BELIMO_EVXXX_RX_FW_4_0_AND_4_1_MOD

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_MOD (FB)

FUNCTION_BLOCK BELIMO_EVXXX_RX_FW_4_0_AND_4_1_MOD

Guidelines - Software creation

The following Function Codes (FC) are supported: 3, 4 (additionally: 2, 4, 16) For write operations on 32-bit data points (2 consecutive Modbus registers) FC16 must be used. No other registers may be written in that telegram. Format of 32-bit data points: Register+0 (LSW): H-Byte L-Byte Register+1 (MSW): H-Byte L-Byte\

FC 02 may only be used for register 105 (Malfunction and service information, start address = 1664). | | For addressing use the address values, not the register addresses. | | For unused registers the value 65535 (dec.) is read/written. | | Calibration of the temperature sensors must be done in the device; however, no adjustment is possible via Modbus. | | Modbus addresses 1 - 247 can be set directly in the integrated web server. | | All writable register addresses > 100 are persistent and must not be written cyclically | | The device firmware cannot currently (06.09.2024) be read from address 103. The value 0 is always read. | | Measured values - calibration: Class ??? | |

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable of communication ( TRUE = enabled )

Input

byUnitId

BYTE

1

Device address ( 1 .. 247 )

Input

xUpdateActual

BOOL

FALSE

Update of actual values ( on each rising edge )

Input

xUpdateSetp

BOOL

FALSE

Update of setpoints ( on each rising edge )

Input

xUpdateConfig

BOOL

FALSE

Update of configuration (on every rising edge) (write and read access)

Input

xUpdateInfo

BOOL

FALSE

Update of information ( on each rising edge )

Input

xResError

BOOL

FALSE

Reinitialization of the outputs ‘eErrorCodeCom’ and ‘xErrorCodeDev’ to the error-free state (on every rising edge)

Input

rRelSetp

REAL

0.0

Relative setpoint - position/volume flow/power in % ( 0.0 - 100.0%)

Input

eCommand

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_COMMAND

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_COMMAND.None

Command for service functions (0 = None)

Input

eOverrideCon

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_OVERRIDE_CONTROL

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_OVERRIDE_CONTROL.None

Forced override of control signal - position/volume flow/power (0 = None)

Input

rSetpDeltaTTempKel

REAL

1.0

Setpoint - temperature difference (Delta-T manager) in Kelvin (minimum value)

Input

rSetpDeltaTAbsFlowUnit

REAL

0.0

Setpoint - volume flow in the selected unit (Delta-T manager) (unit selection at address 147)

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

eSetpSourceFb

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_SETPOINT_SOURCE

Feedback - source for the setpoint - position/volume flow/power (1 = Modbus)

Output

eControlModeFb

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_CONTROL_MODE

Feedback - operating mode of the control (1 = volume flow)

Output

rRelSetpFb

REAL

Feedback - relative setpoint - position/volume flow/power in % (0.0 - 100.0%)

Output

rRelSetpAnalog

REAL

Relative setpoint - position/volume flow/power in % ( 0.0 - 100.0%) from the 0 - 10V input (address 118 = 0 = analog)

Output

rRelPos

REAL

Relative position in XXX.X %

Output

rAbsPos

REAL

Absolute position in XXX degrees (rotation) or mm (linear movement)

Output

rRelVolFlow

REAL

Relative volume flow in % (0.0 - 150.0%) (relative to ‘Maximum volumetric flow Limit - address 106)

Output

rRelVolFlowLimitMin

REAL

Limit - minimum percentage volume flow (reference: Vnom) (Control_Mode = Flow Control or Power Control)

Output

rRelVolFlowLimitMax

REAL

Limit - maximum percentage volume flow (reference: Vnom) (Control_Mode = Flow Control or Power Control)

Output

rNomAbsVolFlowUnit

REAL

Nominal volume flow in the selected unit (addresses 112 and 113) (unit selection at address 147)

Output

rSetpAbsVolFlowUnit

REAL

Setpoint for the absolute volume flow in the selected unit (unit selection at address 147)

Output

rAbsVolFlowUnit

REAL

Absolute volume flow in the selected unit (unit selection at address 147)

Output

eVolFlowUnitFb

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_VOLUME_FLOW_UNIT

Feedback - unit for the absolute volume flow ( unit selection at address 147)

Output

rTemp1Deg

REAL

Current temperature at the cable sensor in degrees Celsius

Output

rTemp2Deg

REAL

Current temperature at the sensor in the flow meter in degrees Celsius

Output

rDeltaTempKel

REAL

Current temperature difference in Kelvin

Output

rRelGlycolCon

REAL

Current glycol concentration in percent

Output

rRelPower

REAL

Current power in percent (0.0 - 300.0%) ( Reference: ‘Maximum Power Limit’ - address 165)

Output

rRelMaxPowerLimitFb

REAL

Feedback - relative maximum power in percent ( Reference: Pnom)

Output

rNomAbsPowerUnit

REAL

Nominal power in the selected unit (addresses 163 and 164) (unit selection at address 148)

Output

rAbsMaxPowerLimitUnitFb

REAL

Feedback - absolute maximum power in the selected unit (reference: Pnom) (unit selection at address 148)

Output

rAbsPowerCoolUnit

REAL

Current absolute cooling power in the selected unit ( unit selection at address 148)

Output

rAbsPowerHeatUnit

REAL

Current absolute heating power in the selected unit ( unit selection at address 148)

Output

ePowerUnitFb

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_POWER_UNIT

Feedback - unit of powers (unit selection at address 148)

Output

eDeltaTManagerStatus

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_DELTA_T_MANAGER_STATUS

Status of the Delta-T manager

Output

rSetpDeltaTTempKelFb

REAL

Feedback - setpoint - temperature difference (Delta-T manager) in Kelvin (minimum value)

Output

rSetpDeltaTAbsFlowUnitFb

REAL

Feedback - setpoint - volume flow in the selected unit (Delta-T manager) (unit selection at address 147)

Output

dwTotalWaterVolume

DWORD

Total water volume in the selected unit (unit selection at address 149)

Output

eVolumeUnitFb

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_VOLUME_UNIT

Feedback - unit of total water volume (unit selection at address 149)

Output

dwTotalCoolingEnergy

DWORD

Total cooling energy in the selected unit (unit selection at address 150)

Output

dwTotalHeatinggEnergy

DWORD

Total heating energy in the selected unit (unit selection at address 150)

Output

eEnergyUnitFb

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_ENERGY_UNIT

Feedback - unit of total energy quantities ( unit selection at address 150)

Output

eOverrideConFb

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_OVERRIDE_CONTROL

Current state - forced override of control signal - position/volume flow/power (0 = None)

Output

rSensor1ValueUnit

REAL

Current value of sensor 1 in the selected unit ( address 120: sensor type, address 121: passive sensor type)

Output

eSensor1TypeFb

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_SENSOR_1_TYPE

Feedback - sensor type (address 120: sensor type)

Output

eSensor1TypePasFb

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_SENSOR_1_PASSIVE_TYPE

Feedback - sensor type - passive (address 121: passive sensor type)

Output

rSensor1TempDeg

REAL

Current temperature at sensor 1 in degrees Celsius

Output

eCommandFb

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_COMMAND

Current state - command for service functions (0 = None )

Output

eDeviceType

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_DEVICE_TYPE

Current state - type of the device (0 = Device not connected)

Output

eBusTermin

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_BUS_TERMINATION

State of the Modbus termination resistor (Active = Enabled)

Output

sSerialNum

STRING

Device serial number

Output

wFirmwareVer

WORD

Firmware version of the device

Output

eAO

eManNum

eManNum.Auto

Indication - manual override on the device (actuator decoupled) (0 = Automatic)

Output

xSensorOffsetInDevice

BOOL

Indicates whether sensor calibration must be performed in the device (TRUE = calibration required in device, FALSE = calibration in FB required)

Output

xAlarm

BOOL

FALSE

Collective fault ( TRUE = fault )

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication ( TRUE = fault )

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication ( 0 = no error )

Output

stErrorCodeDev

STRING

String with the numbers of the active device errors

Output

xBusy

BOOL

Communication indicator ( TRUE = communication )

Input Const

eDeltaTManagerLimitation

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_DELTA_T_MANAGER_LIMITATION

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_DELTA_T_MANAGER_LIMITATION.Disabled

Limitation of the Delta-T manager

Input Const

rAbsMaxPowerLimitUnit

REAL

30.0

Absolute maximum power in the selected unit ( Reference: Pnom) (unit selection at address 148 )

Input Const

eEnergyUnit

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_ENERGY_UNIT

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_ENERGY_UNIT.MWh

Unit of total energy quantities (unit selection at address 150)

Input Const

eVolumeUnit

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_VOLUME_UNIT

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_VOLUME_UNIT.m3

Unit of total water volume (unit selection at address 149)

Input Const

ePowerUnit

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_POWER_UNIT

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_POWER_UNIT.kW

Unit of powers (unit selection at address 148)

Input Const

eVolFlowUnit

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_VOLUME_FLOW_UNIT

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_VOLUME_FLOW_UNIT.m3_per_hour

Unit for the absolute volume flow (unit selection at address 147)

Input Const

rMaxAbsVolFlowUnit

REAL

40.0

Maximum value for the absolute volume flow in the selected unit (0.25rNomAbsVolFlowUnit … 1.0rNomAbsVolFlowUnit ) (unit selection at address 147)

Input Const

rMinAbsVolFlowUnit

REAL

20.0

Minimum value for the absolute volume flow in the selected unit (0 … rMaxAbsVolFlowUnit) (unit selection at address 147)

Input Const

eSensor_1_Passive_Type

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_SENSOR_1_PASSIVE_TYPE

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_SENSOR_1_PASSIVE_TYPE.Resistance_measurement

Definition of the type of passive sensor 1 (0 = None)

Input Const

eSensor_1_Type

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_SENSOR_1_TYPE

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_SENSOR_1_TYPE.None

Definition of the type of sensor 1 (0 = None)

Input Const

eSetpSource

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_SETPOINT_SOURCE

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_SETPOINT_SOURCE.Bus

Source for the setpoint - position/volume flow/power (1 = Modbus)

Input Const

eControlMode

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_CONTROL_MODE

BELIMO_EVXXX_RX_FW_4_0_AND_4_1_CONTROL_MODE.Flow_Control

Operating mode of the control (1 = volume flow)

Input Const

tBusFailTimeout

TIME

TIME#2m0s0ms

Time duration for evaluating a communication failure

Input Const

rBusFailRelSetp

REAL

0.0

Relative setpoint - position/volume flow/power in % ( 0.0 - 100.0%) in the event of a communication failure

Input Const

tTimeUpdateInfo

TIME

TIME#0ms

Update interval for the processes affected by the input ‘xUpdateInfo’

Input Const

tTimeUpdateConfig

TIME

TIME#0ms

Update interval for the processes affected by the input ‘xUpdateConfig’

Input Const

tTimeUpdateSetp

TIME

TIME#45s0ms

Update interval for the processes affected by the input ‘xUpdateSetp’

Input Const

tTimeUpdateActual

TIME

TIME#3s0ms

Update interval for the processes affected by the input ‘xUpdateActual’

Last updated