BELIMO_VRU_D3_BAC_FULL
BELIMO_VRU_D3_BAC_FULL (FB)
BELIMO_VRU_D3_BAC_FULL (FB)FUNCTION_BLOCK BELIMO_VRU_D3_BAC_FULL
Representation

InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Address of the device
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoint values ( on every rising edge )
Input
xUpdateInfo
BOOL
FALSE
Update of device information (on every rising edge)
Input
xResError
BOOL
FALSE
Reinitialization of the outputs ‘eErrorCodeCom’ and ‘stErrorCodeDev’ to the error-free state (on each rising edge)
Input
rSetpPerc
REAL
0.0
Setpoint in % (0.0 - 100.0 %) depending on application
Input
eOverrideCon
BELIMO_VRU_D3_BAC_OVERRIDE_CON
BELIMO_VRU_D3_BAC_OVERRIDE_CON.NO_OVERRIDE
Volume flow control: setpoint - volume flow in % (0.0 - 100.0 %) (0.0 % = Vmin, 100.0 % = Vmax) Forced override of the damper (0 = none)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rVminUnit
REAL
Minimum value - volume flow in the selected volume flow unit
Output
rVmaxUnit
REAL
Maximum value - volume flow in the selected volume flow unit
Output
rVnomUnit
REAL
Nominal volume flow in the selected volume flow unit
Output
rVnomM3H
REAL
Nominal volume flow in m3/h
Output
rDamperPosPerc
REAL
Absolute position of the damper in percent (0.0% = closed, 100.0% = open)
Output
rDamperPosDegree
REAL
Absolute position of the damper in degrees
Output
rVolFlowPerc
REAL
Actual value of the volume flow in percent of the nominal volume flow
Output
rVolFlowM3H
REAL
Actual value of the volume flow in m3/h
Output
rVolFlowUnit
REAL
Actual value of the volume flow in the selected volume flow unit
Output
rDiffPressPerc
REAL
Actual value of the differential pressure in percent (relative to the absolute differential pressure in Pa)
Output
rDiffPressPa
REAL
Actual value of the differential pressure in pascal
Output
rDiffPressUnit
REAL
Actual value of the differential pressure in the selected differential pressure unit
Output
rDiffPressNomUnit
REAL
Actual value of the nominal differential pressure in the selected differential pressure unit
Output
rDiffPressNomPa
REAL
Actual value of the nominal differential pressure in pascal
Output
rSetpPercFb
REAL
Feedback of the setpoint in % (0.0 - 100.0 %)
Output
eCommandFb
BELIMO_VRU_D3_BAC_COMMAND
Feedback of the triggering of test functions (0 = none)
Output
eOverrideConFb
BELIMO_VRU_D3_BAC_OVERRIDE_CON
Feedback of the forced override of the damper (0 = none)
Output
eActuatorType
BELIMO_VRU_D3_BAC_ACTUATOR_TYPE
Type of actuator
Output
eVolumeFlowUnitFb
BELIMO_VRU_D3_BAC_VOLUMEFLOW_UNIT
Feedback of the unit for absolute volume flow values (1 = m3/h)
Output
eControlMode
BELIMO_VRU_D3_BAC_CONTROL_MODE
Type of control / regulation (0 = Position_Control = position control, 1 = Flow_Control = volume flow control)
Output
eSetpSourceFb
BELIMO_VRU_D3_BAC_SETP_SOURCE
Feedback of the source for the setpoint (0 = Analog, 1 = bus)
Output
eBusTermin
BELIMO_VRU_D3_BAC_BUS_TERMINATION
State of the Modbus termination resistor ( 1 = active )
Output
eSensorTypeFb
BELIMO_VRU_D3_BAC_SENSOR_TYPE
Feedback of the type of the connected sensor (0 = none )
Output
eApplication
BELIMO_VRU_D3_BAC_APPLICATION
Active application
Output
ePressOpModeFb
BELIMO_VRU_D3_BAC_PRESS_OP_MODE
Feedback - operating mode for room pressure control (only for VRU-M1R-BAC)
Output
eRoomPressCasc
BELIMO_VRU_D3_BAC_ROOM_PRESS_CASCADE
Enable / disable of the room pressure cascade control
Output
sSerialNum
STRING
Device serial number
Output
wFirmwareVer
WORD
Firmware version of the device
Output
rSensor1Value
REAL
Current actual value of the sensor in mV
Output
xSensorOffsetInDevice
BOOL
Indicates whether the sensor calibration must be performed in the device ( TRUE = calibration required in device, FALSE = calibration required in FB )
Output
rSetpAnalog
REAL
Setpoint in XXX.X % (0.0 - 100.0 %) based on the sensor
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = Fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = Fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
stErrorCodeDev
STRING
String with the numbers of active device errors
Output
xBusy
BOOL
Communication indicator ( TRUE = Communication )
Input Const
rSensor1Offset
REAL
0.0
Constant measurement offset for the transmitted actual value of sensor 1
Input Const
eDiffPressUnit
BELIMO_VRU_D3_BAC_DIFF_PRESS_UNIT
BELIMO_VRU_D3_BAC_DIFF_PRESS_UNIT.PASCAL
Influence: Outputs: rSensor1Value (eSensor1Type = 1-2) Unit for the differential pressure values (0 = Pa)
Input Const
rSystemAltitude
REAL
450.0
Altitude of the site in meters above sea level
Input Const
ePressOpMode
BELIMO_VRU_D3_BAC_PRESS_OP_MODE
BELIMO_VRU_D3_BAC_PRESS_OP_MODE.POSITIVE_PRESSURE
Operating mode for room pressure control (only for VRU-M1R-BAC)
Input Const
eSensor1Type
BELIMO_VRU_D3_BAC_SENSOR_TYPE
BELIMO_VRU_D3_BAC_SENSOR_TYPE.NONE
Type of the connected sensor (0 = none)
Input Const
eSetpSource
BELIMO_VRU_D3_BAC_SETP_SOURCE
BELIMO_VRU_D3_BAC_SETP_SOURCE.BUS
Source for the setpoint (0 = Analog, 1 = Bus)
Input Const
eCommand
BELIMO_VRU_D3_BAC_COMMAND
BELIMO_VRU_D3_BAC_COMMAND.NO_COMMAND
Triggering of test functions (0 = none)
Input Const
eVolumeFlowUnit
BELIMO_VRU_D3_BAC_VOLUMEFLOW_UNIT
BELIMO_VRU_D3_BAC_VOLUMEFLOW_UNIT.M3_PER_H
Unit for the absolute volume flow values (1 = m3/h)
Input Const
xSetpVolumeFlowMinMax
BOOL
FALSE
Triggering of the transmission of the parameters ‘rSetpVolumeFlowMin’ and ‘rSetpVolumeFlowMax’ (on each rising edge)
Input Const
rSetpVolumeFlowMax
REAL
2000.0
Setpoint for the maximum volume flow in the selected volume flow unit (at rSetpVolFlowPerc = 100.0 %)
Input Const
rSetpVolumeFlowMin
REAL
500.0
Setpoint for the minimum volume flow in the selected volume flow unit (at rSetpVolFlowPerc = 0.0 %)
Input Const
tBusFailureTimeOut
TIME
TIME#10s0ms
Time duration for activation of the state ‘communication failure’ (t = 0s = disabled, for t >= 10s (at least 10 s) the parameter ‘rSetpVolFlowPerc’ must be transmitted cyclically with a time period < t)
Input Const
rBusFailurePos
REAL
100.0
Position of the damper in case of a bus failure (in %, 100% = open)
Input Const
tTimeUpdateInfo
TIME
TIME#0ms
Update interval for operations affected by the input 'xUpdateInfo'
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the operations influenced by the input ‘xUpdateSetp’
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the operations influenced by the input ‘xUpdateActual’
Last updated

