either in the device or via Modbus.
A termination resistor (120 ohm) can be enabled/disabled via DIP switch.
The Modbus interface is parameterized as follows without further settings:
RTU 9600 Baud 8 data bits No parity 1 stop bit Device address = 1
The following register ranges may be written with FC16: 21-24, 28-29 and 31-34
Neither in the device (hardware / display menu) nor via Modbus is an adjustment of the measurement value offset provided. Therefore no adjustment may be provided in the function block (program value <> display value).
InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Device address ( 1 .. 247 )
Input
xUpdateActual
BOOL
FALSE
Update of the actual values (on every rising edge ) (Range: Operation)
Input
xResError
BOOL
FALSE
Reinitialization of the output ‘eErrorCodeCom’ (on each rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rInputVolt
REAL
Input voltage from the pressure sensor in XX.XXX volts
Output
rPressure
REAL
Differential pressure in XX.XX bar
Output
rPressureAverage
REAL
Time-averaged differential pressure in XX.XX bar
Output
rPressureMinRamge
REAL
Minimum value of the range for the differential pressure in XX.XX bar (depending on the sensor's measurement range)
Output
rPressureMaxRange
REAL
Maximum value of the range for the differential pressure in XX.XX bar (depending on the sensor's measurement range)
Output
rPressureMinInterv
REAL
Absolute minimum value of the differential pressure in XX.XX bar in the set interval
Output
rPressureMaxInterv
REAL
Absolute maximum value of the differential pressure in XX.XX bar in the set interval
Output
rPressureDisplay
REAL
Display value on the display (depending on the unit set for the display)
Output
eUnitDisplay
SPLUSS_LCD_SHD_MODBUS_EASY_DISPLAY_UNIT
Unit of the display value on the display
Output
wDeviceCode
WORD
Device - code of the device
Output
xAlarm
BOOL
Collective fault ( TRUE = fault )
Output
xAlarmCom
BOOL
Collective fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes affected by the input ‘xUpdateActual’
Last updated

