BELIMO_NM24A_MOD

BELIMO_NM24A_MOD (FB)

FUNCTION_BLOCK BELIMO_NM24A_MOD

Representation

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enable)

Input

byUnitId

BYTE

0

Device address (1 .. 247)

Input

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge )

Input

xUpdateSetp

BOOL

FALSE

Update of setpoints (on every rising edge )

Input

xResError

BOOL

FALSE

Reinitialization of the outputs eErrorCodeCom or xErrorCodeDev to the fault-free state (on every rising edge)

Input

rSetp

REAL

0.0

Setpoint - position in % (0.0 - 100.0 %)

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

rRelPos

REAL

Relative position in XXX.X %

Output

rAbsPos

REAL

Absolute position in XXX degrees (rotation) or mm (linear movement)

Output

rSensor1Value

REAL

Current actual value of sensor 1

Output

xSensorOffsetInDevice

BOOL

Indication of whether the sensors must be calibrated in the device (TRUE = calibration in the device required, FALSE = calibration in the FB required)

Output

rSetpAnalog

REAL

Setpoint - position in % in XXX.X % (0.0 - 100.0 %) from input 0 - 10V

Output

eOverrideConFb

BELIMO_OverrideControl

Current state - forced override of the actuating signal - position (0 = None)

Output

eBusTermin

BELIMO_BusTermination

State of the Modbus terminating resistor (1 = Active)

Output

sSerialNum

STRING

Serial number of the device

Output

eAO

eManNum

eManNum.Auto

Display - manual override on the device (actuator decoupled) (0 = Automatic)

Output

xAlarm

BOOL

FALSE

Collective fault (TRUE = fault)

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication (TRUE = fault)

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

Output

stErrorCodeDev

STRING

String with the numbers of the active device errors

Output

xBusy

BOOL

Communication indicator (TRUE = communication)

Input Const

rSensor1Offset

REAL

0.0

Constant measured value offset for the transmitted actual value of sensor 1

Input Const

eSetpSource

BELIMO_SetpointSource

BELIMO_SetpointSource.Bus

Influence: outputs: rSensor1Value (eSensor1Type = 1-3 and 5-10) source for the setpoint - position (1 = Modbus)

Input Const

eCommand

BELIMO_Command

BELIMO_Command.None

Triggering of test functions (0 = None)

Input Const

wTimeBusFail

WORD

0

Duration of the bus watchdog timeout (60 - 3600s, 0 = disabling)

Input Const

eBusFailPos

BELIMO_BusFailPosition

BELIMO_BusFailPosition.None_LastPosition

Action in the event of a bus watchdog timeout (0 = None / Last Setpoint)

Input Const

eSensor1Type

BELIMO_SensorType

BELIMO_SensorType.None

Selection of the type of sensor 1 (0 = None)

Input Const

rMax

REAL

100.0

Absolute maximum value - actuating signal - position in % (0.0 - 100.0 %)

Input Const

rMin

REAL

0.0

Absolute minimum value - actuating signal - position in % (0.0 - 100.0 %)

Input Const

eOverrideCon

BELIMO_OverrideControl

BELIMO_OverrideControl.None

Forced override of the actuating signal - position (0 = None)

Input Const

tTimeUpdateSetp

TIME

TIME#45s0ms

Update interval for the processes influenced by the input xUpdateSetp influenced

Input Const

tTimeUpdateActual

TIME

TIME#3s0ms

Update interval for the processes influenced by the input xUpdateActual influenced