BELIMO_EVXXX_RX_FW_4_2_0_MOD

BELIMO_EVXXX_RX_FW_4_2_0_MOD (FB)

FUNCTION_BLOCK BELIMO_EVXXX_RX_FW_4_2_0_MOD

Representation

Guidelines - Software creation

The following function codes (FC) are supported: 3, 4 (additionally: 2, 4, 16)

For write operations to 32-bit data points (2 consecutive Modbus registers), FC16 must be used. No further registers may then be written in this telegram. Format of 32-bit data points: Register+0 (LSW): H-byte L-byte Register+1 (MSW): H-byte L-byte

The FC 02 may only be used for register 105 (Malfunction and service information, start address = 1664). | | For addressing, the address specifications must be used, not the register addresses. | | For unused registers, the value 65535 (dec.) is read / written. | | The calibration of the temperature sensors must be carried out in the device; however, no adjustment is possible via Modbus. | | The Modbus addresses 1 - 247 can be set directly in the integrated web server. | | All writable register addresses > 100 are persistent and must not be written cyclically | | The firmware of the device can currently (06.09.2024) not be read from address 103. The value 0 is always read. | | | Notes on the input rRelSetp (Relative setpoint - position/flow rate/power in % (0.0 - 100.0 %)) | | | 1) The function 'Flow rate depending on the signal rRelSetp' is not linear !!! (See Belimo documentation) | 2) The specification of an absolute flow rate setpoint can therefore be made as follows: | | a) External PI controller (inverted, 0 - 100 percent): Actual value = rAbsVolFlowUnit, setpoint = desired absolute setpoint, connect actuating signal to input rRelSetp . | b) Assign constant 100.0 to input rRelSetp , write parameter rMaxAbsVolFlowUnit with the desired absolute setpoint | Attention: Parameter rMaxAbsVolFlowUnit must not be written cyclically !!! | | Measured values - adjustment: Class ??? |

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enable)

Input

byUnitId

BYTE

1

Device address (1 .. 247)

Input

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge )

Input

xUpdateSetp

BOOL

FALSE

Update of setpoints (on every rising edge )

Input

xUpdateConfig

BOOL

FALSE

Configuration update (on every rising edge) (write and read access)

Input

xUpdateInfo

BOOL

FALSE

Update of the information (on every rising edge)

Input

xResError

BOOL

FALSE

Reinitialization of the outputs eErrorCodeCom or xErrorCodeDev to the fault-free state (on every rising edge)

Input

rRelSetp

REAL

0.0

Relative setpoint - position/volume flow/power in % ( 0.0 - 100.0 %)

Input

eCommand

BELIMO_EVXXX_RX_FW_4_2_0_COMMAND

BELIMO_EVXXX_RX_FW_4_2_0_COMMAND.None

Command for service functions (0 = None)

Input

eOverrideCon

BELIMO_EVXXX_RX_FW_4_2_0_OVERRIDE_CONTROL

BELIMO_EVXXX_RX_FW_4_2_0_OVERRIDE_CONTROL.None

Forced override of the actuating signal - Position/flow rate/power (0 = None)

Input

rSetpDeltaTTempKel

REAL

0.0

Setpoint - temperature difference (Delta-T manager) in Kelvin (minimum value)

Input

rSetpDeltaTAbsFlowUnit

REAL

0.0

Setpoint - flow rate in the selected unit (Delta-T - Manager) (unit defined in address 147)

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

eSetpSourceFb

BELIMO_EVXXX_RX_FW_4_2_0_SETPOINT_SOURCE

Feedback - source for the setpoint - position/volume flow/power (1 = Modbus)

Output

eControlModeFb

BELIMO_EVXXX_RX_FW_4_2_0_CONTROL_MODE

Feedback - control mode (1 = flow rate)

Output

rRelSetpFb

REAL

Feedback - relative setpoint - position/volume flow/power in % (0.0 - 100.0 %)

Output

rRelSetpAnalog

REAL

Relative setpoint - position/flow rate/power in % ( 0.0 - 100.0 %) from input 0 - 10V (address 118 = 0 = analog)

Output

rRelPos

REAL

Relative position in XXX.X %

Output

rAbsPos

REAL

Absolute position in XXX degrees (rotation) or mm (linear movement)

Output

rRelVolFlow

REAL

Relative flow rate in % (0.0 - 150.0 %) (relative to 'Maximum volumetric flow Limit - address 106)

Output

rRelVolFlowLimitMin

REAL

Limit value - minimum percentage flow rate (reference: Vnom) (Control_Mode = Flow Control or Power Control)

Output

rRelVolFlowLimitMax

REAL

Limit value - maximum percentage flow rate (reference: Vnom) (Control_Mode = Flow Control or Power Control)

Output

rNomAbsVolFlowUnit

REAL

Nominal airflow rate in the selected unit (addresses 112 and 113) (definition of the unit in address 147)

Output

rSetpAbsVolFlowUnit

REAL

Setpoint for the absolute flow rate in the selected unit (unit defined in address 147)

Output

rAbsVolFlowUnit

REAL

Absolute flow rate in the selected unit (unit defined in address 147)

Output

eVolFlowUnitFb

BELIMO_EVXXX_RX_FW_4_2_0_VOLUME_FLOW_UNIT

Feedback - unit for the absolute flow rate ( unit defined in address 147)

Output

rTemp1Deg

REAL

Current temperature at the cable sensor in degrees Celsius

Output

rTemp2Deg

REAL

Current temperature at the sensor in the flow meter in degrees Celsius

Output

rDeltaTempKel

REAL

Current temperature difference in Kelvin

Output

rRelGlycolCon

REAL

Current glycol concentration in percent

Output

rRelPower

REAL

Current power in percent (0.0 - 300.0 %) ( reference value: 'Maximum Power Limit' - address 165)

Output

rRelMaxPowerLimitFb

REAL

Feedback - relative maximum power in percent (( reference value: Pnom)

Output

rNomAbsPowerUnit

REAL

Nominal power in the selected unit (addresses 163 and 164) (unit defined in address 148)

Output

rAbsMaxPowerLimitUnitFb

REAL

Feedback - absolute maximum power in the selected unit (reference value: Pnom) (unit defined in address 148)

Output

rAbsPowerCoolUnit

REAL

Current absolute cooling power in the selected unit ( unit defined in address 148)

Output

rAbsPowerHeatUnit

REAL

Current absolute heating power in the selected unit ( unit defined in address 148)

Output

ePowerUnitFb

BELIMO_EVXXX_RX_FW_4_2_0_POWER_UNIT

Feedback - unit of the powers (unit defined in address 148) (Configuration_0)

Output

eDeltaTManagerStatus

BELIMO_EVXXX_RX_FW_4_2_0_DELTA_T_MANAGER_STATUS

Status of the Delta-T manager (Configuration_0)

Output

rSetpDeltaTTempKelFb

REAL

Feedback - setpoint - temperature difference (Delta-T - Manager) in Kelvin (minimum value)

Output

rSetpDeltaTAbsFlowUnitFb

REAL

Feedback - setpoint - flow rate in the selected unit (Delta-T - Manager) (unit defined in address 147)

Output

rRelDeltaPres

REAL

Relative differential pressure - water in % (0.0 - 100.0 %) ( relative to 'Absolute differential water pressure setpoint in selected unit' - addresses 172 - 173)

Output

rNomDeltaPresUnit

REAL

Nominal differential pressure - water in the selected unit ( unit defined in address 151)

Output

rSetpDeltaPresAbsUnitFb

REAL

Feedback - setpoint - differential pressure - water in the selected unit (unit defined in address 151) (Configuration_0)

Output

rDeltaPresAbsUnit

REAL

Differential pressure - water in the selected unit ( unit defined in address 151)

Output

eDeltaPresUnitFb

BELIMO_EVXXX_RX_FW_4_2_0_DIFFERENTIAL_PRESSURE_UNIT

Feedback - unit of the differential pressure (unit defined in address 151) (Configuration_0)

Output

eDeltaPresState

BELIMO_EVXXX_RX_FW_4_2_0_DIFFERENTIAL_PRESSURE_STATE

Status of the differential pressure control

Output

dwTotalWaterVolume

DWORD

Total water quantity in the selected unit (unit defined in address 149)

Output

eVolumeUnitFb

BELIMO_EVXXX_RX_FW_4_2_0_VOLUME_UNIT

Feedback - unit of the total water quantity (unit defined in address 149) (Configuration_0)

Output

dwTotalCoolingEnergy

DWORD

Total cooling energy in the selected unit (unit defined in address 150)

Output

dwTotalHeatinggEnergy

DWORD

Total heating energy in the selected unit (unit defined in address 150)

Output

eEnergyUnitFb

BELIMO_EVXXX_RX_FW_4_2_0_ENERGY_UNIT

Feedback - unit of the total energy quantities ( unit defined in address 150) (Configuration_0)

Output

eOverrideConFb

BELIMO_EVXXX_RX_FW_4_2_0_OVERRIDE_CONTROL

Current state - forced override of the actuating signal - position/volume flow/power (0 = None)

Output

rSensor1ValueUnit

REAL

Current value of sensor 1 in the selected unit ( address 120: sensor type, address 121: passive sensor type)

Output

eSensor1TypeFb

BELIMO_EVXXX_RX_FW_4_2_0_SENSOR_1_TYPE

Feedback - sensor type (address 120: sensor type) ( Configuration_0)

Output

eSensor1TypePasFb

BELIMO_EVXXX_RX_FW_4_2_0_SENSOR_1_PASSIVE_TYPE

Feedback - sensor type - passive (address 121: passive sensor type) (Configuration_0)

Output

rSensor1TempDeg

REAL

Current temperature at sensor 1 in degrees Celsius

Output

eCommandFb

BELIMO_EVXXX_RX_FW_4_2_0_COMMAND

Current state - command for service functions (0 = None )

Output

eDeviceType

BELIMO_EVXXX_RX_FW_4_2_0_DEVICE_TYPE

Current state - device type (0 = device not connected)

Output

eBusTermin

BELIMO_EVXXX_RX_FW_4_2_0_BUS_TERMINATION

State of the Modbus termination resistor (Active = Enabled)

Output

sSerialNum

STRING

Serial number of the device

Output

wFirmwareVer

WORD

Firmware version of the device

Output

eAO

eManNum

eManNum.Auto

Display - manual override on the device (actuator decoupled) (0 = Automatic)

Output

xSensorOffsetInDevice

BOOL

Indication of whether the sensors must be calibrated in the device (TRUE = calibration in the device required, FALSE = calibration in the FB required)

Output

xAlarm

BOOL

FALSE

Collective fault (TRUE = fault)

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication (TRUE = fault)

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

Output

stErrorCodeDev_1

STRING

String 1 with the numbers of the active device errors ( error bits 0 - 15)

Output

stErrorCodeDev_2

STRING

String 2 with the numbers of the active device errors ( error bits 16 - 31)

Output

xBusy

BOOL

Communication indicator (TRUE = communication)

Input Const

eDeltaTManagerLimitation

BELIMO_EVXXX_RX_FW_4_2_0_DELTA_T_MANAGER_LIMITATION

BELIMO_EVXXX_RX_FW_4_2_0_DELTA_T_MANAGER_LIMITATION.Disabled

Limitation of the Delta-T manager

Input Const

rSetpDeltaPresAbsUnit

REAL

200.0

Setpoint - differential pressure - water in the selected unit (unit defined in address 151)

Input Const

rAbsMaxPowerLimitUnit

REAL

30.0

Absolute maximum power in the selected unit ( reference value: Pnom) (unit defined in address 148 )

Input Const

eDeltaPresUnit

BELIMO_EVXXX_RX_FW_4_2_0_DIFFERENTIAL_PRESSURE_UNIT

BELIMO_EVXXX_RX_FW_4_2_0_DIFFERENTIAL_PRESSURE_UNIT.mbar

Unit of the differential pressure (unit defined in address 151)

Input Const

eEnergyUnit

BELIMO_EVXXX_RX_FW_4_2_0_ENERGY_UNIT

BELIMO_EVXXX_RX_FW_4_2_0_ENERGY_UNIT.MWh

Unit of the total energy quantities (unit defined in address 150)

Input Const

eVolumeUnit

BELIMO_EVXXX_RX_FW_4_2_0_VOLUME_UNIT

BELIMO_EVXXX_RX_FW_4_2_0_VOLUME_UNIT.m3

Unit of the total water volume (definition of the unit in address 149)

Input Const

ePowerUnit

BELIMO_EVXXX_RX_FW_4_2_0_POWER_UNIT

BELIMO_EVXXX_RX_FW_4_2_0_POWER_UNIT.kW

Unit of the powers (unit defined in address 148)

Input Const

eVolFlowUnit

BELIMO_EVXXX_RX_FW_4_2_0_VOLUME_FLOW_UNIT

BELIMO_EVXXX_RX_FW_4_2_0_VOLUME_FLOW_UNIT.m3_per_hour

Unit for the absolute airflow rate (definition of the unit in address 147)

Input Const

rMaxAbsVolFlowUnit

REAL

40.0

Maximum value for the absolute airflow rate in the selected unit (0.25rNomAbsVolFlowUnit … 1.0rNomAbsVolFlowUnit ) (definition of the unit in address 147)

Input Const

rMinAbsVolFlowUnit

REAL

20.0

Minimum value for the absolute airflow rate in the selected unit (0 … rMaxAbsVolFlowUnit) (definition of the unit in address 147)

Input Const

eSensor_1_Passive_Type

BELIMO_EVXXX_RX_FW_4_2_0_SENSOR_1_PASSIVE_TYPE

BELIMO_EVXXX_RX_FW_4_2_0_SENSOR_1_PASSIVE_TYPE.None

Definition of the type of passive sensor 1 (0 = None)

Input Const

eSensor_1_Type

BELIMO_EVXXX_RX_FW_4_2_0_SENSOR_1_TYPE

BELIMO_EVXXX_RX_FW_4_2_0_SENSOR_1_TYPE.None

Definition of the type of sensor 1 (0 = None)

Input Const

eSetpSource

BELIMO_EVXXX_RX_FW_4_2_0_SETPOINT_SOURCE

BELIMO_EVXXX_RX_FW_4_2_0_SETPOINT_SOURCE.Bus

Source for the setpoint - position/volume flow/power (1 = Modbus)

Input Const

eControlMode

BELIMO_EVXXX_RX_FW_4_2_0_CONTROL_MODE

BELIMO_EVXXX_RX_FW_4_2_0_CONTROL_MODE.Flow_Control

Control mode (1 = airflow rate)

Input Const

tBusFailTimeout

TIME

TIME#2m0s0ms

Time period for evaluating a communication error

Input Const

eBusFailAction

BELIMO_EVXXX_RX_FW_4_2_0_BUS_FAIL_ACTION

BELIMO_EVXXX_RX_FW_4_2_0_BUS_FAIL_ACTION.None

Action when a communication error occurs (0 = none)

Input Const

tTimeUpdateInfo

TIME

TIME#0ms

Update interval for the processes influenced by the input xUpdateInfo influenced

Input Const

tTimeUpdateConfig

TIME

TIME#0ms

Update interval for the processes influenced by the input xUpdateConfig influenced

Input Const

tTimeUpdateSetp

TIME

TIME#45s0ms

Update interval for the processes influenced by the input xUpdateSetp influenced

Input Const

tTimeUpdateActual

TIME

TIME#3s0ms

Update interval for the processes influenced by the input xUpdateActual influenced

Last updated