FanControl
FanControl (FB)
FUNCTION_BLOCK FanControl
Short description
Control of a variable-speed fan (control variables e.g. absolute pressure, differential pressure) Additional functions: manual overrides, maintenance switch, operating hours counter, operation monitoring, air shortage monitoring, limit value monitoring Typical application: control of a fan with frequency converter
Representation

Functional description
General
This function block controls a variable-speed fan using a continuous control signal rHA. The general enable of the fan is via the request xEn and the enable signal xHB. Speed control is performed by means of a freely parameterizable PI controller, to which the setpoint rSetPoint and the actual value rActValue are supplied and from these the controller output signal is generated. Essentially the following function blocks are used:
ControlPI
ManBin
ManNum
TwoPointFun
Ramp
CTime
AirShortage
OperatingHours
Enable - fan before manual override xAB
The enable - fan before manual override xAB is activated (= TRUE) if the following conditions are simultaneously met: Case 1: xEn = TRUE xMSwitch = TRUE xAlarmControl = FALSE Case 2: xEn = TRUE xMSwitch = TRUE xAlarmControl = TRUE xAlarm = FALSE In all other situations, the enable - fan before manual override xAB is not activated (= FALSE).
Enable - fan after manual override xHB
The enable - fan after manual override xHB corresponds to the enable - fan before manual override xAB, additionally extended by a manual override module. The enable can generally only be given if the forced lockout of the fan after manual override is not active (xForce = FALSE) and collective fault message 2 is not active (= FALSE).
xAB
eManModeB
xHB
Notes
FALSE
eMANBIN.Auto
FALSE
Manual override module in automatic mode
TRUE
eMANBIN.Auto
TRUE
Manual override module in automatic mode
X
eMANBIN.ManOn
TRUE
Manual override module in manual mode On
X
eMANBIN.ManOff
FALSE
Manual override module in manual mode Off
Legend: X = any
Maintenance switch message xMSwitch
xMSwitch = TRUE: repair switch has not been triggered (normal state) xMSwitch = FALSE: maintenance switch has tripped (fault state)
Forced lockout of the fan after manual override xForce
xForce = FALSE: no forced lockout (normal state) xForce = TRUE: forced lockout (exception state)
Operating hours and switch-on cycles udiOperatingHours and udiCountFb
The number of operating hours and switch-on cycles are recorded (= counting process active) if the fan operating signal xFb is active and at the same time collective fault message 2 is not active (= FALSE). The results are available at the counter outputs udiOperatingHours and udiCountFb .
Write access to the counter values
Via the path ‘InstanceName._OperatingHours.udiOperatingHours’ or ‘InstanceName._OperatingHours.udiCountFb’, write access to both counter values is possible.
Prerequisite for using the FanControl function block
For correct operation, the use of the TimeRead2 function block is required.
Date / time of the fan's last operation dtLastFb
At output dtLastFb the current date / current time is available during the counting process. At output dtLastFb the date / time at the end of the last counting process is available outside the counting process. At output dtLastFb the initialization value DT#1970-1-1-0.0.0 is output before the first counting process.
Operating supervision xAlarmFb
The operating monitoring can be enabled or disabled by the setpoint / parameter xFbControl (= TRUE) or blocked (= FALSE). When monitoring is blocked, the fault message of the operating monitoring xAlarmFb is always blocked (= FALSE). When monitoring is enabled, the fault message of the operating monitoring xAlarmFb is activated (= TRUE) if the following states are present simultaneously during a minimum time period udiFbControlTime the following states are given: xHB and xFb = unequal (enable state and operating state do not match) eAOO = HVACTYPES.eManBin.Auto (manual override - hardware for enable in automatic mode) xFbControl = TRUE (operating monitoring is enabled) The fault message of the operating monitoring xAlarmFb is reset (= FALSE) if at least one of the following conditions is met: eAOO = HVACTYPES.eManBin.Auto (switching back to automatic mode of the manual override - hardware) xQuit = TRUE (reset of the monitors is active) xFbControl = FALSE (operating monitoring blocked)
Air shortage monitoring xAlarmPFb
The air shortage monitoring is carried out by evaluating the states at the inputs xPFb or xFb. The fault message of the air shortage monitoring xAlarmPFb is activated (= TRUE) if, with monitoring enabled (xPFbControl = TRUE) during the message delay of the air shortage monitoring udiPFbControlTime the input xPFb is permanently not active (= FALSE) and the input xFb is active (= TRUE). The fault message of the air shortage monitoring xAlarmPFb is deactivated (= FALSE) if the conditions for activation are no longer met and at the same time the monitoring is blocked (xPFbControl = FALSE) and / or the reset of the fault messages (monitors) active (xQuit = TRUE).
Collective fault message 1 - output xAlarm
The collective fault message is activated (= TRUE) if at least one of the conditions described below is met. xAlarmIn = TRUE (fault message of the fan is active) xAlarmFB = TRUE (fault from the operating monitoring) xAlarmPFB = TRUE (fault from the air shortage monitoring) xMSwitch = FALSE (maintenance switch in Off position) xAlarmMaxValue = TRUE (maximum value exceeded) xAlarmMinValue = TRUE (minimum value undershot) In all other cases the collective fault is not active (= FALSE).
Collective fault message 2
The collective fault message is activated (= TRUE) if at least one of the conditions described below is met. xAlarmIn = TRUE (fault message of the fan is active) xAlarmFB = TRUE (fault from the operating monitoring) xAlarmPFB = TRUE (fault from the air shortage monitoring) xMSwitch = FALSE (maintenance switch in Off position) xAlarmMaxValue = TRUE (maximum value exceeded) In all other cases the collective fault is not active (= FALSE).
Resetting the fault messages xQuit
Every rising edge (FALSE > TRUE) at the input xQuit clears any fault messages that may be present from the following monitoring devices: Air shortage monitoring Operation monitoring Minimum value monitoring Maximum value monitoring
Control process
General The actual value rActValue is scaled by a linear characteristic curve and fed to the PI controller. The setpoint rSetPoint is filtered by a signal ramp, scaled by a linear characteristic curve and fed to the PI controller. The output signal of the PI controller is filtered by another signal ramp and fed to the output for the control signal rHA. Enable The control process is enabled with a time delay of udiWaitControl after the active fan operating message (xFb = TRUE). The control process is blocked without time delay after the inactive fan operating message (xFb = FALSE). Setpoint The setpoint is fixed to value 0.0 if the fan enable is not active (xHB = FALSE). The setpoint is taken from input rSetPoint, filtered by a signal ramp and scaled by a linear function defined by 2 points (prerequisite: xHB = TRUE). The relevant parameters of the signal ramp can be set individually (maximum variation = (rMaxValue / 5) per 10s). The relevant parameters of the linear function can be set individually (input range in Pa: 0.0 - rMaxValue, output range in %: 0.0 - 100.0). Actual value The actual value is taken from input rActValue and scaled by a linear function defined by 2 points. The relevant parameters of the linear function can be set individually (input range in Pa: 0.0 - rMaxValue, output range in %: 0.0 - 100.0). Limitation of the PI controller output signal rYMin and rYMax The controller output signal (PI controller) is limited by the adjustable limit values rYMin and rYMax (minimum value monitoring not active) or rSubstitueHA (minimum value monitoring active). Signal ramp of the output signal from the PI controller The output signal from the PI controller is filtered by a signal ramp. The relevant parameters of the signal ramp can be set individually (maximum variation = rYRampVariation per rYRampTime). Parameters of the PI controller The parameters essential for the control behavior can be specified externally. They must be adapted depending on the controlled system. A useful base parameterization has already been made, which is sufficient in many applications. rYMin = Lower absolute limit value of the controller output signal rYMax = Upper absolute limit value of the controller output signal rOffset = Setpoint offset - controller rKp = Gain factor - controller rTn = Reset time - controller in s eAction = Direction of action of the controller (inverted, direct) rInitValue = Initialization value for the control signal rYDisabled = Control signal when controller is inactive Signals of the PI controller The signals calculated during the control process (before the signal ramp) are available for monitoring the control process. rPiDiff = Control deviation at the controller rPiPartP = Proportional component of the control signal rPiPartI = Integral component of the control signal xPiLimitActiv = Status - limit value exceeded - control signal (FALSE = Off, TRUE = On) Controller output signal When the controller is not enabled, the switch-off value rYDisabled is transferred to the controller output signal output (prerequisite: ePiManModeN = eMANNUM.Auto) and limited by the absolute limit values. The integral component is set to 0.0. When the controller is enabled, the controller output signal is calculated (prerequisite: ePiManModeN = eMANNUM.Auto) and limited by the absolute limit values. With the default setting of the direction of action eAction (= eControlMode.Inverted), an actual value that is too low (actual value < setpoint) causes a continuous increase in the value of the controller output signal.
Control signal fan before manual override rAA
The control signal of the fan before manual override rAA is primarily adopted from the controller output signal after the signal ramp. However, this output signal is additionally limited during the fan request (xHB = TRUE) by the lower absolute limit value rYMin limited downward. In the event of a minimum value undershoot (xAlarmMinValue = TRUE) the control signal before manual override rAA by the fixed value rSubstitueHA is replaced.
Control signal fan after manual override rHA
The fan control signal after manual override rHA corresponds to the control signal of the fan before manual override rAA additionally extended by a manual override module.
rAA
eManModeN
rHA
Notes
X
eMANNUM.Auto
rAA
Manual override module in automatic mode
X
eMANNUM.Man
eManValue
Manual override module in manual mode
Legend: X = any
Operating mode for the controller output signal ePIManModeN
The parameter ePiManModeN allows switching the controller output signal from automatic to manual mode and vice versa. In manual mode, the controller output signal adopts the output signal in manual mode ePiManValue.
ePiManModeN
output signal
Function
eMANNUM.Auto
Signal according to formula / switch-off value
Automatic mode - output signal
eMANNUM.Man
ePiManValue
Manual mode - output signal
Monitoring of maximum pressure xAlarmMaxValue
The output xAlarmMaxValue is activated (= TRUE) if, over a minimum duration of 10 s, the current actual value rActValue the adjustable maximum value rMaxValue exceeds. The output xAlarmMaxValue is deactivated (= FALSE) if the current actual value rActValue the adjustable maximum value rMaxValue falls below and at the same time at the input xQuit a rising edge (FALSE > TRUE) is detected.
Monitoring of minimum pressure xAlarmMinValue
The output xAlarmMinValue is activated (= TRUE) if, over a minimum duration udiWaitMinValue (1.0 - 600.0 s) the following conditions are continuously met simultaneously: xFb = TRUE (fan is in operation) eAO = HVACTYPES.eManNum.Auto (manual override operating mode - hardware for the control signal in automatic mode) rHA > rMinHAValue (control signal is greater than the minimum value) rActValue < rMinValue (actual value is smaller than the minimum value) No rising edge (FALSE > TRUE) was detected at the input xQuit detected The output xAlarmMinValue is deactivated (= FALSE) if the activation conditions are no longer met and at the same time at the input xQuit a rising edge (FALSE > TRUE) is detected.
Collective automatic operation message xAuto
The collective automatic operation message xAuto is activated (= TRUE) if the following conditions are simultaneously met:
Input eAOO = HVACTYPES.eManBin.Auto
Input eAO = HVACTYPES.eManNum.Auto
Setpoint / parameter eManModeB = eMANBIN.Auto
Setpoint / parameter eManModeN = eMANNUM.Auto
Setpoint / parameter ePiManModeN = eMANNUM.Auto
CODESYS
InOut:
Input
xEn
BOOL
Input
xForce
BOOL
FALSE
Input
xFb
BOOL
Input
xPFb
BOOL
Input
xMSwitch
BOOL
TRUE
Input
xAlarmIn
BOOL
Input
eAOO
eManBin
eManBin.Auto
Input
eAO
eManNum
eManNum.Auto
Input
rPoti
REAL
Input
rU
REAL
Input
xQuit
BOOL
FALSE
Input
rActValue
REAL
Input
rSetPoint
REAL
Output
xHB
BOOL
Output
xAB
BOOL
Output
rHA
REAL
Output
rAA
REAL
Output
xAlarmFb
BOOL
Output
xAlarmPFb
BOOL
Output
xAlarmMinValue
BOOL
Output
xAlarmMaxValue
BOOL
Output
dtLastFb
DT
Output
udiOperatingHours
UDINT
Output
udiCountFb
UDINT
Output
xAlarm
BOOL
Output
xAuto
BOOL
Output
rPiDiff
REAL
Output
rPiPartP
REAL
Output
rPiPartI
REAL
Output
xPiLimitActiv
BOOL
Input Const
rMaxValue
REAL
490
Input Const
rSubstituteHA
REAL
30
Input Const
udiWaitMinValue
UDINT
60
Input Const
rMinHAValue
REAL
20
Input Const
rMinValue
REAL
20
Input Const
tYRampTime
TIME
TIME#1m0s0ms
Input Const
rYRampVariation
REAL
30
Input Const
udiWaitControl
UDINT
30
Input Const
rYMax
REAL
100
Input Const
rYMin
REAL
20
Input Const
rTn
REAL
60
Input Const
rKp
REAL
1
Input Const
rOffset
REAL
0
Input Const
rInitValue
REAL
20
Input Const
rYDisabled
REAL
0
Input Const
eAction
eControlMode
eControlMode.Inverted
Input Const
ePiManValue
REAL
Input Const
ePiManModeN
eMANNUM
eMANNUM.Auto
Input Const
udiPFbControlTime
UDINT
60
Input Const
xPFbControl
BOOL
TRUE
Input Const
xAlarmControl
BOOL
TRUE
Input Const
udiFbControlTime
UDINT
60
Input Const
xFbControl
BOOL
TRUE
Input Const
rManValue
REAL
Input Const
eManModeN
eMANNUM
eMANNUM.Auto
Input Const
eManModeB
eMANBIN
eMANBIN.Auto
Methods:
mQuit
mResetOperatingHours
Structure:
mQuit (Method)
mResetOperatingHours (Method)
Last updated

