FilterMonitoringA
FilterMonitoringA (FB)
FUNCTION_BLOCK FilterMonitoringA
Short description
Detection of filter contamination and generation of a fault message Typical application: Monitoring the contamination of an air filter with a differential pressure sensor
Representation

Functional description
General
This function block is used to detect filter contamination by evaluating the input for the differential pressure sensor rPressure. If the differential pressure exceeds rPressure during the alarm delay udiControlTime the limit value permanently rControlPressure, (Prerequisite: monitoring enabled xControl is active (= TRUE)), then the alarm output xAlarm is active (= TRUE).
Enable of monitoring xControl
Monitoring can generally be enabled (= TRUE) or blocked (= FALSE). If monitoring is not enabled, the output - fault message xAlarm is deactivated (= FALSE) and the time until the fault message is triggered tTimeToAlarm takes the value 0 s.
Output - pre-alarm xPreAlarm
The output - fault message xPreAlarm is activated (xPreAlarm = TRUE) if Condition 1 below is met. Condition 1: The input for the differential pressure sensor rPressure is greater than the maximum permissible differential pressure rControlPressure (= filter contamination).
Output - fault message xAlarm
The output - fault message xAlarm is activated (xAlarm = TRUE) if Condition 1 below is met. Condition 1: The input for the differential pressure sensor rPressure is at least during the alarm delay udiControlTime permanently greater than the maximum permissible differential pressure rControlPressure (= filter contamination). At the same time, monitoring is generally enabled (xControl = TRUE). The output - fault message xAlarm is deactivated in the following cases (xAlarm = FALSE: Case 1: Condition 1 is not met and the reset of the fault message xQuit is active (= TRUE). Case 2: Condition 1 is not met and monitoring enable xControl is not active (= FALSE).
Time until the fault message is triggered tTimeToAlarm
At output tTimeToAlarm different values are displayed depending on the operating situation: Situation 1: Output of the remaining time until the fault message is triggered (conditions: rPressure > rControlPressure, xControl = TRUE) Situation 2: If situation 1 does not apply, then the value 0.0 is continuously output.
CODESYS
InOut:
Input
rPressure
REAL
Input
xAlarmSensor
BOOL
Input
xQuit
BOOL
FALSE
Input Const
rMaxControlPressureVisu
REAL
500
Input Const
rMinControlPressureVisu
REAL
10
Input Const
udiControlTime
UDINT
300
Input Const
rControlPressure
REAL
200
Input Const
xControl
BOOL
TRUE
Output
xAlarm
BOOL
Output
xPreAlarm
BOOL
Output
tTimeToAlarm
TIME
Last updated

