BELIMO_C615QP_B_MOD
BELIMO_C615QP_B_MOD (FB)
BELIMO_C615QP_B_MOD (FB)FUNCTION_BLOCK BELIMO_C615QP_B_MOD
InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
1
Device address ( 1 .. 247 )
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on each rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints ( on each rising edge )
Input
xResError
BOOL
FALSE
Reinitialization of the outputs ‘eErrorCodeCom’ and ‘xErrorCodeDev’ to the error-free state (on every rising edge)
Input
rSetp
REAL
0.0
Setpoint - position/volumetric flow in % ( 0.0 - 100.0 % )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rSetpFb
REAL
Feedback of the setpoint - position/volumetric flow in % ( 0.0 - 100.0 % )
Output
rRelPos
REAL
Relative position in XXX.X %
Output
rRelVolFlow
REAL
Relative volumetric flow in % ( 0.0 - 100.0 % ) (relative to VMax1 or VMax2, depending on active sequence )
Output
rAbsVolFlow
REAL
Absolute volumetric flow in the selected unit
Output
rSetpAbsVolFlow
REAL
Setpoint for the absolute volumetric flow in the selected unit
Output
rNomAbsVolFlow
REAL
Nominal volumetric flow in the selected unit
Output
eUnitSelecFlowFb
BELIMO_UnitSelectionFlow
Display of the selected unit
Output
eActiveSequence
BELIMO_Active_Sequence
Current state of the sequence ( 0 = Sequence 1, 1 = Sequence 2, 2 = Deadband )
Output
rSetpAnalog
REAL
Setpoint - position/volumetric flow in % in XXX.X % ( 0.0 - 100.0 % ) from input 0 - 10V
Output
eOverrideConFb
BELIMO_OverrideControl_TYPE_2
Current state - forced override of the control signal - position/volumetric flow ( 0 = None )
Output
sSerialNum
STRING
Device serial number
Output
eAO
eManNum
eManNum.Auto
Indication - manual override on the device (actuator decoupled) (0 = Automatic)
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
stErrorCodeDev
STRING
String with the numbers of the active device errors
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
eSetpSource
BELIMO_SetpointSource
BELIMO_SetpointSource.Bus
Source for the setpoint - position/volumetric flow ( 1 = Modbus )
Input Const
eUnitSelecFlow
BELIMO_UnitSelectionFlow
BELIMO_UnitSelectionFlow.l_h
Unit for the absolute volumetric flows ( 4 = l/h )
Input Const
rVMaxSeq1
REAL
100.0
Maximum value - position/volumetric flow in % ( 5.0 - 100.0 % of V-nominal ) for sequence 1
Input Const
rVMaxSeq2
REAL
100.0
Maximum value - position/volumetric flow in % ( 5.0 - 100.0 % of V-nominal ) for sequence 2
Input Const
eOverrideCon
BELIMO_OverrideControl_TYPE_2
BELIMO_OverrideControl_TYPE_2.None
Forced override of the control signal - position/volumetric flow ( 0 = None )
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the processes affected by the input ‘xUpdateSetp’
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes affected by the input ‘xUpdateActual’
Last updated

