FilterMonitoringB
FilterMonitoringB (FB)
FUNCTION_BLOCK FilterMonitoringB
Short description
Detection of filter contamination and generation of a fault message Typical application: Monitoring the contamination of an air filter with a differential pressure switch
Representation

Interfaces
Inputs
xIn
BOOL
Input - Differential pressure switch
xQuit
BOOL
FALSE
Reset - Fault message
Outputs
xAlarm
BOOL
Output - fault message
xPreAlarm
BOOL
Output - pre-alarm
tTimeToAlarm
TIME
Time duration until the fault message is triggered
Setpoints / parameters
udiControlTime
UDINT
1s … 3600s
300s
Waiting time
xControl
BOOL
TRUE
Enable monitoring
Function description
General
This function block is used to detect filter contamination by evaluating the input for the differential pressure switch xIn.
Enable monitoring xControl
The monitoring can generally be enabled (= TRUE) or disabled (= FALSE). If monitoring is not enabled the output - fault message xAlarm is deactivated (= FALSE) and the time duration until the triggering of the fault message tTimeToAlarm takes the value 0s.
Output - pre-alarm xPreAlarm
The output - fault message xPreAlarm is activated (xPreAlarm = TRUE), if the condition 1 below is met. Condition 1: The input for the differential pressure switch xIn is in the TRUE state (= filter contamination).
Output - fault message xAlarm
The output - fault message xAlarm is activated (xAlarm = TRUE), if the condition 1 below is met. Condition 1: The input for the differential pressure switch xIn is in the state FALSE for at least the waiting time udiControlTime permanently in the TRUE state (= filter contamination). At the same time, monitoring is generally enabled (xControl = TRUE). The output - fault message xAlarm is deactivated in the following cases (xAlarm = FALSE): Case 1: Condition 1 is not met and the reset of the fault message xQuit is active (= TRUE). Case 2: Condition 1 is not fulfilled and the enabling of the monitoring xControl is not active (= FALSE).
Time duration until the fault message is triggered tTimeToAlarm
At the output time duration until the fault message is triggered tTimeToAlarm different values are displayed depending on the operating situation. Situation 1: Output of the remaining time until the fault message is triggered (conditions: xIn = TRUE, xControl = TRUE) Situation 2: If situation 1 does not apply, the value 0.0 is output continuously.
CODESYS
InOut:
Input
xIn
BOOL
Input
xQuit
BOOL
FALSE
Input Const
udiControlTime
UDINT
300
Input Const
xControl
BOOL
TRUE
Output
xAlarm
BOOL
Output
xPreAlarm
BOOL
Output
tTimeToAlarm
TIME
Last updated

