SPLUSS_724X_MOD
SPLUSS_724X_MOD (FB)
SPLUSS_724X_MOD (FB)FUNCTION_BLOCK SPLUSS_724X_MOD
General
This is a two-channel differential pressure transmitter (including calculation of volumetric flow, including PT-1000 temperature sensor input).
7245: Measurement range: +/- 500 Pa (with manual zero-point calibration) (channels 1 + 2) 7247: Measurement range: +/- 7000 Pa (with manual zero-point calibration) (channels 1 + 2) 7249: Measurement range: +/- 500 Pa (with manual zero-point calibration) (channel 1)
Measurement range: +/- 7000 Pa (with manual zero-point calibration) (channel 2)
The transmitter can optionally be equipped with a display.
The actual volumetric flow is calculated based on the differential pressure actual value of channel 1
The Modbus interface configuration is done via DIP switches in the transmitter Modbus - RTU Modbus address: 1 - 247 (0 = broadcast) 9600 - 38400 baud For data safety the options 1-8-E-1, 1-8-O-1, 1-8-N-2 and 1-8-N-1 (contrary to the standard's specifications) can be set.
A termination resistor (120 ohm) can be enabled/disabled via DIP switch.
The calculation coefficients for the volumetric flow display are not stored fail-safe against power loss. Therefore they must be written again when communication is resumed correctly.
The calibration of the differential pressure transmitter must be performed on the device by hardware, since further derived measured variables (volumetric flow actual value) are calculated from this actual value.
InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Device address ( 1 .. 247 )
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on each rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints ( on each rising edge )
Input
xUpdateConfigWrite
BOOL
FALSE
Update of the configuration (write access) ( on every rising edge)
Input
xResError
BOOL
FALSE
Reinitialization of the output ‘eErrorCodeCom’ (on each rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rDifPressureCH1
REAL
Differential pressure - channel 1 unfiltered
Output
rDifPressureCH1_1s
REAL
Differential pressure - channel 1 filtered 1s
Output
rDifPressureCH1_10s
REAL
Differential pressure - channel 1 filtered 10s
Output
rVolumeFlowCH1
REAL
Volumetric flow - channel 1
Output
rDifPressureCH2
REAL
Differential pressure - channel 2 unfiltered
Output
rDifPressureCH2_1s
REAL
Differential pressure - channel 2 filtered 1s
Output
rDifPressureCH2_10s
REAL
Differential pressure - channel 2 filtered 10s
Output
rTemperature
REAL
Temperature unfiltered
Output
rTemperature_10s
REAL
Temperature filtered 10s
Output
xSensorOffsetInDevice
BOOL
Indicates whether sensor calibration must be performed in the device (TRUE = calibration required in device, FALSE = calibration in FB required)
Output
xAlarm
BOOL
Collective fault ( TRUE = fault )
Output
xAlarmCom
BOOL
Collective fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
stDisplayText
STRING(7)
‘powerIO’
Arbitrary text with 7 characters (fixed length) in the lowest display line (characters H - N)
Input Const
eDisplayValue
SPLUSS_724X_MOD_DISPLAY_VALUE
SPLUSS_724X_MOD_DISPLAY_VALUE.Standard_Display
Selection of the value to be displayed (static) (0 = standard display)
Input Const
xDisplayAvailable
BOOL
FALSE
Definition whether a display is present (TRUE = display is present)
Input Const
eVolFlowEquationType
SPLUSS_724X_MOD_VOL_FLOW_EQUATION_TYPE
SPLUSS_724X_MOD_VOL_FLOW_EQUATION_TYPE.Rosenberg_Comefri_Gebhardt_Nicotra
Selection of the fan manufacturer to determine the formula for calculating the volumetric flow
Input Const
rVolFlowConstant
REAL
100.0
K-factor for calculating the current volumetric flow (1.0 - 2000.0)
Input Const
xEnAutoZero
BOOL
TRUE
Enable/disable of the automatic cyclic zero-point calibration (TRUE = enabled)
Input Const
eUnitType
SPLUSS_724X_MOD_UNIT_TYPE
SPLUSS_724X_MOD_UNIT_TYPE.Type_SI
Central selection of the unit system (0 = SI)
Input Const
eDeviceType
SPLUSS_724X_MOD_DEVICE_TYPE
SPLUSS_724X_MOD_DEVICE_TYPE.Type_7245
Selection of the device type (1 = 7148 = +/- 500Pa)
Input Const
tTimeUpdateConfigWrite
TIME
TIME#0ms
Update interval for the processes influenced by the input ‘xUpdateConfigWrite’
Input Const
tTimeUpdateSetp
TIME
TIME#0ms
Update interval for the processes affected by the input ‘xUpdateSetp’
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes affected by the input ‘xUpdateActual’
Last updated

