For the complete documentation index, see llms.txt. This page is also available as Markdown.

FireDamperMot

FireDamperMot (FB)

FUNCTION_BLOCK FireDamperMot

Short description

Control of a motorized fire damper with two position feedback signals Additional functions: functional test of the fire damper Typical application: control of a fire damper in an HVAC system

Representation

Functional description

General

This function block controls a binary motorized fire damper(xEn = TRUE), monitors the runtimes during the opening and closing process and can perform a complete fire damper test. The function block can operate either in normal mode or in test mode. Test mode has a higher priority than normal mode and can be triggered by a rising edge at the input xTestEx and / or at the setpoint / parameter xRunTest be triggered.

Enable opening / closing of the fire damper before manual override xAB

The enable for opening / closing of the fire damper before manual override xAB is taken unchanged from the request to open / close the fire damper xEn if the fire damper test is not active.

Enable opening / closing of the fire damper after manual override xHB

The enable for opening / closing of the fire damper after manual override xHB corresponds to the enable for opening / closing of the fire damper before manual override xAB additionally extended by a manual override module

xAB

eManModeB

xHB

Notes

FALSE

eMANBIN.Auto

FALSE

Manual override module in automatic mode

TRUE

eMANBIN.Auto

TRUE

Manual override module in automatic mode

X

eMANBIN.ManOn

TRUE

Manual override module in manual mode On

X

eMANBIN.ManOff

FALSE

Manual override module in manual mode Off

Legend: X = any

Collective fault xAlarm

The collective fault xAlarm is activated (= TRUE) if at least one of the following conditions is met:

  1. The fault message for the opening feedback xAlarmOpen is active (= TRUE).

  2. The fault message for the closing feedback xAlarmClosed is active (= TRUE).

  3. The fire damper is not fully open (xOpen = FALSE). (Background: Any fire damper that is not fully open represents a faulty state).

  4. The input *xAlarmIn* is active (= TRUE). In all other cases, the collective fault xAlarm is not activated (= FALSE).

Enable / disable the fault message for the opening feedback xAlarmOpen

Monitoring the damper runtime during the opening process to an adjustable maximum value (tOpen) starts if, in normal mode, at least one of the following conditions is met:

  1. A rising edge (FALSE > TRUE) is detected at the output xHB detected (= standard case).

  2. The request to open is active (xEn = TRUE) and at the same time a rising edge (FALSE > TRUE) is detected at the input xQuit.

  3. The output xHB is active (= TRUE) and at the same time a falling edge (TRUE > FALSE) is detected at the input xOpen.

The fault message for the opening feedback xAlarmOpen* is activated (= TRUE) if, after the maximum runtime has elapsed tOpen with the output active (xHB = TRUE), at least one of the following conditions is met:

  1. The feedback for full opening is not active (xOpen = FALSE) (= standard case).

  2. The feedback signals xOpen or xClosed have the same state.

The fault message for the opening feedback xAlarmOpen is deactivated (= FALSE) if a rising edge (FALSE > TRUE) is detected at the input xQuit.

Enable / disable the fault message for the closing feedback xAlarmClosed

Monitoring the damper runtime during the closing process to an adjustable maximum value (tclose) starts if, in normal mode, at least one of the following conditions is met:

1) A falling edge (TRUE > FALSE) is detected at the output xHB detected (= standard case). 2) The request to close is active (xEn = FALSE) and at the same time a rising edge (FALSE > TRUE) is detected at the input xQuit. The fault message for the closing feedback xAlarmClosed is activated (= TRUE) if, after the maximum runtime tClose has elapsed, with the output not active (xHB = FALSE), at least one of the following conditions is met: 1) The feedback for full closing is not active (xClosed = FALSE) (= standard case). 2) The feedback signals xOpen and xClosed have the same state. The fault message for the closing feedback xAlarmClosed is deactivated (= FALSE) if a rising edge (FALSE > TRUE) is detected at the input xQuit.

Duration of the last complete opening tLastOpen

The duration measurement begins whenever at least one of the following conditions is met:

1) A rising edge (FALSE > TRUE) is detected at the input xOpen detected. 2) A falling edge (TRUE > FALSE) is detected at the input xOpen. 3) A rising edge (FALSE > TRUE) is detected at the input xClosed. 4) A falling edge (TRUE > FALSE) is detected at the input xClosed. (standard case) 5) A rising edge (FALSE > TRUE) is detected at the output xHB. 6) A falling edge (TRUE > FALSE) is detected at the output xHB. At this output, the runtime is available after each rising edge at the feedback for full opening xOpen (FALSE > TRUE).

Duration of the last complete closing tLastClosed

The duration measurement begins whenever at least one of the following conditions is met:

1) A rising edge (FALSE > TRUE) is detected at the input xOpen detected. 2) A falling edge (TRUE > FALSE) is detected at the input xOpen. (standard case) 3) A rising edge (FALSE > TRUE) is detected at the input xClosed. 4) A falling edge (TRUE > FALSE) is detected at the input xClosed. 5) A rising edge (FALSE > TRUE) is detected at the output xHB. 6) A falling edge (TRUE > FALSE) is detected at the output xHB. At this output, the runtime is available after each rising edge at the feedback for full closing xClosed (FALSE > TRUE).

Duration of the current opening / closing in tRunTime

At this output, the current runtime is available during each runtime measurement.

Testing the functions of the fire damper (test mode)

Test mode is always generally triggered if at least one of the following conditions is met:

1) A rising edge (FALSE > TRUE) is detected at the input xTestEx detected. 2) The active state (= TRUE) is detected at the setpoint / parameter xRunTest. The active state is reset immediately after detection to (= FALSE). However, the actual test mode only takes place if the feedback from automatic mode eAOO (0 = automatic, >0 = manual mode) contains the value 0 and, at the same time, the manual override mode for the digital output xHB signals automatic mode (eMANBIN = eMANBIN.Auto). In test mode, the fire damper is closed and then opened, each with runtime monitoring. At the start of test mode, the outputs xAlarmOpen, xAlarmClosed, tTestOpen, tTestClosed and xTestOK are reset (= FALSE). Now the control command for closing is triggered and the runtime is monitored for exceeding the maximum value tClosed monitored. If the correct feedback situation (xClosed = TRUE and xOpen = FALSE) is reached without exceeding the maximum value, output xAlarmClosed is not activated (= FALSE). In all other situations, output xAlarmClosed is activated (= TRUE). Now the control command for opening is triggered and the runtime is monitored for exceeding the maximum value tOpen monitored. If the correct feedback situation (xOpen = TRUE and xClosed = FALSE) is reached without exceeding the maximum value, output xAlarmOpen is not activated (= FALSE). In all other situations, output xAlarmOpen is activated (= TRUE). The result indicator for the fire damper test xTestOK is activated (= test successful) if neither of the two outputs xAlarmOpen nor xAlarmClosed is active (= TRUE). The achieved values tLastOpen and tLastClosed are each assigned to the outputs tTestOpen and tTestClosed and stored until the next fire damper test. The test mode ends automatically as soon as the fire damper test is completed.

Requirements

Prerequisite for using the function block FireDamperMot

For correct operation, the use of the TimeRead2 function block is required.

CODESYS

InOut:

Scope
Name
Type
Initial

Input

xEn

BOOL

Input

xAlarmIn

BOOL

FALSE

Input

eAOO

eManBin

eManBin.Auto

Input

xOpen

BOOL

Input

xClosed

BOOL

Input

xQuit

BOOL

FALSE

Input

xTestEx

BOOL

FALSE

Output

sLine1

STRING

Output

sLine2

STRING

Output

sText

STRING

Output

xHB

BOOL

Output

xAB

BOOL

Output

xAlarm

BOOL

Output

xAlarmOpen

BOOL

Output

xAlarmClosed

BOOL

Output

xTestOK

BOOL

Output

tLastOpen

TIME

Output

tLastClosed

TIME

Output

tTestOpen

TIME

Output

tTestClosed

TIME

Output

tRunTime

TIME

Output

xAuto

BOOL

Input Const

udiOpen

UDINT

150

Input Const

udiClose

UDINT

25

Input Const

eManModeB

eMANBIN

eMANBIN.Auto

Input Const

xRunTest

BOOL

FALSE

Input Const

sEditLine2

STRING

‘’

Input Const

sEditLine1

STRING

‘Room’

Last updated