FilterMonitoringA

FilterMonitoringA (FB)

FUNCTION_BLOCK FilterMonitoringA

Short description

Detection of a filter contamination and generation of a fault message Typical application: Monitoring the contamination of an air filter with a differential pressure sensor

Representation

Function description

General

This function block is used to detect filter contamination by evaluating the input from the differential pressure sensor rPressure. If the differential pressure exceeds rPressure during the reporting delay udiControlTime continuously the threshold value rControlPressure, (precondition: enabling of the monitoring xControl is active (= TRUE)) then the alarm output xAlarm becomes active (= TRUE).

Enable monitoring xControl

The monitoring can generally be enabled (= TRUE) or disabled (= FALSE). If monitoring is not enabled the output - fault message xAlarm is deactivated (= FALSE) and the time duration until the triggering of the fault message tTimeToAlarm takes the value 0s.

Output - pre-alarm xPreAlarm

The output - fault message xPreAlarm is activated (xPreAlarm = TRUE), if the condition 1 below is fulfilled. Condition 1: The input from the differential pressure sensor rPressure is greater than the maximum allowable differential pressure rControlPressure (= filter contamination).

Output - fault message xAlarm

The output - fault message xAlarm is activated (xAlarm = TRUE), if the condition 1 below is fulfilled. Condition 1: The input from the differential pressure sensor rPressure is at least during the reporting delay udiControlTime continuously greater than the maximum allowable differential pressure rControlPressure (= filter contamination). At the same time the monitoring is generally enabled (xControl = TRUE). The output - fault message xAlarm is deactivated in the following cases (xAlarm = FALSE : Case 1: Condition 1 is not fulfilled and the reset of the fault message xQuit is active (= TRUE). Case 2: Condition 1 is not fulfilled and the enabling of the monitoring xControl is not active (= FALSE).

Time duration until the fault message is triggered tTimeToAlarm

At the output tTimeToAlarm show different values depending on the operating situation: Situation 1: Display of the remaining time duration until the triggering of the fault message (conditions: rPressure > rControlPressure, xControl = TRUE) Situation 2: If situation 1 does not apply, the value 0.0 is output continuously.

CODESYS

InOut:

Scope
Name
Type
Initial

Input

rPressure

REAL

Input

xAlarmSensor

BOOL

Input

xQuit

BOOL

FALSE

Input Const

rMaxControlPressureVisu

REAL

500

Input Const

rMinControlPressureVisu

REAL

10

Input Const

udiControlTime

UDINT

300

Input Const

rControlPressure

REAL

200

Input Const

xControl

BOOL

TRUE

Output

xAlarm

BOOL

Output

xPreAlarm

BOOL

Output

tTimeToAlarm

TIME

Last updated