For the complete documentation index, see llms.txt. This page is also available as Markdown.

FireDamperMot_OnOff

FireDamperMot_OnOff (FB)

FUNCTION_BLOCK FireDamperMot_OnOff

Short description

Control of a motorized fire damper with two position feedback signals Additional functions: functional test of the fire damper Typical application: control of a fire damper in an HVAC system

Representation

Functional description

General

This function block controls a binary motorized fire damper(xEn = TRUE = opening), monitors the runtimes during the opening and closing process and can perform a complete fire damper test. The function block can be operated either in normal mode or in test mode (= fire damper test). Test mode has a higher priority than normal mode and can be triggered by a rising edge at the input xTestEx and / or at the setpoint / parameter xRunTest be triggered.

Release opening / closing of the fire damper before manual override xAB

The release of opening / closing of the fire damper before manual override xAB remains unchanged from the request for opening / closing of the fire damper xEn if the fire damper test is not active.

Enable opening / closing of the fire damper after manual override xHB

The release of opening / closing of the fire damper after manual override xHB corresponds to the release of opening / closing of the fire damper before manual override xAB additionally extended by a manual override module

xAB

eManModeB

xHB

Notes

FALSE

eMANBIN.Auto

FALSE

Manual override module in automatic mode

TRUE

eMANBIN.Auto

TRUE

Manual override module in automatic mode

X

eMANBIN.ManOn

TRUE

Manual override module in manual mode On

X

eMANBIN.ManOff

FALSE

Manual override module in manual mode Off

Legend: X = any

Selection of operating mode wMode

The selection of the operating mode currently allows two valid variants:

  1. 'wMode' = 1: The function block behaves like the function block 'FireDamperMot'

    1. xHB = TRUE: Immediate alarm message if the fire damper is not open according to the feedback (fire case)

    2. Fire damper test: fixed sequence — closing + opening

  2. 'wMode' = 2: The function block can be used for applications in Switzerland where the fire dampers are opened / closed in parallel to the demand of the HVAC system.

    1. xHB = FALSE: Immediate alarm message if the fire damper is not closed according to the feedback after the runtime has elapsed

    2. xHB = TRUE: Immediate alarm message if the fire damper is not open according to the feedback after the runtime has elapsed (fire case)

    3. Fire damper test: xClosed = TRUE: fixed sequence — opening + closing

    4. Fire damper test: xOpen = TRUE: fixed sequence — closing + opening

Collective fault xAlarm

'wMode' = 1: The collective fault xAlarm is activated (= TRUE) if at least one of the following conditions is met:

1) The fault message for the opening feedback xAlarmOpen is active (= TRUE). 2) The fault message for the closing feedback xAlarmClosed is active (= TRUE). 3) The fire damper is not fully open (xOpen = FALSE). (Background: Any fire damper that is not fully open represents a faulty state). 4) The input *xAlarmIn* is active (= TRUE). In all other cases the collective fault xAlarm is not activated (= FALSE). 'wMode' = 2: The collective fault xAlarm is activated (= TRUE) if at least one of the following conditions described below is met: 1) The fault message for the opening feedback xAlarmOpen is active (= TRUE). 2) The fault message for the closing feedback xAlarmClosed is active (= TRUE). 3) xHB = TRUE: The fire damper is not fully open (xOpen = FALSE). (Background: Any fire damper that is not fully open represents a faulty state). 4) xHB = FALSE: The fire damper is not fully closed (xClosed = FALSE). (Background: Any fire damper that is not fully closed represents a faulty state). 5) The input xAlarmIn is active (= TRUE). In all other cases the collective fault xAlarm is not activated (= FALSE).

Enable / disable the fault message for the opening feedback xAlarmOpen

Monitoring the damper runtime during the opening process to an adjustable maximum value (tOpen) starts if, in normal mode, at least one of the following conditions is met:

1) A rising edge (FALSE > TRUE) is detected at the output xHB is detected (= normal case). 2) The request for opening is active (xEn = TRUE) and at the same time a rising edge (FALSE > TRUE) is detected at input xQuit. 3) The output xHB is active (= TRUE) and at the same time a falling edge (TRUE > FALSE) is detected at input xOpen. The fault message for the opening feedback xAlarmOpen is activated (= TRUE) if, after the maximum runtime tOpen has elapsed while the output is active (xHB = TRUE), at least one of the following conditions is met: 1) The feedback of the complete opening is not active (xOpen = FALSE) (= normal case). 2) The feedbacks xOpen and xClosed have the same state. The fault message for the opening feedback xAlarmOpen is deactivated (= FALSE) if a rising edge (FALSE > TRUE) is detected at input xQuit.

Enable / disable the fault message for the closing feedback xAlarmClosed

Monitoring the runtime of the damper during the closing process up to an adjustable maximum value (tclose) starts if, in normal mode, at least one of the following conditions is met:

1) A falling edge (TRUE > FALSE) is detected at the output xHB is detected (= normal case). 2) The request for closing is active (xEn = FALSE) and at the same time a rising edge (FALSE > TRUE) is detected at input xQuit. The fault message for the closing feedback xAlarmClosed is activated (= TRUE) if, after the maximum runtime tClose has elapsed while the output is not active (xHB = FALSE), at least one of the following conditions is met: 1) The feedback of the complete closing is not active (xClosed = FALSE) (= normal case). 2) The feedbacks xOpen and xClosed have the same state. The fault message for the closing feedback xAlarmClosed is deactivated (= FALSE) if a rising edge (FALSE > TRUE) is detected at input xQuit.

Release / blocking of the fault message for the released, but not open fire damper after the runtime has elapsed (FALSE = block, TRUE = release) xAlarmOn_Closed

The fault message is released (prerequisite: 'wMode' = 2) if, after any runtime monitoring has elapsed, the released fire damper ('xHB' = TRUE) is not fully open ('xOpen' = FALSE) (= fire case). The fault message is deactivated (= FALSE) if input xQuit a rising edge (FALSE > TRUE) is detected. It is also deactivated (= FALSE) in all other modes ('wMode' <> 2).

Release / blocking of the fault message for the blocked, but not closed fire damper after the runtime has elapsed (FALSE = block, TRUE = release) xAlarmOff_Opened

The fault message is released (prerequisite: 'wMode' = 2) if, after any runtime monitoring has elapsed, the blocked fire damper ('xHB' = FALSE) is not fully closed ('xClosed' = FALSE). The fault message is deactivated (= FALSE) if input xQuit a rising edge (FALSE > TRUE) is detected. It is also deactivated (= FALSE) in all other modes ('wMode' <> 2).

Duration of the last complete opening tLastOpen

The duration measurement begins whenever at least one of the following conditions is met:

1) A rising edge (FALSE > TRUE) is detected at the input xOpen detected. 2) A falling edge (TRUE > FALSE) is detected at the input xOpen. 3) A rising edge (FALSE > TRUE) is detected at the input xClosed. 4) A falling edge (TRUE > FALSE) is detected at the input xClosed. (standard case) 5) A rising edge (FALSE > TRUE) is detected at the output xHB. 6) A falling edge (TRUE > FALSE) is detected at the output xHB. At this output, the runtime is available after each rising edge at the feedback for full opening xOpen (FALSE > TRUE).

Duration of the last complete closing tLastClosed

The duration measurement begins whenever at least one of the following conditions is met:

1) A rising edge (FALSE > TRUE) is detected at the input xOpen is detected. 2) A falling edge (TRUE > FALSE) is detected at input xOpen. (normal case) 3) A rising edge (FALSE > TRUE) is detected at input xClosed. 4) A falling edge (TRUE > FALSE) is detected at input xClosed. 5) A rising edge (FALSE > TRUE) is detected at output xHB. 6) A falling edge (TRUE > FALSE) is detected at output xHB. After each rising edge at the feedback of the complete closing xClosed (FALSE > TRUE), this output provides the runtime.

Duration of the current opening / closing in tRunTime

At this output, the current runtime is available during each runtime measurement.

Testing the functions of the fire damper (test mode)

Test mode is always generally triggered if at least one of the following conditions is met:

1) A rising edge (FALSE > TRUE) is detected at the input xTestEx detected. 2) The active state (= TRUE) at the setpoint / parameter xRunTest is detected. The active state is reset to (= FALSE) immediately after detection. However, the actual test mode only takes place if the feedback of automatic operation eAOO (0 = automatic, >0 = manual operation) contains the value 0 and at the same time the operating mode of the manual override for the digital output xHB signals automatic operation (eMANBIN = eMANBIN.Auto). 'wMode' = 1: In test mode, the fire damper is closed and then opened, each with runtime monitoring. At the start of test mode, the outputs xAlarmOpen, xAlarmClosed, tTestOpen, tTestClosed and xTestOK are reset (= FALSE). Now the control command for closing is triggered and the runtime is monitored for exceeding the maximum value tClosed. If the correct feedback situation (xClosed = TRUE and xOpen = FALSE) is reached without exceeding the maximum value, the output xAlarmClosed is not activated (= FALSE). In all other situations, the output xAlarmClosed is activated (= TRUE). Now the control command for opening is triggered and the runtime is monitored for exceeding the maximum value tOpen. If the correct feedback situation (xOpen = TRUE and xClosed = FALSE) is reached without exceeding the maximum value, the output xAlarmOpen is not activated (= FALSE). In all other situations, the output xAlarmOpen is activated (= TRUE). The result indicator for the fire damper test xTestOK is activated (= test successful) if neither of the two outputs xAlarmOpen nor xAlarmClosed is active (= TRUE). The achieved values tLastOpen and tLastClosed are each applied to the outputs tTestOpen and tTestClosed and stored until the next fire damper test. Test mode ends automatically as soon as the fire damper test is completed. 'wMode' = 2: The sequence for test mode is determined at the time it is triggered: a) 'xClosed' = TRUE: The sequence 'opening - closing' is executed b) 'xOpen' = TRUE: The sequence 'closing - opening' is executed Sequence closing - opening: In test mode, the fire damper is closed and then opened, each with runtime monitoring. At the start of test mode, the outputs xAlarmOpen, xAlarmClosed, tTestOpen, tTestClosed and xTestOK are reset (= FALSE). Now the control command for closing is triggered and the runtime is monitored for exceeding the maximum value tClosed. If the correct feedback situation (xClosed = TRUE and xOpen = FALSE) is reached without exceeding the maximum value, the output xAlarmClosed is not activated (= FALSE). In all other situations, the output xAlarmClosed is activated (= TRUE). Now the control command for opening is triggered and the runtime is monitored for exceeding the maximum value tOpen. If the correct feedback situation (xOpen = TRUE and xClosed = FALSE) is reached without exceeding the maximum value, the output xAlarmOpen is not activated (= FALSE). In all other situations, the output xAlarmOpen is activated (= TRUE). The result indicator for the fire damper test xTestOK is activated (= test successful) if neither of the two outputs xAlarmOpen nor xAlarmClosed is active (= TRUE). The achieved values tLastOpen and tLastClosed are each applied to the outputs tTestOpen and tTestClosed and stored until the next fire damper test. Test mode ends automatically as soon as the fire damper test is completed. Sequence opening - closing: In test mode, the fire damper is opened and then closed, each with runtime monitoring. At the start of test mode, the outputs xAlarmOpen, xAlarmClosed, tTestOpen, tTestClosed and xTestOK are reset (= FALSE). Now the control command for opening is triggered and the runtime is monitored for exceeding the maximum value tOpen. If the correct feedback situation (xOpen = TRUE and xClosed = FALSE) is reached without exceeding the maximum value, the output xAlarmOpen is not activated (= FALSE). In all other situations, the output xAlarmOpen is activated (= TRUE). Now the control command for closing is triggered and the runtime is monitored for exceeding the maximum value tClosed. If the correct feedback situation (xClosed = TRUE and xOpen = FALSE) is reached without exceeding the maximum value, the output xAlarmClosed is not activated (= FALSE). In all other situations, the output xAlarmClosed is activated (= TRUE). The result indicator for the fire damper test xTestOK is activated (= test successful) if neither of the two outputs xAlarmOpen nor xAlarmClosed is active (= TRUE). The achieved values tLastOpen and tLastClosed are each applied to the outputs tTestOpen and tTestClosed and stored until the next fire damper test. Test mode ends automatically as soon as the fire damper test is completed.

Requirements

Prerequisite for using the FireDamperMot_OnOff function block

For correct operation, the use of the TimeRead2 function block is required.

CODESYS

InOut:

Scope
Name
Type
Initial

Input

xEn

BOOL

Input

xAlarmIn

BOOL

FALSE

Input

eAOO

eManBin

eManBin.Auto

Input

xOpen

BOOL

Input

xClosed

BOOL

Input

xQuit

BOOL

FALSE

Input

xTestEx

BOOL

FALSE

Input

wMode

WORD

2

Output

sLine1

STRING

Output

sLine2

STRING

Output

sText

STRING

Output

xHB

BOOL

Output

xAB

BOOL

Output

xAlarm

BOOL

Output

xAlarmOpen

BOOL

Output

xAlarmClosed

BOOL

Output

xAlarmOn_Closed

BOOL

Output

xAlarmOff_Opened

BOOL

Output

xTestOK

BOOL

Output

tLastOpen

TIME

Output

tLastClosed

TIME

Output

tTestOpen

TIME

Output

tTestClosed

TIME

Output

tRunTime

TIME

Output

xAuto

BOOL

Input Const

udiOpen

UDINT

150

Input Const

udiClose

UDINT

25

Input Const

eManModeB

eMANBIN

eMANBIN.Auto

Input Const

xRunTest

BOOL

FALSE

Input Const

sEditLine2

STRING

‘’

Input Const

sEditLine1

STRING

‘Room’

Last updated