For the complete documentation index, see llms.txt. This page is also available as Markdown.

FilterMonitoringA

FilterMonitoringA (FB)

FUNCTION_BLOCK FilterMonitoringA

Short description

Detection of filter contamination and generation of a fault message Typical application: Monitoring the contamination of an air filter with a differential pressure sensor

Representation

Functional description

General

This function block is used to detect filter contamination by evaluating the input for the differential pressure sensor rPressure. If the differential pressure exceeds rPressure during the alarm delay udiControlTime the limit value permanently rControlPressure, (Prerequisite: monitoring enabled xControl is active (= TRUE)), then the alarm output xAlarm is active (= TRUE).

Enable of monitoring xControl

Monitoring can generally be enabled (= TRUE) or blocked (= FALSE). If monitoring is not enabled, the output - fault message xAlarm is deactivated (= FALSE) and the time until the fault message is triggered tTimeToAlarm takes the value 0 s.

Output - pre-alarm xPreAlarm

The output - fault message xPreAlarm is activated (xPreAlarm = TRUE) if Condition 1 below is met. Condition 1: The input for the differential pressure sensor rPressure is greater than the maximum permissible differential pressure rControlPressure (= filter contamination).

Output - fault message xAlarm

The output - fault message xAlarm is activated (xAlarm = TRUE) if Condition 1 below is met. Condition 1: The input for the differential pressure sensor rPressure is at least during the alarm delay udiControlTime permanently greater than the maximum permissible differential pressure rControlPressure (= filter contamination). At the same time, monitoring is generally enabled (xControl = TRUE). The output - fault message xAlarm is deactivated in the following cases (xAlarm = FALSE: Case 1: Condition 1 is not met and the reset of the fault message xQuit is active (= TRUE). Case 2: Condition 1 is not met and monitoring enable xControl is not active (= FALSE).

Time until the fault message is triggered tTimeToAlarm

At output tTimeToAlarm different values are displayed depending on the operating situation: Situation 1: Output of the remaining time until the fault message is triggered (conditions: rPressure > rControlPressure, xControl = TRUE) Situation 2: If situation 1 does not apply, then the value 0.0 is continuously output.

CODESYS

InOut:

Scope
Name
Type
Initial

Input

rPressure

REAL

Input

xAlarmSensor

BOOL

Input

xQuit

BOOL

FALSE

Input Const

rMaxControlPressureVisu

REAL

500

Input Const

rMinControlPressureVisu

REAL

10

Input Const

udiControlTime

UDINT

300

Input Const

rControlPressure

REAL

200

Input Const

xControl

BOOL

TRUE

Output

xAlarm

BOOL

Output

xPreAlarm

BOOL

Output

tTimeToAlarm

TIME

Last updated