SPLUSS_KFTM_LQ_CO2_MOD
SPLUSS_KFTM_LQ_CO2_MOD (FB)
SPLUSS_KFTM_LQ_CO2_MOD (FB)FUNCTION_BLOCK SPLUSS_KFTM_LQ_CO2_MOD
Representation

InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
Input
byUnitId
BYTE
0
Device address
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints (on every rising edge )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rCO2_4s
REAL
Filtered CO2 concentration 4s in XXXX ppm
Output
rCO2_32s
REAL
Filtered CO2 concentration 32s in XXXX ppm
Output
rVOC_4s
REAL
Air quality filtered 4s in XXX.X % VOC
Output
rVOC_32s
REAL
Air quality filtered 32s in XXX.X % VOC
Output
rTemp_4s
REAL
Temperature filtered 4s in XX.X degrees Celsius
Output
rTemp_32s
REAL
Temperature filtered 32s in XX.X degrees Celsius
Output
rrH_4s
REAL
Relative humidity filtered 4s in XX.X % rH
Output
rrH_32s
REAL
Relative humidity filtered 32s in XX.X % rH
Output
rAirPressure_4s
REAL
Air pressure filtered 4s in XXXX hPa
Output
rAirPressure_32s
REAL
Air pressure humidity filtered XXXX hPa
Output
xSensorOffsetInDevice
BOOL
Indication of whether the sensors must be calibrated in the device (TRUE = calibration in the device required, FALSE = calibration in the FB required)
Output
xAutoZeroAct
BOOL
Display of the execution of an auto-zero function (TRUE = function active)
Output
xAlarm
BOOL
FALSE
Collective fault (TRUE = fault)
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication (TRUE = fault)
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
Output
eErrorCodeDev
SPLUSS_ERROR_CODE_TYPE_1
Error code - device (0 = no error)
Output
xBusy
BOOL
Communication indicator (TRUE = communication)
Input Const
rAirPressureOffset
REAL
0.0
Constant measured-value offset for the transmitted air pressure actual value
Input Const
rrHOffset
REAL
0.0
Constant measurement value offset for the transmitted relative humidity - actual value
Input Const
rTempOffset
REAL
0.0
Constant measured-value offset for the transmitted temperature actual value
Input Const
rVOCOffset
REAL
0.0
Constant measurement value offset for the transmitted air quality - actual value
Input Const
rCO2Offset
REAL
0.0
Constant measurement value offset for the transmitted CO2 - actual value (positive / negative integers)
Input Const
xDisplayAvailable
BOOL
FALSE
Option Display (TRUE = The device is equipped with a display)
Input Const
xAutoCalVOC
BOOL
FALSE
Enable automatic calibration of the VOC measured value ( FALSE = no automatic calibration)
Input Const
xAutoCalCO2
BOOL
FALSE
Enable automatic calibration of the CO2 measured value ( FALSE = no automatic calibration)
Input Const
xAutoZeroVOC
BOOL
FALSE
Reset the VOC measured value (at every rising edge)
Input Const
xAutoZeroCO2
BOOL
FALSE
Reset the CO2 measured value (at every rising edge)
Input Const
stDisplText
STRING(7)
‘Pfänder’
Any text with 7 characters (fixed length) in the bottom display line
Input Const
eSensVOC
SPLUSS_VOC_SENSIBILITY
Sensitivity of the VOC sensor (0 = no change, 1 = low, 2 = medium, 3 = high)
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the processes influenced by the input
xUpdateSetp influenced
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes influenced by the input
xUpdateActual influenced
Last updated