SPLUSS_FSFTM_MOD
SPLUSS_FSFTM_MOD (FB)
SPLUSS_FSFTM_MOD (FB)FUNCTION_BLOCK SPLUSS_FSFTM_MOD
InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Address of the device
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on each rising edge )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rTemp_4s
REAL
Temperature filtered 4s in XX.X degrees Celsius
Output
rTemp_32s
REAL
Temperature filtered 32s in XX.X degrees Celsius
Output
rrH_4s
REAL
Relative humidity filtered 4s in XX.X % rH
Output
rrH_32s
REAL
Relative humidity filtered 32s in XX.X % rH
Output
xSensorOffsetInDevice
BOOL
Indicates whether sensor calibration must be performed in the device (TRUE = calibration required in device, FALSE = calibration in FB required)
Output
rDewPoint
REAL
Dew point temperature in XX.X degrees Celsius
Output
rAbsH_KG
REAL
Absolute humidity in XX.X g/kg
Output
rEnthalpy
REAL
Enthalpy in XX.X kJ/kg
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
eErrorCodeDev
SPLUSS_ERROR_CODE_TYPE_1
Error code - device (0 = no error)
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
rrHOffset
REAL
0.0
Constant sensor offset for the transmitted relative humidity - actual value
Input Const
rTempOffset
REAL
0.0
Constant measurement offset for the transmitted temperature - actual value
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes affected by the input ‘xUpdateActual’
Last updated