Burner3P

Burner3P (FB)

FUNCTION_BLOCK Burner3P

Short description

Control of a heat generator (temperature control via binary control commands More / Less) Typical application: heat generation

Representation

Function description

General

This function block is used to control / regulate a heat generator depending on the demand of the heat generator xEn, the flow setpoint temperature rSetPtTemp and the flow temperature rFdT. The enable / disable of the heat generator is done via the output xHB ( FALSE = disabled, TRUE = enabled ). The flow temperature control (analogously also boiler temperature control) is performed by two power controllers (P-controllers, slow and fast) via the outputs xMoreHB and xLessHB. The enabling of the control is delayed (setpoint / parameter udiWaitControl ) after the running feedback ( xFb = TRUE ) of the heat generator. The following function blocks are essentially used:

ControlP

Out3P

OperatingHours

ManBin

Enable / disable of the heat generator

The enabling of the heat generator ( xAB = TRUE, xHB = TRUE ( eManModeB = eManBin.Auto )) occurs if the flow temperature rFdT the sum of flow setpoint temperature rSetPtTemp and setpoint / parameter rSwitchOnPoint falls below, at the same time the general enable xEn active ( = TRUE ) and the minimum off time is not active. The disabling of the heat generator ( xAB = FALSE, xHB = FALSE ( eManModeB = eManBin.Auto )) occurs if the flow temperature rFdT the sum of flow setpoint temperature rSetPtTemp and setpoint / parameter rSwitchOffPoint exceeds and at the same time the general enable xEn active ( = TRUE ). A minimum off time (duration = udiTimeMinOff, display - remaining time: tOnDelay ) is always inserted between two consecutive operating cycles. The minimum off time always begins with the falling edge ( TRUE > FALSE ) at the input xFb.

Temperature control of the heat generator

The enabling of the temperature control is delayed (duration = udiWaitControl, display - remaining time: tOnControlDelay ) after the active running feedback ( xFb = TRUE ) of the heat generator. The disabling of the temperature control occurs immediately after the inactive running feedback ( xFb = FALSE ) of the heat generator (switch-off value: rYDisabled ). The two internal power controllers (P-controllers, slow and fast, output range each -100.0 - 100.0 %) are enabled / disabled simultaneously. (Setpoint = flow setpoint temperature rSetPtTemp, actual value = flow temperature rFdT ). The control signals of both power controllers are forwarded to the output controller in a minimum-value selection (forwarding the signal with the smaller value) in the range -100.0 - 100.0 %. The output controller finally generates output signals for a 3-point actuator (pulse-width modulation, integration interval = tIntegration ) with the outputs xMoreHB or xLessHB. The constant pulse duration for the two outputs is freely adjustable in each case ( tImpulsOpen or tImpuls Close ), the variable pulse pauses are determined by the output controller. The two power controllers can be configured individually and independently of each other (P-controller fast: gain factor rKpBig, P-controller slow: gain factor rKpTiny ).

Manual override of the digital outputs

All digital control outputs after manual override ( xHB, xMoreHB*, xLessHB ) can be operated either in automatic mode ( eMANBIN.Auto ) or in one of the two manual operation modes ( eMANBIN.ManOn, eMANBIN.ManOff ).

xAB

eMANBIN

xHB

Notes

FALSE

eMANBIN.Auto

FALSE

Manual override module in automatic

TRUE

eMANBIN.Auto

TRUE

Manual override module in automatic

X

eMANBIN.ManOn

TRUE

Manual override module in manual operation On

X

eMANBIN.ManOff

FALSE

Manual override module in manual operation Off

Legend: X = don't care

Aggregate fault xAlarm

The aggregate fault xAlarm is active ( = TRUE ) if the fault message of the heat generator xAlarmIn is active ( = TRUE ). In all other situations the aggregate fault xAlarm is not active ( = FALSE ).

Collective automatic mode message xAuto

The collective automatic mode message xAuto is set active ( = TRUE ) if the following conditions are met simultaneously:\

  • Input eAOO = HVACTYPES.eManBin.Auto

  • Input eAOOMore = HVACTYPES.eManBin.Auto

  • Input eAOOLess = HVACTYPES.eManBin.Auto

  • Setpoint / parameter eManModeB = eMANBIN.Auto

  • Setpoint / parameter eManModeBMore = eMANBIN.Auto

  • Setpoint / parameter eManModeBLess = eMANBIN.Auto

Operating hours counter - heat generator

The operating hours counter ( udiOperatingHours, udiCountFb ) for the heat generator is active when the running feedback is active ( xFb = TRUE ).

Write access to the counters

Via the path ‘InstanceName._OperatingHours.udiOperatingHours’ or ‘InstanceName._OperatingHours.udiCountFb’ a write access to both counter values is possible.\

Prerequisite for using the Burner3P function block

The use of the TimeRead2 function block is required for correct operation.

Currently calculated output of the heat generator rPos

The current calculated output of the heat generator is shown at the output rPos in the range 0.0 - 100.0 %. For this, the correct specification of the actuator travel time between minimum and maximum output ( tDuration ) is required. No repositioning to a reference position takes place.

Feedback of the heat generator output rU

The current actual Output of the heat generator can be connected to the input rU . This input is currently not used for control and regulation purposes.

Inactive state ( xEn = FALSE )

xHB

xAB

xMoreHB

xMoreAB

xLessHB

xLessAB

rPos

tOnDelay

tOnControlDelay

dtLastFb

udiOperatingHours

udiCountFb

xAlarm

xAuto

Notes

FALSE ( eManModeB = eManBin.Auto )

FALSE

FALSE ( eManModeBMore = eManBin.Auto )

FALSE

FALSE ( eManModeBLess = eManBin.Auto )

FALSE

0.0 %

old value

old value

old value

old value

old value

State of xAlarmIn

old value

xEn = FALSE

Legend: X = don't care

CODESYS

InOut:

Scope
Name
Type
Initial

Input

xEn

BOOL

Input

rSetPtTemp

REAL

Input

xFb

BOOL

Input

rU

REAL

0

Input

xAlarmIn

BOOL

Input

eAOO

eManBin

eManBin.Auto

Input

eAOOMore

eManBin

eManBin.Auto

Input

eAOOLess

eManBin

eManBin.Auto

Input

rFdT

REAL

Output

xHB

BOOL

Output

xAB

BOOL

Output

xMoreHB

BOOL

Output

xMoreAB

BOOL

Output

xLessHB

BOOL

Output

xLessAB

BOOL

Output

rPos

REAL

Output

tOnDelay

TIME

Output

tOnControlDelay

TIME

Output

dtLastFb

DT

Output

udiOperatingHours

UDINT

Output

udiCountFb

UDINT

Output

xAlarm

BOOL

Output

xAuto

BOOL

Input Const

udiTimeTOFxFb

UDINT

7

Input Const

tDuration

TIME

TIME#1m0s0ms

Input Const

tIntegration

TIME

TIME#100ms

Input Const

tImpulsClose

TIME

TIME#1s0ms

Input Const

tImpulsOpen

TIME

TIME#1s0ms

Input Const

rKpTiny

REAL

0.6

Input Const

rKpBig

REAL

4

Input Const

rOffset

REAL

0

Input Const

rYDisabled

REAL

0

Input Const

udiWaitControl

UDINT

3

Input Const

rSwitchOffPoint

REAL

2.5

Input Const

rSwitchOnPoint

REAL

-2.5

Input Const

udiTimeMinOff

UDINT

3

Input Const

eManModeBLess

eMANBIN

eMANBIN.Auto

Input Const

eManModeBMore

eMANBIN

eMANBIN.Auto

Input Const

eManModeB

eMANBIN

eMANBIN.Auto

Last updated