BELIMO_C615QP_B_MOD
BELIMO_C615QP_B_MOD (FB)
BELIMO_C615QP_B_MOD (FB)FUNCTION_BLOCK BELIMO_C615QP_B_MOD
Representation

InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
Input
byUnitId
BYTE
1
Device address (1 .. 247)
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints (on every rising edge )
Input
xResError
BOOL
FALSE
Reinitialization of the outputs eErrorCodeCom or
xErrorCodeDev to the fault-free state (on every rising edge)
Input
rSetp
REAL
0.0
Setpoint - Position/Flow rate in % (0.0 - 100.0 %)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rSetpFb
REAL
Feedback of the setpoint - Position/Flow rate in % (0.0 - 100.0 %)
Output
rRelPos
REAL
Relative position in XXX.X %
Output
rRelVolFlow
REAL
Relative flow rate in % (0.0 - 100.0 %) (relative to VMax1 or VMax2, depending on the active sequence)
Output
rAbsVolFlow
REAL
Absolute flow rate in the selected unit
Output
rSetpAbsVolFlow
REAL
Setpoint for the absolute flow rate in the selected unit
Output
rNomAbsVolFlow
REAL
Nominal flow rate in the selected unit
Output
eUnitSelecFlowFb
BELIMO_UnitSelectionFlow
Display of the selected unit
Output
eActiveSequence
BELIMO_Active_Sequence
Current state of the sequence (0 = sequence 1, 1 = sequence 2, 2 = dead band)
Output
rSetpAnalog
REAL
Setpoint - Position/Flow rate in % in XXX.X % (0.0 - 100.0 %) from input 0 - 10V
Output
eOverrideConFb
BELIMO_OverrideControl_TYPE_2
Current state - forced override of the control signal - position/flow rate (0 = None)
Output
sSerialNum
STRING
Serial number of the device
Output
eAO
eManNum
eManNum.Auto
Display - manual override on the device (actuator decoupled) (0 = Automatic)
Output
xAlarm
BOOL
FALSE
Collective fault (TRUE = fault)
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication (TRUE = fault)
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
Output
stErrorCodeDev
STRING
String with the numbers of the active device errors
Output
xBusy
BOOL
Communication indicator (TRUE = communication)
Input Const
eSetpSource
BELIMO_SetpointSource
BELIMO_SetpointSource.Bus
Source for the setpoint - position/airflow rate (1 = Modbus )
Input Const
eUnitSelecFlow
BELIMO_UnitSelectionFlow
BELIMO_UnitSelectionFlow.l_h
Unit for the absolute flow rates (4 = l/h)
Input Const
rVMaxSeq1
REAL
100.0
Maximum value - Position/Flow rate in % (5.0 - 100.0 % of V-nominal) for sequence 1
Input Const
rVMaxSeq2
REAL
100.0
Maximum value - Position/Flow rate in % (5.0 - 100.0 % of V-nominal) for sequence 2
Input Const
eOverrideCon
BELIMO_OverrideControl_TYPE_2
BELIMO_OverrideControl_TYPE_2.None
Forced override of the control signal - position/airflow rate (0 = None)
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the processes influenced by the input
xUpdateSetp influenced
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes influenced by the input
xUpdateActual influenced
Last updated

