BurnerP
BurnerP (FB)
BurnerP (FB)FUNCTION_BLOCK BurnerP
Short description
Control of a heat generator (temperature control via analog power signal 0.0 - 100.0 %) Typical application: heat generation
Representation

Function description
General
This function block is used to control / regulate a heat generator depending on the demand of the heat generator xEn, the flow setpoint temperature rSetPtTemp and the flow temperature rFdT. The enable / disable of the heat generator is done via the output xHB ( FALSE = lockout, TRUE = enable ). The flow temperature control (analog also boiler temperature control) is performed by a power controller (PI controller) via the analog output rHa in the range of rYMin to rYMax. The enabling of the controller is delayed (setpoint / parameter udiWaitControl ) after the running feedback ( xFb = TRUE ) of the heat generator. The following function blocks are essentially used:
ControlPI
OperatingHours
ManBin
ManNum
Enable / disable of the heat generator
The enabling of the heat generator ( xAB = TRUE, xHB = TRUE ( eManModeB = eManBin.Auto )) occurs if the flow temperature rFdT the sum of flow setpoint temperature rSetPtTemp and setpoint / parameter rSwitchOnPoint falls below, at the same time the general enable xEn active ( = TRUE ) and the minimum off time is not active. The disabling of the heat generator ( xAB = FALSE, xHB = FALSE ( eManModeB = eManBin.Auto )) occurs if the flow temperature rFdT the sum of flow setpoint temperature rSetPtTemp and setpoint / parameter rSwitchOffPoint exceeds and at the same time the general enable xEn active ( = TRUE ). A minimum off time (duration = udiTimeMinOff, display - remaining time: tOnDelay ) is always inserted between two consecutive operating cycles. The minimum off time always begins with the falling edge ( TRUE > FALSE ) at the input xFb.
Temperature control of the heat generator
The enabling of the temperature control is delayed (duration = udiWaitControl, display - remaining time: tOnControlDelay ) after the active operation message ( xFb = TRUE ) of the heat generator. The disabling of the temperature control occurs immediately after the inactive running feedback ( xFb = FALSE ) of the heat generator (power signal - heat generator before manual override rAA in the locked state = rYDisabled ). The internal power controller (PI controller, output range: rYMin to rYMax ) is enabled/disabled with the temperature control. (setpoint = flow set temperature rSetPtTemp, actual value = flow temperature rFdT ). The parameters of the internal power controller can be configured individually: Power controller - upper absolute limit of the output signal in % : rYMax Power controller - lower absolute limit of the output signal in % : rYMin Power controller - reset time in s : rTn Power controller - gain factor : rKp Power controller - offset temperature in °C : rOffset Power controller - initialization value for the output signal in % : rInitValue Power controller - switch-off value in % : rYDisabled The output signal of the power controller is fed directly to the output rAA supplied.
Manual override of the digital output xHB
The enable/disable of the heat generator ( xHB ) can be operated either in automatic mode ( eMANBIN.Auto ) or in one of the two manual modes ( eMANBIN.ManOn, eMANBIN.ManOff ).
xAB
eMANBIN
xHB
Notes
FALSE
eMANBIN.Auto
FALSE
Manual override module in automatic
TRUE
eMANBIN.Auto
TRUE
Manual override module in automatic
X
eMANBIN.ManOn
TRUE
Manual override module in manual operation On
X
eMANBIN.ManOff
FALSE
Manual override module in manual operation Off
Legend: X = don't care
Manual override of the analog output rHA
The output signal of the power controller ( rHA ) can be operated either in automatic mode ( eMANNUM.Auto ) or in manual mode ( eMANNUM.Man ).
rAA
eMANNUM
rHA
Notes
Value
eMANNUM.Auto
Value
Manual override module in automatic
X
eMANNUM.Man
rManValue
Manual override module in manual operation
Legend: X = don't care
Aggregate fault xAlarm
The aggregate fault xAlarm is active ( = TRUE ) if the fault message of the heat generator xAlarmIn is active ( = TRUE ). In all other situations the aggregate fault xAlarm is not active ( = FALSE ).
Collective automatic mode message xAuto
The collective automatic mode message xAuto is set active ( = TRUE ) if the following conditions are met simultaneously:\
Input eAOO = HVACTYPES.eManBin.Auto
Input eAO = HVACTYPES.eManNum.Auto
Setpoint / parameter eManModeB = eMANBIN.Auto
Setpoint / parameter eManModeN = eMANNUM.Auto
Operating hours counter - heat generator
The operating hours counter ( udiOperatingHours, udiCountFb ) for the heat generator is active when the running feedback is active ( xFb = TRUE ).
Write access to the counters
Via the path ‘InstanceName._OperatingHours.udiOperatingHours’ or ‘InstanceName._OperatingHours.udiCountFb’ a write access to both counter values is possible.\
Prerequisite for using the function block BurnerP
The use of the TimeRead2 function block is required for correct operation.
Feedback of the heat generator output rU
The current actual Output of the heat generator can be connected to the input rU . This input is currently not used for control and regulation purposes.
Feedback of the manual value for the power signal from the manual override - hardware rPoti
The feedback of the manual value can be at the input rPoti . This input is currently not used for control and regulation purposes.
Inactive state ( xEn = FALSE )
xHB
xAB
rHA
rAA
tOnDelay
tOnControlDelay
dtLastFb
udiOperatingHours
udiCountFb
xAlarm
xAuto
Notes
FALSE ( eManModeB = eManBin.Auto )
FALSE
rYDisabled ( eManModeN = eManNum.Auto )
rYDisabled
old value
old value
old value
old value
old value
State of xAlarmIn
old value
xEn = FALSE
Legend: X = don't care
CODESYS
InOut:
Input
xEn
BOOL
Input
rSetPtTemp
REAL
Input
xFb
BOOL
Input
rU
REAL
0
Input
xAlarmIn
BOOL
Input
eAOO
eManBin
eManBin.Auto
Input
eAO
eManNum
eManNum.Auto
Input
rPoti
REAL
Input
rFdT
REAL
Output
xHB
BOOL
Output
xAB
BOOL
Output
rHA
REAL
Output
rAA
REAL
Output
tOnDelay
TIME
Output
tOnControlDelay
TIME
Output
dtLastFb
DT
Output
udiOperatingHours
UDINT
Output
udiCountFb
UDINT
Output
xAlarm
BOOL
Output
xAuto
BOOL
Input Const
udiTimeTOFxFb
UDINT
7
Input Const
rYMax
REAL
100
Input Const
rYMin
REAL
0
Input Const
rTn
REAL
200
Input Const
rKp
REAL
2
Input Const
rOffset
REAL
0
Input Const
rInitValue
REAL
0
Input Const
rYDisabled
REAL
0
Input Const
udiWaitControl
UDINT
3
Input Const
rSwitchOffPoint
REAL
2.5
Input Const
rSwitchOnPoint
REAL
-2.5
Input Const
udiTimeMinOff
UDINT
3
Input Const
rManValue
REAL
0
Input Const
eManModeN
eMANNUM
eMANNUM.Auto
Input Const
eManModeB
eMANBIN
eMANBIN.Auto
Last updated

