> For the complete documentation index, see [llms.txt](https://support.powerio.com/hub/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://support.powerio.com/hub/codesys-hvac/en/hvac-modbus-library/functionblocks/spluss/spluss_714x_mod.md).

# SPLUSS\_714X\_MOD

## `SPLUSS_714X_MOD` (FB)

`FUNCTION_BLOCK` SPLUSS\_714X\_MOD

### General

> This is a single-channel differential pressure transmitter (incl. calculation of the volume flow rate).

> 7148: Measuring range: +/- 500 Pa (with automatic zero-point calibration) 7147: Measuring range: +/- 7000 Pa (optional with automatic zero-point calibration)

> The transmitter can optionally be equipped with a display.

> The configuration of the Modbus interface is carried out via DIP switches in the transmitter Modbus RTU Modbus address: 1 - 247 (0 = Broadcast) 9600 - 38400 baud For data backup, the options 1-8-E-1, 1-8-O-1, 1-8-N-2 and 1-8-N-1 (deviating from the standard specifications) can be set.

> A terminating resistor (120 ohm) can be activated/deactivated via DIP switch.

> The calculation factors for the volume flow display are not saved fail-safe in the event of a zero-voltage outage. They must therefore be written again when fault-free communication is resumed.

> The adjustment of the differential pressure transmitter must be carried out imperatively in the device via hardware, since further derived measured variables (actual volume flow value) are calculated from this actual value.

### Representation

<figure><img src="https://2592874069-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FQR4vCFzt6ixgsqlR3pdR%2Fuploads%2FPC6baJq2zawcGtW0CEHp%2FHVACModbus.SPLUSS_714X_MOD.png?alt=media&amp;token=25d8df59-7ed8-461d-9dbf-8a3610b0f85c" alt=""><figcaption></figcaption></figure>

InOut:

| Scope       | Name                          | Type                                         | Initial                                                                            | Comment                                                                                                                                                                       |
| ----------- | ----------------------------- | -------------------------------------------- | ---------------------------------------------------------------------------------- | ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
| Input       | `xEn`                         | `BOOL`                                       | TRUE                                                                               | Enable / disable communication (TRUE = enable)                                                                                                                                |
| Input       | `byUnitId`                    | `BYTE`                                       | 0                                                                                  | Device address (1 .. 247)                                                                                                                                                     |
| Input       | `xUpdateActual`               | `BOOL`                                       | FALSE                                                                              | <p>Update of actual values (on every rising edge<br>)</p>                                                                                                                     |
| Input       | `xUpdateSetp`                 | `BOOL`                                       | FALSE                                                                              | <p>Update of setpoints (on every rising edge<br>)</p>                                                                                                                         |
| Input       | `xUpdateConfigWrite`          | `BOOL`                                       | FALSE                                                                              | <p>Configuration update (write access) (<br>with every rising edge)</p>                                                                                                       |
| Input       | `xResError`                   | `BOOL`                                       | FALSE                                                                              | <p>Reinitialization of the output <code>eErrorCodeCom</code> (with every<br>rising edge)</p>                                                                                  |
| Inout       | `ModbusClient`                | `ModbusClientBase`                           |                                                                                    | Client of the device                                                                                                                                                          |
| Output      | `rDifPressure`                | `REAL`                                       |                                                                                    | <p>Differential pressure unfiltered in XXXX Pa (7147) or XXX.X Pa<br>(7148) (selection via parameter <code>eDeviceType</code>)</p>                                            |
| Output      | `rDifPressure_1s`             | `REAL`                                       |                                                                                    | <p>Differential pressure filtered 1s in XXXX Pa (7147) or XXX.X<br>Pa (7148) (selection via parameter <code>eDeviceType</code>)</p>                                           |
| Output      | `rDifPressure_10s`            | `REAL`                                       |                                                                                    | <p>Differential pressure filtered 10s in XXXX Pa (7147) or XXX.X<br>Pa (7148) (selection via parameter <code>eDeviceType</code>)</p>                                          |
| Output      | `rVolumeFlow`                 | `REAL`                                       |                                                                                    | Volume flow in m3/h (0.0 - 999999.0 m3/h)                                                                                                                                     |
| Output      | `xSensorOffsetInDevice`       | `BOOL`                                       |                                                                                    | <p>Display indicating whether the sensor adjustment must take place in the device<br>(TRUE = adjustment in the device required, FALSE = adjustment in<br>the FB required)</p> |
| Output      | `xAlarm`                      | `BOOL`                                       |                                                                                    | Collective fault (TRUE = fault)                                                                                                                                               |
| Output      | `xAlarmCom`                   | `BOOL`                                       |                                                                                    | Collective fault - communication (TRUE = fault)                                                                                                                               |
| Output      | `eErrorCodeCom`               | ModbusErrorCode                              |                                                                                    | Error code - communication (0 = no error)                                                                                                                                     |
| Output      | `xBusy`                       | `BOOL`                                       |                                                                                    | Communication indicator (TRUE = communication)                                                                                                                                |
| Input Const | `stDisplayText`               | `STRING(7)`                                  | `powerIO`                                                                          | <p>Any text with 7 characters (fixed length) in the<br>bottommost display line (characters H - N)</p>                                                                         |
| Input Const | `eDisplayValue`               | SPLUSS\_714X\_MOD\_DISPLAY\_VALUE            | SPLUSS\_714X\_MOD\_DISPLAY\_VALUE.Standard\_Display                                | <p>Definition of the value to be displayed (static) (0 =<br>standard display = differential pressure)</p>                                                                     |
| Input Const | `xDisplayAvailable`           | `BOOL`                                       | FALSE                                                                              | <p>Definition of whether a display is present (TRUE = display<br>is present)</p>                                                                                              |
| Input Const | `rVolFlowHeightAboveSeaLevel` | `REAL`                                       | 450.0                                                                              | <p>Altitude above sea level for calculating the volume flow<br>in meters (-500.0 - +5000.0)</p>                                                                               |
| Input Const | `eVolFlowEquationType`        | SPLUSS\_714X\_MOD\_VOL\_FLOW\_EQUATION\_TYPE | SPLUSS\_714X\_MOD\_VOL\_FLOW\_EQUATION\_TYPE.Rosenberg\_Comefri\_Gebhardt\_Nicotra | <p>Selection of the fan manufacturer to define the formula<br>for calculating the volume flow</p>                                                                             |
| Input Const | `rVolFlowConstant`            | `REAL`                                       | 100.0                                                                              | <p>K-factor for calculating the current volume flow (1.0 -<br>2000.0)</p>                                                                                                     |
| Input Const | `tTimeAutoZeroIntervall`      | `TIME`                                       | TIME#720m0s0ms                                                                     | <p>Cycle time for automatic zero-point adjustment in<br>minutes (15.0 - 1440.0)</p>                                                                                           |
| Input Const | `xEnAutoZero`                 | `BOOL`                                       | TRUE                                                                               | <p>Enable / disable automatic, cyclical zero-point<br>adjustment (TRUE = enable)</p>                                                                                          |
| Input Const | `eDeviceType`                 | SPLUSS\_714X\_MOD\_DEVICE\_TYPE              | SPLUSS\_714X\_MOD\_DEVICE\_TYPE.Type\_7148                                         | Selection of the device type (1 = 7148 = +/- 500Pa)                                                                                                                           |
| Input Const | `tTimeUpdateConfigWrite`      | `TIME`                                       | TIME#0ms                                                                           | <p>Update interval for the operations that are influenced by the input<br><code>xUpdateConfigWrite</code> influenced</p>                                                      |
| Input Const | `tTimeUpdateSetp`             | `TIME`                                       | TIME#0ms                                                                           | <p>Update interval for the operations that are influenced by the input<br><code>xUpdateSetp</code> influenced</p>                                                             |
| Input Const | `tTimeUpdateActual`           | `TIME`                                       | TIME#3s0ms                                                                         | <p>Update interval for the operations that are influenced by the input<br><code>xUpdateActual</code> influenced</p>                                                           |


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://support.powerio.com/hub/codesys-hvac/en/hvac-modbus-library/functionblocks/spluss/spluss_714x_mod.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.
