For the complete documentation index, see llms.txt. This page is also available as Markdown.

FanControl

FanControl (FB)

FUNCTION_BLOCK FanControl

Short description

Control of a variable-speed fan (control variables e.g. absolute pressure, differential pressure) Additional functions: manual overrides, maintenance switch, operating hours counter, operation monitoring, air shortage monitoring, limit value monitoring Typical application: control of a fan with frequency converter

Representation

Functional description

General

This function block controls a variable-speed fan using a continuous control signal rHA. The general enable of the fan is via the request xEn and the enable signal xHB. Speed control is performed by means of a freely parameterizable PI controller, to which the setpoint rSetPoint and the actual value rActValue are supplied and from these the controller output signal is generated. Essentially the following function blocks are used:

  • ControlPI

  • ManBin

  • ManNum

  • TwoPointFun

  • Ramp

  • CTime

  • AirShortage

  • OperatingHours

Enable - fan before manual override xAB

The enable - fan before manual override xAB is activated (= TRUE) if the following conditions are simultaneously met: Case 1: xEn = TRUE xMSwitch = TRUE xAlarmControl = FALSE Case 2: xEn = TRUE xMSwitch = TRUE xAlarmControl = TRUE xAlarm = FALSE In all other situations, the enable - fan before manual override xAB is not activated (= FALSE).

Enable - fan after manual override xHB

The enable - fan after manual override xHB corresponds to the enable - fan before manual override xAB, additionally extended by a manual override module. The enable can generally only be given if the forced lockout of the fan after manual override is not active (xForce = FALSE) and collective fault message 2 is not active (= FALSE).

xAB

eManModeB

xHB

Notes

FALSE

eMANBIN.Auto

FALSE

Manual override module in automatic mode

TRUE

eMANBIN.Auto

TRUE

Manual override module in automatic mode

X

eMANBIN.ManOn

TRUE

Manual override module in manual mode On

X

eMANBIN.ManOff

FALSE

Manual override module in manual mode Off

Legend: X = any

Maintenance switch message xMSwitch

xMSwitch = TRUE: repair switch has not been triggered (normal state) xMSwitch = FALSE: maintenance switch has tripped (fault state)

Forced lockout of the fan after manual override xForce

xForce = FALSE: no forced lockout (normal state) xForce = TRUE: forced lockout (exception state)

Operating hours and switch-on cycles udiOperatingHours and udiCountFb

The number of operating hours and switch-on cycles are recorded (= counting process active) if the fan operating signal xFb is active and at the same time collective fault message 2 is not active (= FALSE). The results are available at the counter outputs udiOperatingHours and udiCountFb .

Write access to the counter values

Via the path ‘InstanceName._OperatingHours.udiOperatingHours’ or ‘InstanceName._OperatingHours.udiCountFb’, write access to both counter values is possible.

Prerequisite for using the FanControl function block

For correct operation, the use of the TimeRead2 function block is required.

Date / time of the fan's last operation dtLastFb

At output dtLastFb the current date / current time is available during the counting process. At output dtLastFb the date / time at the end of the last counting process is available outside the counting process. At output dtLastFb the initialization value DT#1970-1-1-0.0.0 is output before the first counting process.

Operating supervision xAlarmFb

The operating monitoring can be enabled or disabled by the setpoint / parameter xFbControl (= TRUE) or blocked (= FALSE). When monitoring is blocked, the fault message of the operating monitoring xAlarmFb is always blocked (= FALSE). When monitoring is enabled, the fault message of the operating monitoring xAlarmFb is activated (= TRUE) if the following states are present simultaneously during a minimum time period udiFbControlTime the following states are given: xHB and xFb = unequal (enable state and operating state do not match) eAOO = HVACTYPES.eManBin.Auto (manual override - hardware for enable in automatic mode) xFbControl = TRUE (operating monitoring is enabled) The fault message of the operating monitoring xAlarmFb is reset (= FALSE) if at least one of the following conditions is met: eAOO = HVACTYPES.eManBin.Auto (switching back to automatic mode of the manual override - hardware) xQuit = TRUE (reset of the monitors is active) xFbControl = FALSE (operating monitoring blocked)

Air shortage monitoring xAlarmPFb

The air shortage monitoring is carried out by evaluating the states at the inputs xPFb or xFb. The fault message of the air shortage monitoring xAlarmPFb is activated (= TRUE) if, with monitoring enabled (xPFbControl = TRUE) during the message delay of the air shortage monitoring udiPFbControlTime the input xPFb is permanently not active (= FALSE) and the input xFb is active (= TRUE). The fault message of the air shortage monitoring xAlarmPFb is deactivated (= FALSE) if the conditions for activation are no longer met and at the same time the monitoring is blocked (xPFbControl = FALSE) and / or the reset of the fault messages (monitors) active (xQuit = TRUE).

Collective fault message 1 - output xAlarm

The collective fault message is activated (= TRUE) if at least one of the conditions described below is met. xAlarmIn = TRUE (fault message of the fan is active) xAlarmFB = TRUE (fault from the operating monitoring) xAlarmPFB = TRUE (fault from the air shortage monitoring) xMSwitch = FALSE (maintenance switch in Off position) xAlarmMaxValue = TRUE (maximum value exceeded) xAlarmMinValue = TRUE (minimum value undershot) In all other cases the collective fault is not active (= FALSE).

Collective fault message 2

The collective fault message is activated (= TRUE) if at least one of the conditions described below is met. xAlarmIn = TRUE (fault message of the fan is active) xAlarmFB = TRUE (fault from the operating monitoring) xAlarmPFB = TRUE (fault from the air shortage monitoring) xMSwitch = FALSE (maintenance switch in Off position) xAlarmMaxValue = TRUE (maximum value exceeded) In all other cases the collective fault is not active (= FALSE).

Resetting the fault messages xQuit

Every rising edge (FALSE > TRUE) at the input xQuit clears any fault messages that may be present from the following monitoring devices: Air shortage monitoring Operation monitoring Minimum value monitoring Maximum value monitoring

Control process

General The actual value rActValue is scaled by a linear characteristic curve and fed to the PI controller. The setpoint rSetPoint is filtered by a signal ramp, scaled by a linear characteristic curve and fed to the PI controller. The output signal of the PI controller is filtered by another signal ramp and fed to the output for the control signal rHA. Enable The control process is enabled with a time delay of udiWaitControl after the active fan operating message (xFb = TRUE). The control process is blocked without time delay after the inactive fan operating message (xFb = FALSE). Setpoint The setpoint is fixed to value 0.0 if the fan enable is not active (xHB = FALSE). The setpoint is taken from input rSetPoint, filtered by a signal ramp and scaled by a linear function defined by 2 points (prerequisite: xHB = TRUE). The relevant parameters of the signal ramp can be set individually (maximum variation = (rMaxValue / 5) per 10s). The relevant parameters of the linear function can be set individually (input range in Pa: 0.0 - rMaxValue, output range in %: 0.0 - 100.0). Actual value The actual value is taken from input rActValue and scaled by a linear function defined by 2 points. The relevant parameters of the linear function can be set individually (input range in Pa: 0.0 - rMaxValue, output range in %: 0.0 - 100.0). Limitation of the PI controller output signal rYMin and rYMax The controller output signal (PI controller) is limited by the adjustable limit values rYMin and rYMax (minimum value monitoring not active) or rSubstitueHA (minimum value monitoring active). Signal ramp of the output signal from the PI controller The output signal from the PI controller is filtered by a signal ramp. The relevant parameters of the signal ramp can be set individually (maximum variation = rYRampVariation per rYRampTime). Parameters of the PI controller The parameters essential for the control behavior can be specified externally. They must be adapted depending on the controlled system. A useful base parameterization has already been made, which is sufficient in many applications. rYMin = Lower absolute limit value of the controller output signal rYMax = Upper absolute limit value of the controller output signal rOffset = Setpoint offset - controller rKp = Gain factor - controller rTn = Reset time - controller in s eAction = Direction of action of the controller (inverted, direct) rInitValue = Initialization value for the control signal rYDisabled = Control signal when controller is inactive Signals of the PI controller The signals calculated during the control process (before the signal ramp) are available for monitoring the control process. rPiDiff = Control deviation at the controller rPiPartP = Proportional component of the control signal rPiPartI = Integral component of the control signal xPiLimitActiv = Status - limit value exceeded - control signal (FALSE = Off, TRUE = On) Controller output signal When the controller is not enabled, the switch-off value rYDisabled is transferred to the controller output signal output (prerequisite: ePiManModeN = eMANNUM.Auto) and limited by the absolute limit values. The integral component is set to 0.0. When the controller is enabled, the controller output signal is calculated (prerequisite: ePiManModeN = eMANNUM.Auto) and limited by the absolute limit values. With the default setting of the direction of action eAction (= eControlMode.Inverted), an actual value that is too low (actual value < setpoint) causes a continuous increase in the value of the controller output signal.

Control signal fan before manual override rAA

The control signal of the fan before manual override rAA is primarily adopted from the controller output signal after the signal ramp. However, this output signal is additionally limited during the fan request (xHB = TRUE) by the lower absolute limit value rYMin limited downward. In the event of a minimum value undershoot (xAlarmMinValue = TRUE) the control signal before manual override rAA by the fixed value rSubstitueHA is replaced.

Control signal fan after manual override rHA

The fan control signal after manual override rHA corresponds to the control signal of the fan before manual override rAA additionally extended by a manual override module.

rAA

eManModeN

rHA

Notes

X

eMANNUM.Auto

rAA

Manual override module in automatic mode

X

eMANNUM.Man

eManValue

Manual override module in manual mode

Legend: X = any

Operating mode for the controller output signal ePIManModeN

The parameter ePiManModeN allows switching the controller output signal from automatic to manual mode and vice versa. In manual mode, the controller output signal adopts the output signal in manual mode ePiManValue.

ePiManModeN

output signal

Function

eMANNUM.Auto

Signal according to formula / switch-off value

Automatic mode - output signal

eMANNUM.Man

ePiManValue

Manual mode - output signal

Monitoring of maximum pressure xAlarmMaxValue

The output xAlarmMaxValue is activated (= TRUE) if, over a minimum duration of 10 s, the current actual value rActValue the adjustable maximum value rMaxValue exceeds. The output xAlarmMaxValue is deactivated (= FALSE) if the current actual value rActValue the adjustable maximum value rMaxValue falls below and at the same time at the input xQuit a rising edge (FALSE > TRUE) is detected.

Monitoring of minimum pressure xAlarmMinValue

The output xAlarmMinValue is activated (= TRUE) if, over a minimum duration udiWaitMinValue (1.0 - 600.0 s) the following conditions are continuously met simultaneously: xFb = TRUE (fan is in operation) eAO = HVACTYPES.eManNum.Auto (manual override operating mode - hardware for the control signal in automatic mode) rHA > rMinHAValue (control signal is greater than the minimum value) rActValue < rMinValue (actual value is smaller than the minimum value) No rising edge (FALSE > TRUE) was detected at the input xQuit detected The output xAlarmMinValue is deactivated (= FALSE) if the activation conditions are no longer met and at the same time at the input xQuit a rising edge (FALSE > TRUE) is detected.

Collective automatic operation message xAuto

The collective automatic operation message xAuto is activated (= TRUE) if the following conditions are simultaneously met:

  • Input eAOO = HVACTYPES.eManBin.Auto

  • Input eAO = HVACTYPES.eManNum.Auto

  • Setpoint / parameter eManModeB = eMANBIN.Auto

  • Setpoint / parameter eManModeN = eMANNUM.Auto

  • Setpoint / parameter ePiManModeN = eMANNUM.Auto

CODESYS

InOut:

Scope
Name
Type
Initial

Input

xEn

BOOL

Input

xForce

BOOL

FALSE

Input

xFb

BOOL

Input

xPFb

BOOL

Input

xMSwitch

BOOL

TRUE

Input

xAlarmIn

BOOL

Input

eAOO

eManBin

eManBin.Auto

Input

eAO

eManNum

eManNum.Auto

Input

rPoti

REAL

Input

rU

REAL

Input

xQuit

BOOL

FALSE

Input

rActValue

REAL

Input

rSetPoint

REAL

Output

xHB

BOOL

Output

xAB

BOOL

Output

rHA

REAL

Output

rAA

REAL

Output

xAlarmFb

BOOL

Output

xAlarmPFb

BOOL

Output

xAlarmMinValue

BOOL

Output

xAlarmMaxValue

BOOL

Output

dtLastFb

DT

Output

udiOperatingHours

UDINT

Output

udiCountFb

UDINT

Output

xAlarm

BOOL

Output

xAuto

BOOL

Output

rPiDiff

REAL

Output

rPiPartP

REAL

Output

rPiPartI

REAL

Output

xPiLimitActiv

BOOL

Input Const

rMaxValue

REAL

490

Input Const

rSubstituteHA

REAL

30

Input Const

udiWaitMinValue

UDINT

60

Input Const

rMinHAValue

REAL

20

Input Const

rMinValue

REAL

20

Input Const

tYRampTime

TIME

TIME#1m0s0ms

Input Const

rYRampVariation

REAL

30

Input Const

udiWaitControl

UDINT

30

Input Const

rYMax

REAL

100

Input Const

rYMin

REAL

20

Input Const

rTn

REAL

60

Input Const

rKp

REAL

1

Input Const

rOffset

REAL

0

Input Const

rInitValue

REAL

20

Input Const

rYDisabled

REAL

0

Input Const

eAction

eControlMode

eControlMode.Inverted

Input Const

ePiManValue

REAL

Input Const

ePiManModeN

eMANNUM

eMANNUM.Auto

Input Const

udiPFbControlTime

UDINT

60

Input Const

xPFbControl

BOOL

TRUE

Input Const

xAlarmControl

BOOL

TRUE

Input Const

udiFbControlTime

UDINT

60

Input Const

xFbControl

BOOL

TRUE

Input Const

rManValue

REAL

Input Const

eManModeN

eMANNUM

eMANNUM.Auto

Input Const

eManModeB

eMANBIN

eMANBIN.Auto

Methods:

mQuit

mResetOperatingHours

Structure:

  • mQuit (Method)

  • mResetOperatingHours (Method)

Last updated