BELIMO_NV24A_MOD
BELIMO_NV24A_MOD (FB)
BELIMO_NV24A_MOD (FB)FUNCTION_BLOCK BELIMO_NV24A_MOD
InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Device address ( 1 .. 247 )
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on each rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints ( on each rising edge )
Input
xResError
BOOL
FALSE
Reinitialization of the outputs ‘eErrorCodeCom’ and ‘xErrorCodeDev’ to the error-free state (on every rising edge)
Input
rSetp
REAL
0.0
Setpoint - position in % (0.0 - 100.0%)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rRelPos
REAL
Relative position in XXX.X %
Output
rAbsPos
REAL
Absolute position in XXX degrees (rotation) or mm (linear movement)
Output
rSensor1Value
REAL
Current actual value of sensor 1
Output
xSensorOffsetInDevice
BOOL
Indicates whether sensor calibration must be performed in the device (TRUE = calibration required in device, FALSE = calibration in FB required)
Output
rSetpAnalog
REAL
Setpoint - position in % in XXX.X % (0.0 - 100.0%) from input 0 - 10V
Output
eOverrideConFb
BELIMO_OverrideControl
Current state - forced override of control signal - position (0 = None)
Output
eBusTermin
BELIMO_BusTermination
State of the Modbus termination resistor (1 = active)
Output
sSerialNum
STRING
Device serial number
Output
eAO
eManNum
eManNum.Auto
Indication - manual override on the device (actuator decoupled) (0 = Automatic)
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
stErrorCodeDev
STRING
String with the numbers of the active device errors
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
rSensor1Offset
REAL
0.0
Constant measurement offset for the transmitted actual value of sensor 1
Input Const
eSetpSource
BELIMO_SetpointSource
BELIMO_SetpointSource.Bus
Affects: outputs: rSensor1Value (eSensor1Type = 1-3 and 5-10) Source for the setpoint - position (1 = Modbus)
Input Const
eCommand
BELIMO_Command
BELIMO_Command.None
Triggering of test functions (0 = None)
Input Const
wTimeBusFail
WORD
0
Duration of the bus watchdog timeout (60 - 3600s, 0 = deactivation)
Input Const
eBusFailPos
BELIMO_BusFailPosition
BELIMO_BusFailPosition.None_LastPosition
Action on a bus watchdog timeout (0 = None / last setpoint)
Input Const
eSensor1Type
BELIMO_SensorType
BELIMO_SensorType.None
Selection of the type of sensor 1 (0 = None)
Input Const
rMax
REAL
100.0
Absolute maximum value - control signal - position in % (0.0 - 100.0%)
Input Const
rMin
REAL
0.0
Absolute minimum value - control signal - position in % (0.0 - 100.0%)
Input Const
eOverrideCon
BELIMO_OverrideControl
BELIMO_OverrideControl.None
Forced override of the control signal - position (0 = None)
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the processes affected by the input ‘xUpdateSetp’
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes affected by the input ‘xUpdateActual’
Last updated

