Valve3P

Valve3P (FB)

FUNCTION_BLOCK Valve3P

Short description

Control of a 3-point valve actuator and calculation of the valve position In addition, the 3-point actuator is protected by an anti-blocking function. Typical application: Control of a 3-point valve actuator in a heating circuit

Representation

Interfaces

Inputs

Name
Data type
Value range
Initial value
Function

xYOpen

BOOL

Control signal - valve opening

xYClose

BOOL

Control signal - valve closing

xForce

BOOL

FALSE

Forced override after manual override

xAlarmIn

BOOL

FALSE

Actuator fault message

eAOOOpen

HVACTYPES.eManBin

HVACTYPES.eManBin.Auto, HVACTYPES.eManBin.ManOff, HVACTYPES.eManBin.ManOn

Manual override mode - hardware for valve opening

eAOOClose

HVACTYPES.eManBin

HVACTYPES.eManBin.Auto, HVACTYPES.eManBin.ManOff, HVACTYPES.eManBin.ManOn

Manual override mode - hardware for valve closing

Outputs

Name
Data type
Value range
Initial value
Function

xHBOpen

BOOL

Enable - valve opening after manual override

xHBClose

BOOL

Enable - valve closing after manual override

xABOpen

BOOL

Enable - valve opening before manual override

xABClose

BOOL

Enable - valve closing before manual override

dtAbsLastOn

DATE_AND_TIME

Start date/time of the last blocking protection process

rPos

REAL

0.0 … 100.0

Calculated current valve position

xAuto

BOOL

Collective automatic operation message

Setpoints / Parameters

Name
Data type
Value range
Initial value
Function

tDuration

TIME

120s

Actuator running time

udiAbsTime

UDINT

0 to 3600s

200s

Duration of the blocking protection process

todAbsStartTime

TOD

TOD#09:00:00

Start time of the blocking protection process

eAbsDay

eDoW

eDow.Monday

Weekday of the blocking protection process

xForceOption

BOOL

TRUE

Status of outputs xHBOpen or xHBClose under forced override

eManModeOpen

eMANBIN

eMANBIN.Auto, eMANBIN.Off, eMANBIN.On

eMANBIN.Auto

Manual override mode - valve opening

eManModeClose

eMANBIN

eMANBIN.Auto, eMANBIN.Off, eMANBIN.On

eMANBIN.Auto

Manual override mode - valve closing

Functional description

General

This function block is used to control the position of a 3-point valve actuator via the outputs Enable - valve opening after manual override xHBOpen or xHBClose. The current valve position is continuously calculated and is available at the output rPos is available. The following function blocks are mainly used:

  • Abs3P

  • ManBin

  • Position3P

Anti-blocking protection process

This process is implemented by monitoring signals 1 and 2 for activity and, if necessary, by triggering the anti-blocking function. The test period is 168 hours each time (= 1 week). Signals 1 and 2 are active if they are continuously active during the test period for the minimum operating time of 30.0 s (signal 1 only or signal 2 only or both). The anti-blocking process is thereby prevented, the test period starts again. Signal 1: (xYOpen AND eAOOOpen = HVACTYPES.eManBin.Auto) OR (eAOOOpen = HVACTYPES.eManBin.ManOn) Signal 2: (xYClose AND eAOOClose = HVACTYPES.eManBin.Auto) OR (eAOOClose = HVACTYPES.eManBin.ManOn) If no activity is detected during the test period, the anti-blocking process is triggered on the weekday eAbsDay at the time todAbsStartTime triggered. At the same time, the test period starts again. The active anti-blocking process is divided into two consecutive time sections (section 1 and section 2). In section 1, during the time period udiAbsTime the combination Enable - output xABOpen = TRUE, Enable - output xABClose = FALSE is output. In section 2, during the time period udiAbsTime the combination Enable - output xABOpen = FALSE, Enable - output xABClose = TRUE is output. The initial triggering of the anti-blocking process can, depending on the relevant settings (weekday eAbsDay and todAbsStartTime) be delayed.

Example

Test period ended on Tuesday morning, triggering of the blocking protection process only on the following Monday.

At output dtAbsLastOn the start date and start time of the last blocking protection process are available.

Prerequisite for using the function block Abs3P

For correct operation, the use of the TimeRead2 function block is required.

Enable - valve opening before manual override xABOpen

The Enable - valve opening before manual override xABOpen is controlled by the input Request - valve opening xYOpen and the anti-blocking protection module.

xYOpen

Anti-blocking protection process

xABOpen

Notes

FALSE

FALSE

FALSE

Request not active, no anti-blocking process

X

TRUE

Section 1: TRUE Section 2: FALSE

Blocking protection process active

TRUE

FALSE

TRUE

Request active, no anti-blocking process

Legend: X = any

Enable - valve closing before manual override xABClose

The Enable - valve closing before manual override xABClose is controlled by the input Request - valve closing xYClose and the anti-blocking protection module.

xYClose

Anti-blocking protection process

xABClose

Notes

FALSE

FALSE

FALSE

Request not active, no anti-blocking process

X

TRUE

Section 1: FALSE Section 2: TRUE

Blocking protection process active

TRUE

FALSE

TRUE

Request active, no anti-blocking process

Legend: X = any

Enable - valve opening after manual override xHBOpen

The Enable - valve opening after manual override xHBOpen corresponds to the Enable - valve opening before manual override xABOpen additionally extended by a manual override module and a forced override.

xABOpen

eManModeOpen

xForce

xForceOption

xHBOpen

Notes

FALSE

eMANBIN.Auto

FALSE

X

FALSE

Manual override module in automatic mode

TRUE

eMANBIN.Auto

FALSE

X

TRUE

Manual override module in automatic mode

X

eMANBIN.On

FALSE

X

TRUE

Manual override module in manual mode On

X

eMANBIN.Off

FALSE

X

FALSE

Manual override module in manual mode Off

X

X

TRUE

FALSE

FALSE

Forced override Close

X

X

TRUE

TRUE

TRUE

Forced override Open

Legend: X = any

Enable - valve closing after manual override xHBClose

The Enable - valve closing after manual override xHBClose corresponds to the Enable - valve closing before manual override xABClose additionally extended by a manual override module and a forced override.

xABClose

eManModeOpen

xForce

xForceOption

xHBClose

Notes

FALSE

eMANBIN.Auto

FALSE

X

FALSE

Manual override module in automatic mode

TRUE

eMANBIN.Auto

FALSE

X

TRUE

Manual override module in automatic mode

X

eMANBIN.On

FALSE

X

TRUE

Manual override module in manual mode On

X

eMANBIN.Off

FALSE

X

FALSE

Manual override module in manual mode Off

X

X

TRUE

FALSE

FALSE

Forced override Close

X

X

TRUE

TRUE

TRUE

Forced override Open

Legend: X = any

Forced control of the manual overrides of the outputs

If the manual override mode - valve opening is eManModeOpen in state eMANBIN.On (= manual override opening active), then the manual override mode - valve closing is forcibly eManModeClose set to state eMANBIN.Off (= manual override closing not active). If the manual override mode - valve closing is eManModeClose in state eMANBIN.On (= manual override closing active), then the manual override mode - valve opening is forcibly eManModeOpen set to state eMANBIN.Off (= manual override opening not active).

Current valve position rPos

It is used to display the current position of the 3-point actuator in the range 0 - 100% and is calculated from the duration of the signals at the outputs Enable - valve opening after manual override xHBOpen and Enable - valve closing after manual override xHBClose in combination with the actuator running time tDuration calculated. The position display is independent of signal generation, i.e. if the position display reaches an end position (0% or 100%), signals are still continued at the outputs xABOpen and xABClose or xHBOpen and xHBClose generated. The position display does not take into account any position changes caused by the manual override - hardware.

Collective fault xAlarm

The collective fault xAlarm is activated (= TRUE) if the input xAlarmIn is active. In all other cases the collective fault is xAlarm is not activated (= FALSE).

Collective automatic operation message xAuto

The collective automatic operation message xAuto is activated (= TRUE) if the following conditions are simultaneously met:

  • Input eAOOUp = HVACTYPES.eManBin.Auto

  • Input eAOODown = HVACTYPES.eManBin.Auto

  • Setpoint / parameter eManModeUp = eMANBIN.Auto

  • Setpoint / parameter eManModeDown = eMANBIN.Auto

Forced override xForce

The forced override acts directly on the outputs xHBOpen and xHBClose. With the parameter xForceOption it is determined which state the output xHB assumes when TRUE is at the input xForce takes. With xForceOption = FALSE If the input xForce is TRUE, then the output xHBOpen to FALSE and at the same time the output xHBClose is set to TRUE. When xForceOption = TRUE If the input xForce is TRUE, then the output xHBOpen to TRUE and at the same time the output xHBClose is set to FALSE.

CODESYS

InOut:

Scope
Name
Type
Initial

Input

xYOpen

BOOL

Input

xYClose

BOOL

Input

xForce

BOOL

FALSE

Input

xAlarmIn

BOOL

FALSE

Input

eAOOOpen

eManBin

Input

eAOOClose

eManBin

Output

xHBOpen

BOOL

Output

xHBClose

BOOL

Output

xABOpen

BOOL

Output

xABClose

BOOL

Output

dtAbsLastOn

DT

Output

rPos

REAL

Output

xAlarm

BOOL

Output

xAuto

BOOL

Input Const

udiDuration

UDINT

120

Input Const

udiAbsTime

UDINT

200

Input Const

todAbsStartTime

TOD

TIME_OF_DAY#9:0

Input Const

eAbsDay

eDoW

eDow.Monday

Input Const

xForceOption

BOOL

TRUE

Input Const

eManModeOpen

eMANBIN

eMANBIN.Auto

Input Const

eManModeClose

eMANBIN

eMANBIN.Auto

Last updated