BurnerT

BurnerT (FB)

FUNCTION_BLOCK BurnerT

Short description

Control of a heat generator (temperature setpoint via temperature signal) Typical application: heat generation

Representation

Function description

General

This function block is used to control a heat generator depending on the demand of the heat generator xEn and the supply setpoint temperature rSetPtTemp. The enable / disable of the heat generator is done via the output xHB (FALSE = lockout, TRUE = enable). The temperature signal is generated from the supply setpoint temperature rSetPtTemp by means of a linear characteristic curve defined by two points, if the heat generator is enabled ( xHB = TRUE). If the heat generator is locked out, the constant 0.0 is output. The following function blocks are essentially used:

TwoPoint

OperatingHours

ManBin

ManNum

Enable / disable of the heat generator xHB

The enabling of the heat generator ( xAB = TRUE, xHB = TRUE (eManModeB = eManBin.Auto)) occurs if the demand of the heat generator is active ( xEn = TRUE). The lockout of the heat generator ( xAB = FALSE, xHB = FALSE (eManModeB = eManBin.Auto)) occurs if the demand of the heat generator is not active ( xEn = FALSE).

Temperature signal for the heat generator rHA

The temperature signal for the heat generator is transmitted to the output rAA (and rHA, if eManModeN = eManNum.Auto) provided the heat generator is enabled ( xHB = TRUE). If the heat generator is locked out ( xHB = FALSE) the constant 0.0 is output. The temperature signal is generated from the supply setpoint temperature rSetPtTemp by means of a linear characteristic curve defined by two points and is absolutely limited to the range 0.0 - 100.0%. The input characteristic is defined by the setpoints / parameters rTwoPointX1 or rTwoPointX2 defined. The output characteristic is defined by the setpoints / parameters rTwoPointY1 or rTwoPointY2 defined. The line defined by the points P1 (X1 / Y1) and P2 (X2 / Y2) now allows the mapping of arbitrary supply setpoint temperatures rSetPtTemp to a temperature signal rAA. Example: Characteristic: X1 = 20.0, X2 = 90.0, Y1 = 20.0, Y2 = 100.0 &#xNAN;rSetPtTemp = 55.0 °C &#xNAN;rAA = 60.0 %

Manual override of the digital output xHB

The enable/disable of the heat generator ( xHB ) can be operated either in automatic mode ( eMANBIN.Auto ) or in one of the two manual modes ( eMANBIN.ManOn, eMANBIN.ManOff ).

xAB

eMANBIN

xHB

Notes

FALSE

eMANBIN.Auto

FALSE

Manual override module in automatic

TRUE

eMANBIN.Auto

TRUE

Manual override module in automatic

X

eMANBIN.ManOn

TRUE

Manual override module in manual operation On

X

eMANBIN.ManOff

FALSE

Manual override module in manual operation Off

Legend: X = don't care

Manual override of the analog output rHA

The temperature signal ( rHA ) can be operated either in automatic mode ( eMANNUM.Auto ) or in manual mode ( eMANNUM.Man ).

rAA

eMANNUM

rHA

Notes

Value

eMANNUM.Auto

Value

Manual override module in automatic

X

eMANNUM.Man

rManValue

Manual override module in manual operation

Legend: X = don't care

Aggregate fault xAlarm

The aggregate fault xAlarm is active ( = TRUE ) if the fault message of the heat generator xAlarmIn is active ( = TRUE ). In all other situations the aggregate fault xAlarm is not active ( = FALSE ).

Collective automatic mode message xAuto

The collective automatic mode message xAuto is set active ( = TRUE ) if the following conditions are met simultaneously:\

  • Input eAOO = HVACTYPES.eManBin.Auto

  • Input eAO = HVACTYPES.eManNum.Auto

  • Setpoint / parameter eManModeB = eMANBIN.Auto

  • Setpoint / parameter eManModeN = eMANNUM.Auto

Operating hours counter - heat generator

The operating hours counter ( udiOperatingHours, udiCountFb ) for the heat generator is active when the running feedback is active ( xFb = TRUE ).

Write access to the counters

Via the path ‘InstanceName._OperatingHours.udiOperatingHours’ or ‘InstanceName._OperatingHours.udiCountFb’ a write access to both counter values is possible.\

Prerequisite for the use of the function block BurnerT

The use of the TimeRead2 function block is required for correct operation.

Feedback of the heat generator output rU

The current actual Output of the heat generator can be connected to the input rU . This input is currently not used for control and regulation purposes.

Feedback of the manual value for the power signal from the manual override - hardware rPoti

The feedback of the manual value can be at the input rPoti . This input is currently not used for control and regulation purposes.

Inactive state ( xEn = FALSE )

xHB

xAB

rHA

rAA

dtLastFb

udiOperatingHours

udiCountFb

xAlarm

xAuto

Notes

FALSE ( eManModeB = eManBin.Auto )

FALSE

0.0 (eManModeN = eManNum.Auto)

0

old value

old value

old value

State of xAlarmIn

old value

xEn = FALSE

Legend: X = any\

CODESYS

InOut:

Scope
Name
Type
Initial

Input

xEn

BOOL

Input

rSetPtTemp

REAL

Input

xFb

BOOL

Input

rU

REAL

0

Input

xAlarmIn

BOOL

Input

eAOO

eManBin

eManBin.Auto

Input

eAO

eManNum

eManNum.Auto

Input

rPoti

REAL

Output

xHB

BOOL

Output

xAB

BOOL

Output

rHA

REAL

Output

rAA

REAL

Output

dtLastFb

DT

Output

udiOperatingHours

UDINT

Output

udiCountFb

UDINT

Output

xAlarm

BOOL

Output

xAuto

BOOL

Input Const

rTwoPointY2

REAL

100

Input Const

rTwoPointX2

REAL

90

Input Const

rTwoPointY1

REAL

20

Input Const

rTwoPointX1

REAL

20

Input Const

rManValue

REAL

0

Input Const

eManModeN

eMANNUM

eMANNUM.Auto

Input Const

eManModeB

eMANBIN

eMANBIN.Auto

Last updated