SPLUSS_2327_MOD_LCD
SPLUSS_2327_MOD_LCD (FB)
SPLUSS_2327_MOD_LCD (FB)FUNCTION_BLOCK SPLUSS_2327_MOD_LCD
InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Address of the device
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on each rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints ( on each rising edge )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rDifPressure
REAL
Differential pressure unfiltered in XXXX Pa
Output
rDifPressure_1s
REAL
Differential pressure filtered 1s in XXXX Pa
Output
rDifPressure_10s
REAL
Differential pressure filtered 10s in XXXX Pa
Output
xSensorOffsetInDevice
BOOL
Indicates whether sensor calibration must be performed in the device (TRUE = calibration required in device, FALSE = calibration in FB required)
Output
xAutoZeroAct
BOOL
Display of execution of an auto-zero function ( TRUE = function active )
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
eErrorCodeDev
SPLUSS_ERROR_CODE_TYPE_1
Error code - device (0 = no error)
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
rDifPressureOffset
REAL
0.0
Constant measurement offset for the transmitted differential pressure - actual value
Input Const
xDisplayAvailable
BOOL
FALSE
Option 'Display' ( TRUE = The device is equipped with a display )
Input Const
xAutoZeroPress
BOOL
FALSE
Zero point adjustment of the differential pressure measurement ( on each rising edge )
Input Const
stDisplText
STRING(7)
‘powerIO’
Any text with 7 characters ( fixed length ) in the bottom display line
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the processes affected by the input ‘xUpdateSetp’
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes affected by the input ‘xUpdateActual’