Damper2P
Damper2P (FB)
Damper2P (FB)FUNCTION_BLOCK Damper2P
Short description
Control of a binary damper actuator with two position feedbacks Typical application: outdoor and exhaust air dampers of an HVAC system
Representation

Interfaces
Inputs
xY
BOOL
Control signal
xForce
BOOL
FALSE
Forced override after manual override
xAlarmIn
BOOL
FALSE
Actuator fault message
eAOO
HVACTYPES.eManBin
HVACTYPES.eManBin.Auto, HVACTYPES.eManBin.ManOff, HVACTYPES.eManBin.ManOn
HVACTYPES.eManBin.Auto
Operating mode of the manual override - hardware
xOpen
BOOL
Feedback damper open
xClosed
BOOL
Feedback damper closed
Outputs
xHB
BOOL
Release of damper actuator after manual override
xAB
BOOL
Release of damper actuator before manual override
xAlarmOpen
BOOL
Fault for damper open position
xAlarmClosed
BOOL
Fault for damper closed position
xAlarm
BOOL
Aggregate fault
xAuto
BOOL
Combined message automatic mode
Setpoints / Parameters
udiControlTime
UDINT
10s … 600s
150s
Reporting delay of the position monitoring
xControl
BOOL
TRUE
Enable position monitoring
xForceOption
BOOL
FALSE
State of the output xHB during forced override
eManModeB
eMANBIN
eMANBIN.Auto, eMANBIN.ManOff, eMANBIN.ManOn
eMANBIN.Auto
Operating mode of the manual override for the digital output xHB
Function description
Automatic output xAB
The release of the damper actuator before manual override xAB is taken unchanged from the enable input xY adopted.
Manual output xHB
The release of the damper actuator after manual override xHB corresponds to the release of the damper actuator before manual override xAB additionally extended by a manual override module and a forced override.
xAB
eManModeB
xForce
xForceOption
xHB
Notes
FALSE
eMANBIN.Auto
FALSE
X
FALSE
Manual override module in automatic
TRUE
eMANBIN.Auto
FALSE
X
TRUE
Manual override module in automatic
X
eMANBIN.ManOff
FALSE
X
FALSE
Manual override module in manual operation Off
X
eMANBIN.ManOn
FALSE
X
TRUE
Manual override module in manual operation On
X
X
TRUE
FALSE
FALSE
Forced override Closed
X
X
TRUE
TRUE
TRUE
Forced override Open
Legend: X = any
Fault for damper open position xAlarmOpen
The fault message for the position at damper opening xAlarmOpen is activated ( xAlarmOpen = TRUE ), if the following conditions are met simultaneously:
1) The release of the position monitoring xControl is enabled ( = TRUE ) 2) As operating mode of the manual override - hardware *eAOO* the automatic mode is selected ( *eAOO* = HVACTYPES.eManBin.Auto ) 3) The states of the release of the damper actuator after manual override *xHB* and the feedback for damper open *xOpen* are continuously different for at least the reporting delay of the position monitoring **udiControlTime** ( ( *xHB* = FALSE and *xOpen* = TRUE ) OR ( *xHB* = TRUE and *xOpen* = FALSE ) ). The fault message for the position at damper opening *xAlarmOpen* is deactivated if at least one of the above conditions is no longer met.
Fault for damper open position xAlarmClosed
The fault message for the position at damper opening xAlarmClosed is activated ( xAlarmClosed = TRUE ), if the following conditions are met simultaneously:
1) The release of the position monitoring xControl is enabled ( = TRUE ) 2) As operating mode of the manual override - hardware *eAOO* the automatic mode is selected ( *eAOO* = HVACTYPES.eManBin.Auto ) 3) The states of the release of the damper actuator after manual override *xHB* and the feedback for damper closed *xClosed* are continuously equal for at least the reporting delay of the position monitoring **udiControlTime** ( ( *xHB* = TRUE and *xOpen* = TRUE ) OR ( *xHB* = FALSE and *xOpen* = FALSE ) ). The fault message for the position at damper opening *xAlarmClosed* is deactivated if at least one of the above conditions is no longer met.
Aggregate fault xAlarm
The aggregate fault xAlarm is activated ( = TRUE ), if at least one of the two faults for the positions of the damper ( xAlarmOpen and xAlarmClosed ) or the input xAlarmIn is active. In all other cases the combined fault is xAlarm is not activated ( = FALSE ).
Combined message automatic mode xAuto
The combined message automatic mode xAuto is activated ( = TRUE ), if the input eAOO contains the value HVACTYPES.eManBin.Auto and the setpoint / parameter eManModeB contains the value eMANBIN.Auto. In all other cases the combined message automatic mode is xAuto is not activated ( = FALSE ).
Forced override xForce
The forced override acts directly on the output xHB. With the parameter xForceOption it is defined which state the output xHB assumes when TRUE at the input xForce takes.
CODESYS
InOut:
Input
xY
BOOL
Input
xForce
BOOL
FALSE
Input
xAlarmIn
BOOL
FALSE
Input
eAOO
eManBin
eManBin.Auto
Input
xOpen
BOOL
Input
xClosed
BOOL
Output
xHB
BOOL
Output
xAB
BOOL
Output
xAlarmOpen
BOOL
Output
xAlarmClosed
BOOL
Output
xAlarm
BOOL
Output
xAuto
BOOL
Input Const
udiControlTime
UDINT
200
Input Const
xControl
BOOL
TRUE
Input Const
xForceOption
BOOL
FALSE
Input Const
eManModeB
eMANBIN
eMANBIN.Auto
Last updated

