FilterMonitoringA
FilterMonitoringA (FB)
FilterMonitoringA (FB)FUNCTION_BLOCK FilterMonitoringA
Short description
Detection of a filter contamination and generation of a fault message Typical application: Monitoring the contamination of an air filter with a differential pressure sensor
Representation

Function description
General
This function block is used to detect filter contamination by evaluating the input from the differential pressure sensor rPressure. If the differential pressure exceeds rPressure during the reporting delay udiControlTime continuously the threshold value rControlPressure, (precondition: enabling of the monitoring xControl is active (= TRUE)) then the alarm output xAlarm becomes active (= TRUE).
Enable monitoring xControl
The monitoring can generally be enabled (= TRUE) or disabled (= FALSE). If monitoring is not enabled the output - fault message xAlarm is deactivated (= FALSE) and the time duration until the triggering of the fault message tTimeToAlarm takes the value 0s.
Output - pre-alarm xPreAlarm
The output - fault message xPreAlarm is activated (xPreAlarm = TRUE), if the condition 1 below is fulfilled. Condition 1: The input from the differential pressure sensor rPressure is greater than the maximum allowable differential pressure rControlPressure (= filter contamination).
Output - fault message xAlarm
The output - fault message xAlarm is activated (xAlarm = TRUE), if the condition 1 below is fulfilled. Condition 1: The input from the differential pressure sensor rPressure is at least during the reporting delay udiControlTime continuously greater than the maximum allowable differential pressure rControlPressure (= filter contamination). At the same time the monitoring is generally enabled (xControl = TRUE). The output - fault message xAlarm is deactivated in the following cases (xAlarm = FALSE : Case 1: Condition 1 is not fulfilled and the reset of the fault message xQuit is active (= TRUE). Case 2: Condition 1 is not fulfilled and the enabling of the monitoring xControl is not active (= FALSE).
Time duration until the fault message is triggered tTimeToAlarm
At the output tTimeToAlarm show different values depending on the operating situation: Situation 1: Display of the remaining time duration until the triggering of the fault message (conditions: rPressure > rControlPressure, xControl = TRUE) Situation 2: If situation 1 does not apply, the value 0.0 is output continuously.
CODESYS
InOut:
Input
rPressure
REAL
Input
xAlarmSensor
BOOL
Input
xQuit
BOOL
FALSE
Input Const
rMaxControlPressureVisu
REAL
500
Input Const
rMinControlPressureVisu
REAL
10
Input Const
udiControlTime
UDINT
300
Input Const
rControlPressure
REAL
200
Input Const
xControl
BOOL
TRUE
Output
xAlarm
BOOL
Output
xPreAlarm
BOOL
Output
tTimeToAlarm
TIME
Last updated

