BELIMO_P_22RTX_1U00X_2_FULL

BELIMO_P_22RTX_1U00X_2_FULL (FB)

FUNCTION_BLOCK BELIMO_P_22RTX_1U00X_2_FULL

Representation

Short description

Control of the device series P-22RT..-1U00..-2 from Belimo Typical application: Room operating unit in a zone\

Guidelines - Software creation

Supported Modbus - Function Codes: 2, 3, 4, 6 and 16. For addressing use the address specifications, not the register addresses. Registers from 111 are persistent in the device and must not be written cyclically !!! Unused registers contain the value 65535 (unsigned) (FFFF - hex) or -1 (signed). Unused registers within the defined ranges may be read/written. In the constellation ‘eEcoBoostOnOffIconMode = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.OPERATION_MODE’ in ECO mode, on the first rising edge at the input ‘xBoostIcon’ the unit switches to On/Comfort mode. On the second rising edge the BOOST mode is activated. When operated at the room operating unit the switch from ECO to BOOST occurs immediately. Workaround: Write address 30 with FC06 !!! with the desired value, do not write address 22 at the same time. Measured values - Calibration: Class 4\

Interfaces

Inputs

Outputs

Name
Data type
Value range
Initial value
Function

eOperationMode

BELIMO_P_22RTX_1U00X_2_OPERATION_MODE

Display of the current operating mode on the room operating unit (register address 30)

xModeDev

BOOL

Operating mode of the zone control on the room operating unit (FALSE = night operation, TRUE = day operation)

xButtonPresence

BOOL

Actuation of the presence button (pulse with duration ‘tTimeButtonPulse’) (ROU and/or VISU)

rSetpTempAbs

REAL

Current absolute setpoint temperature depending on the parameter ‘eTemperatureUnit’ (e.g. +23.5 degrees Celsius) (register address 34) (unit depends on register address 120)

rOffset

REAL

Current difference between ‘rSetpTempAbs’ and ‘rAdjCenterSetpTemp’ (range: +/- ‘rAdjOffsetSetpTemp’) in day operation (unit depends on register address 120)

rSetpTempRel

REAL

Current relative setpoint temperature depending on the parameter ‘eOffsetUnit’ (e.g. -2.0 Kelvin) (range: +/- ‘rAdjOffsetSetpTemp’) (register address 36) (unit depends on register address 122)

rTemp

REAL

Room temperature (unit depends on register address 120)

rRelHumidity

REAL

Relative room humidity in percent

rCO2

REAL

CO2 concentration (ppm)

eCO2Status

BELIMO_P_22RTX_1U00X_2_CO2_STATUS

Current status of the CO2 measured-value monitoring

xSensorOffsetInDevice

BOOL

Indicates whether sensor calibration must be performed in the device (TRUE = calibration required in device, FALSE = calibration required in FB)

rDewPointTemp

REAL

Dew point temperature (unit depends on register address 120 in degrees Celsius or Fahrenheit)

eFanLevel

BELIMO_P_22RTX_1U00X_2_FAN_LEVEL

Current fan level depending on the parameter ‘eFanLevelConfig’ (register address 22)

xDI1

BOOL

State of digital input 1 depending on the parameter ‘eDI1OutpMode’ (RAW: FALSE = open, TRUE = closed with +24VDC, PULSE: pulse with duration ‘tTimeDIPulse’ at each rising edge on input DI1)

xEnLocalAdjFb

BOOL

Indication whether local operation is possible (TRUE = local operation possible) — feedback

eBusTermin

BELIMO_P_22RTX_1U00X_2_BUS_TERMINATION

State of the Modbus termination resistor (Active = Enabled)

sSerialNum

STRING

Device serial number

wFirmwareVer

WORD

Firmware version of the device

xAlarmCom

BOOL

Collective fault - communication ( TRUE = Fault )

eErrorCodeCom

ModbusErrorCode

Error code - communication ( 0 = no error )

eErrorCodeDev

SPLUSS_ERROR_CODE_TYPE_2

Error code - device (0 = no error)

xBusy

BOOL

Communication indicator ( TRUE = Communication )

Inputs and outputs

Name
Data type
Value range
Initial value
Function

ModbusClient

ModbusClientBase

Client of the device

General information about setpoints / parameters (addresses 110 - 149)

The following setpoints / parameters (addresses 110 - 149) are valid for the function block with the index ‘_FULL’. \

Setpoints / Parameters FULL

Name
Data type
Value range
Initial value
Address
Function

tTimeUpdateActual

TIME

T#3s

Update interval for processes influenced by the input ‘xUpdateActual’ (0 = no automatic update, > 0 cyclic update)

tTimeUpdateSetp

TIME

T#45s

Update interval for processes influenced by the input ‘xUpdateSetp’ (0 = no automatic update, > 0 cyclic update)

tTimeUpdateStates

TIME

T#500ms

Update interval for processes influenced by the input ‘xUpdateStates’ (0 = no automatic update, > 0 cyclic update)

tTimeUpdateInfo

TIME

T#0s

Update interval for processes influenced by the input ‘xUpdateInfo’ (0 = no automatic update, > 0 cyclic update)

eDI1OutpMode

BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE

BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE.RAW

Operating mode of the output ‘xDI1’ (RAW, PULSE)

tTimeDIPulse

TIME

T#1s

Duration of the pulse at output ‘xDI1’ if a rising edge is detected at the digital input (‘eDI1OutpMode’ = BELIMO_P_22RTX_1U00X_2_FULL_DIGITAL_INPUT_OUTP_MODE.PULSE)

eFanStageControlMode

BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE

BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE.AUTOMATIC_STAGES_CONTROL

31

Definition of the operating mode of the control of the fan stages

tTimeButtonPulse

TIME

T#1s

Duration of the pulse at output ‘xButton Presence’

Additional setpoints / parameters FULL

Name
Data type
Value range
Initial value
Address
Function

rTempOffset

REAL

+/- 15.0 K

0.0

110

Offset of the room temperature (for calibration of the temperature sensor) in K

rHumidityOffset

REAL

+/- 20.0 %

0.0

111

Offset of the room humidity (for calibration of the humidity sensor) in percent

rCO2Offset

REAL

+/- 500 ppm

0.0

112

Offset of the CO2 sensor (for calibration of the CO2 sensor) in ppm

rCO2_LED_ThresholdGreenYellow

REAL

600.0 - 1249.0 ppm, integer values only

1000.0

115

Threshold for changing the LED color from green to yellow

rCO2_LED_ThresholdYellowRed

REAL

1250.0 - 2000.0 ppm, integer values only

1500.0

116

Threshold for changing the LED color from yellow to red

xCO2_LED_Enable

BOOL

TRUE

117

Enable/disable of the CO2 LED (TRUE = enabled)

eTemperatureUnit

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE.DEGREES_CELSIUS

120

Definition of the unit for temperature (affects: ‘rTemp’ (address 1), ‘rDewPointTemp’ (address 5) and ‘rSetpTemp’ (address 34))

eTemperatureUnitDisplay

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE_DISPLAY

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE_DISPLAY.DEGREES_CELSIUS

121

Definition of the unit for the temperature display on the display (affects: Display)

eOffsetUnit

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE.DEGREES_CELSIUS

122

Definition of the unit for the relative set temperature (affects: ‘rSetpTempRel’ (address 36))

eColorScheme

BELIMO_P_22RTX_1U00X_2_COLOR_SCHEME

BELIMO_P_22RTX_1U00X_2_COLOR_SCHEME.WHITE_BACKGROUND

130

Definition of the display color scheme

eDsplIconsHeatCool

BELIMO_P_22RTX_1U00X_2_SYMBOL_VISIBILITY

BELIMO_P_22RTX_1U00X_2_SYMBOL_VISIBILITY.INVISIBLE

134

Display of the visibility of the icons for heating and cooling operation

eWarningIconFunct

BELIMO_P_22RTX_1U00X_2_WARNING_ICON_FUNCTION

BELIMO_P_22RTX_1U00X_2_WARNING_ICON_FUNCTION.DEVICE_ERROR_STATUS

135

Definition of the function of the 'Warning' icon

eWindowIconFunct

BELIMO_P_22RTX_1U00X_2_WINDOW_ICON_FUNCTION

BELIMO_P_22RTX_1U00X_2_WINDOW_ICON_FUNCTION.INPUT_xDsplIconWind

136

Definition of the function of the 'Window' icon

eEcoBoostOnOffIconMode

BELIMO_P_22RTX_1U00X_2_ICON_MODE

BELIMO_P_22RTX_1U00X_2_ICON_MODE.PRESENCE_BUTTON

139 - 141

Central definition of the functions of the icons ‘Eco’, ‘Boost’ and ‘OnOff’

tBoostModeDuration

TIME

T#900s

142

Duration of the 'Boost' operating mode

eSetpTempMode

BELIMO_P_22RTX_1U00X_2_SETP_TEMP_MODE

BELIMO_P_22RTX_1U00X_2_SETP_TEMP_MODE.ABSOLUTE_SETPOINT

145

Definition of the operating mode of the setpoint display (absolute / relative)

rAdjOffsetSetpTempAbs

REAL

-5.0 … +5.0 Kelvin

3.0

147

Definition of the adjustment range around the absolute base setpoint (center value) (+/- 5.0 K) (automatic internal conversion to other temperature units in the ROU). Affects the adjustment ranges of the absolute and the relative setpoint

eFanLevelConfig

BELIMO_P_22RTX_1U00X_2_FAN_LEVEL_CONFIG

BELIMO_P_22RTX_1U00X_2_FAN_LEVEL_CONFIG.SEVEN_STAGES

148

Definition of the number of fan stages

eFanControlMode

BELIMO_P_22RTX_1U00X_2_FAN_CONTROL_MODE

BELIMO_P_22RTX_1U00X_2_FAN_CONTROL_MODE.MANUAL_MODE_ONLY

1498

Definition of the operating mode of the fan control

Function description

General

This function block controls room operating units of the device series P-22RT..-1U00..-2 from Belimo via Modbus communication. The configuration (addresses 110 - 149) is done internally in the function block with the index ‘_FULL’.\

Operating modes - Room operating unit (address 30) — Outputs ‘eOperationMode’ and ‘xModeDev’

Four operating modes are distinguished: 0: Off/Protection (‘xModeDev’ = FALSE) 1: On/Comfort (‘xModeDev’ = TRUE) 2: Eco Mode (‘xModeDev’ = TRUE) 3: Boost Mode (‘xModeDev’ = TRUE) Operating modes 2 and 3 can only be selected additionally to operating mode 1. Operating mode 3 is active for a limited time and requires enabling of the highest fan stage for correct function. The operating modes are set automatically depending on the operating method (see below). \

Central definition of the functions of the icons / controls ‘OnOff’, ‘Eco’ and ‘Boost’ (operating methods)

A total of four operating methods are distinguished, which are defined via addresses 139 - 141: (FULL: parameter ‘eEcoBoostOnOffIconMode’) \

Operating method INVISIBLE

Visibility
Operability
Function

Eco: NO

Eco: NO

Icons not visible and not operable

Boost: NO

Boost: NO

Icons not visible and not operable

OnOff: NO

OnOff: NO

Icons not visible and not operable

Operating method DISPLAY_MODE

Visibility
Operability
Function

Eco: YES

Eco: NO

Display of the Eco and OnOff modes

Boost: NO

Boost: NO

Display of the Eco and OnOff modes

OnOff: YES

OnOff: NO

Display of the Eco and OnOff modes

Operating method OPERATION_MODE

Visibility
Operability
Function

Eco: YES

Eco: YES

Switching of the functions at the ROU as well as by rising edges at the icon inputs

Boost: YES

Boost: YES

Switching of the functions at the ROU as well as by rising edges at the icon inputs

OnOff: YES

OnOff: YES

Switching of the functions at the ROU as well as by rising edges at the icon inputs

Operating method PRESENCE_BUTTON

Visibility
Operability
Function

Eco: NO

Eco: NO

Occupancy time extension with external HVAC.Button1 function block

Boost: NO

Boost: NO

Occupancy time extension with external HVAC.Button1 function block

OnOff: YES

OnOff: YES

Occupancy time extension with external HVAC.Button1 function block

In DISPLAY mode the operating modes Eco Mode and On/Comfort are set by the inputs ‘xEcoIcon’ and ‘xMode’ (TRUE = on). If none of the inputs is active, Off/Protection is automatically selected. In OPERATION mode the operating modes ECO, Boost and OnOff are set by the corresponding inputs (rising edges) and by operation at the room operating unit. In PRESENCE-BUTTON mode the operating modes Off/Protection and On/Comfort are set by the input ‘xMode’ (rising edges: On/Comfort, falling edge: Off/Protection) and in parallel by operation at the room operating unit. On every change from night to day operation and vice versa triggered by the room operating unit, a pulse with duration ‘tTimeButtonPulse’ is generated at the output ‘xButtonPresence’. Additionally, on every rising edge at the input ‘xVisuPresence’ a pulse with duration ‘tTimeButtonPulse’ is generated at the output ‘xButtonPresence’. \

Restrictions in PRESENCE-BUTTON mode

  1. In the function block ‘HVAC.Button1’ the parameters ‘xEnClockButton’ and ‘xEnToggle’ must not be set to FALSE.\

  2. In the function block ‘HVAC.Button1’ the parameters ‘xEnClockButton’ and ‘xEnToggle’ must not be changed ONLINE.\

\

Day operation / Night operation (output ‘xModeDev’)

The output ‘xModeDev’ indicates the current state of day operation on the room operating unit (TRUE = day operation).\

Room setpoint temperatures

Room setpoint temperatures are defined in different ways depending on the parameter ‘eSetpTempMode’ (address 145): \

  1. Absolute setpoint (e.g. +23.5 degrees Celsius) (index ‘Abs’) (inputs ‘rSetpTempAbsNight’, ‘rSetpTempAbsBaseDay’) (output ‘rSetpTempAbs’)\

  2. Relative setpoint (e.g. +1.0 Kelvin) (index ‘Rel’) (inputs ‘rSetpTempRelNight’, ‘rSetpTempRelBaseDay’) (output ‘rSetpTempRel’)\

Changes to the assigned inputs are transferred immediately in the related state, otherwise at the next transition into that state. Example: A change at input ‘rSetpTempAbsNight’ is transferred and becomes effective immediately in night operation. Example: A change at input ‘rSetpTempBaseDay’ is not effective immediately in night operation, but only at the next transition to day operation. Changes to the parameter ‘rAdjOffsetSetpTempAbs’ (address 147) are transferred immediately in the appropriate state, otherwise delayed. (FULL). Changes in the content of address 147 affect the absolute and relative setpoint. The current values at inputs ‘rSetpTempAbsNight’ and ‘rSetpTempAbsBaseDay’ must be specified depending on the parameter ‘eTemperatureUnit’ (address 120). The current setpoint in the chosen unit is then available at the output ‘rSetpTempAbs’. The current values at inputs ‘rSetpTempRelNight’ and ‘rSetpTempRelBaseDay’ must be specified depending on the parameter ‘eOffsetUnit’ (address 122). The current setpoint in the chosen unit is then available at the output ‘rSetpTempRel’. Night operation - room setpoint When switching from day to night operation the state at the input ‘rSetpTempAbsNight’ is transferred to the room operating unit and displayed there (‘eSetpTempMode’ = absolute setpoint). When switching from day to night operation the state at the input ‘rSetpTempRelNight’ is transferred to the room operating unit and displayed there (‘eSetpTempMode’ = relative setpoint). Any change of the state at input ‘rSetpTempXXXNight’ is transmitted to the room operating unit during night operation. Day operation - room setpoint Case 1 - There is no valid room setpoint yet in day operation When switching from night to day operation the state at input ‘rSetpTempAbsBaseDay’ is transferred to the room operating unit and displayed there. At the room operating unit an adjustment within the symmetric range defined by address 147 is possible. The step size is fixed 0.5K and changes only in the sequence X.0 - X.5 - X.0, etc. Case 2 - There is already a valid room setpoint in day operation When switching from night to day operation the previous valid room setpoint is transferred to the room operating unit and displayed there. At the room operating unit an adjustment within the symmetric range defined by address 147 is possible. The step size is fixed 0.5K and changes only in the sequence X.0 - X.5 - X.0, etc.\

Output ‘xDI1’

At the output ‘xDI1’ the state at the input DI1 of the room operating unit is available in different ways (parameter ‘xDI1OutpMode’). Operating modes RAW The output immediately adopts the state at input DI1 (FALSE: contact open, TRUE: contact closed with +24VDC) PULSE Each rising edge at input DI1 triggers a pulse of duration ‘tTimeDIPulse’ (default: 1s) at the corresponding output xDI1. \

Preset / display of the fan stage

The preselection of the number of fan stages is done via the parameter ‘eFanLevelConfig’ (address 148). In Boost Mode the maximum fan stage (independent of the input ‘eSetpFanLevel’) is applied. The fan stage is selected and transmitted via the input ‘eSetpFanLevel’ within the permitted limits. The current fan stage is output via the output ‘eFanLevel’ within the permitted limits. The representation of the current fan stage and the adjustment options are additionally defined by the parameters ‘eFanStagesControlMode’ (address 31) ‘eFanControlMode’ (address 149), ‘eFanLevelConfig’ (address 148) and ‘xDsplFanStages’ (address 138).\

Assessment of the current CO2 level using a multicolored LED

The assessment of the current CO2 level is done using a multicolored LED (off / green / yellow / red) and the output ‘eCO2Status’. The threshold for the transition of the LED color from green to yellow is set by parameter ‘rCO2_LED_ThresholdwGreenYellow’ (address 115). The threshold for the transition of the LED color from yellow to red is set by parameter ‘rCO2_LED_ThresholdYellowRed’ (address 116). The assessment and the LED display can be defined by parameter ‘xCO2_LED_Enable’ (address 117) (TRUE = display).\

Display of symbols / measured values

The display of the desired symbols on the room operating unit display is triggered by the TRUE state of the assigned inputs. These inputs are marked with the index ‘Dspl’. Example: xDsplTemp = TRUE causes the current room temperature to be displayed on the display.\

Display of faults

Faults are indicated at the collective output ‘xAlarm’ ( = TRUE ). It includes communication faults (time delay: gc_Parameters.gc_tOnDelayxAlarmCom, default = 60s) and device faults (direct). Here the collective error message, the collective warning message and excessive CO2 level (LED = red) are output as device fault. At the output ‘eErrorCodeCom’ an explanatory text for the cause is available in case of a communication error. It always shows the cause of the last communication error.

Codesys

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable of communication ( TRUE = enabled )

Input

byUnitId

BYTE

0

Device address (1 .. 247) (via Belimo Assistant - App via NFC)

Input

xUpdateActual

BOOL

FALSE

Update of actual values ( on every rising edge )

Input

xUpdateSetp

BOOL

FALSE

Update of setpoint values ( on every rising edge )

Input

xUpdateConfig

BOOL

FALSE

Update of the configuration (on every rising edge)

Input

xUpdateStates

BOOL

FALSE

Updating of states (on every rising edge )

Input

xUpdateInfo

BOOL

FALSE

Update of information (on every rising edge)

Input

rSetpTempAbsNight

REAL

18.0

Absolute set temperature - night operation (unit depending on ‘eTemperatureUnit’)

Input

rSetpTempAbsBaseDay

REAL

22.0

Absolute base set temperature - day operation (unit depending on ‘eTemperatureUnit’)

Input

rSetpTempRelNight

REAL

0.0

Relative set temperature - night operation (unit depending on ‘eTemperatureUnit’)

Input

rSetpTempRelBaseDay

REAL

0.0

Relative base set temperature - day operation (unit depending on ‘eTemperatureUnit’)

Input

xMode

BOOL

FALSE

Display of the 'OnOff' icon (‘eEcoBoostOnOffIconMode’ = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.DISPLAY_MODE)

Input

xEcoIcon

BOOL

FALSE

Display of the 'Eco' icon (‘eEcoIconMode’ = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.DISPLAY_MODE)

Input

xBoostIcon

BOOL

FALSE

Operation of the 'Boost' icon (‘eBoostIconMode’ = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.OPERATION_MODE)

Input

eSetpFanLevel

BELIMO_P_22RTX_1U00X_2_FAN_LEVEL

BELIMO_P_22RTX_1U00X_2_FAN_LEVEL.STAGE_0

(each rising edge toggles the Boost mode) Setpoint - Current fan stage depending on the parameter ‘eFanLevelConfig’ Depending on the parameters ‘eFanStagesControlMode’ (register 31 - Setpoints_0) and ‘eFanControlMode’ (register 149 - Configuration_0) the following operation options are available: Register 31 = Automatic // Register 149 = Hybrid: If stage 0 is selected on the ROU, the display of the current stage is deactivated and an automatic symbol is shown. If a stage greater than 0 is selected on the ROU, the display of the current stage is activated and the automatic symbol is hidden. Stage selection is possible on the ROU and via register 22. In all other constellations applies: The display of the current stage is active, it can be changed on the ROU and via register 22, the last made change remains.

Input

xDsplTemp

BOOL

TRUE

Display of room temperature (TRUE = display)

Input

xDsplRelHumidity

BOOL

TRUE

Display of relative room humidity (TRUE = display)

Input

xDsplCO2

BOOL

TRUE

Display of CO2 concentration (TRUE = display)

Input

xDsplFanStages

BOOL

FALSE

Display of the fan controls (TRUE = display)

Input

eTempDsplMode

BELIMO_P_22RTX_1U00X_2_MODE_DISPLAY_TEMP

BELIMO_P_22RTX_1U00X_2_MODE_DISPLAY_TEMP.SETP_TEMPERATURE

Definition of the function of the central temperature display area

Input

eIconsHeatCool

BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL

BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL.NONE

Selection of heating or cooling operation

Input

xDsplIconWarn

BOOL

FALSE

Display of the 'Warning' symbol (TRUE = display)

Input

xDsplIconWind

BOOL

FALSE

Display of the 'Window' symbol (TRUE = display)

Input

xEnLocalAdj

BOOL

TRUE

Definition of whether local operation is possible (TRUE = enabled)

Input

xVisuPresence

BOOL

FALSE

Actuation of the presence button in the visualization (eEcoBoostOnOffIconMode = BELIMO_P_22RTX_1U00X_2_ICON_MODE.PRESENCE_BUTTON)

Input

xResError

BOOL

FALSE

Reinitialization of the output 'eErrorCodeCom' ( on each rising edge )

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

eOperationMode

BELIMO_P_22RTX_1U00X_2_OPERATION_MODE

Current operating mode 0 = OFF_PROTECTION: Night operation 1 = ON_COMFORT: Day operation 2 = ECO_MODE: Day operation — Eco mode 3 = BOOST_MODE: Day operation — Boost mode

Output

xModeDev

BOOL

Operating mode of the zone control from the device (FALSE = night operation, TRUE = day operation)

Output

xButtonPresence

BOOL

Actuation of the presence button (pulse with duration ‘tTimeButtonPulse’) (ROU and/or VISU)

Output

rSetpTempAbs

REAL

Current absolute setpoint temperature depending on the parameter ‘eTemperatureUnit’ (e.g. +23.5 degrees Celsius) ( register 34)

Output

rOffset

REAL

Current difference between ‘rSetpTempAbs’ and ‘rAdjCenterSetpTemp’ depending on the parameter ‘eTemperatureUnit’ (range: +/- ‘rAdjOffsetSetpTemp’) in day operation

Output

rSetpTempRel

REAL

Current relative setpoint temperature depending on the parameter ‘eOffsetUnit’ (e.g. -2.0 Kelvin) (range: +/- ‘rAdjOffsetSetpTemp’) (register 36)

Output

rTemp

REAL

Current room temperature depending on the parameter ‘eUnitTemperature’

Output

rRelHumidity

REAL

Relative room humidity in percent

Output

rCO2

REAL

Current CO2 concentration in ppm

Output

eCO2Status

BELIMO_P_22RTX_1U00X_2_CO2_STATUS

Current status of the CO2 measured-value monitoring

Output

xSensorOffsetInDevice

BOOL

Indicates whether the sensor calibration must be performed in the device ( TRUE = calibration required in device, FALSE = calibration required in FB )

Output

rDewPointTemp

REAL

Dew point temperature in degrees Celsius or Fahrenheit

Output

eFanLevel

BELIMO_P_22RTX_1U00X_2_FAN_LEVEL

Current fan stage depending on the parameter ‘eFanLevelConfig’

Output

xDI1

BOOL

State of digital input 1 depending on the parameter ‘eDI1OutpMode’:

Output

xEnLocalAdjFb

BOOL

Indication whether local operation is possible (TRUE = local operation possible) — feedback

Output

eBusTermin

BELIMO_P_22RTX_1U00X_2_BUS_TERMINATION

State of the Modbus termination resistor (Active = Enabled)

Output

sSerialNum

STRING

Device serial number

Output

wFirmwareVer

WORD

Firmware version of the device

Output

xAlarm

BOOL

FALSE

Collective fault ( TRUE = Fault )

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication ( TRUE = Fault )

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication ( 0 = no error )

Output

xBusy

BOOL

Communication indicator ( TRUE = Communication )

Input Const

xEcoIconPresenceButtonMode

BOOL

FALSE

Enable/disable of the display / operation of the ECO icon / button in the ‘PRESENCE_BUTTON’ operating method

Input Const

tTimeButtonPulse

TIME

TIME#1s0ms

Duration of the pulse at output ‘xButton Presence’

Input Const

eFanStageControlMode

BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE

BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE.AUTOMATIC_STAGES_CONTROL

Definition of the operating mode of the control of the fan stages

Input Const

eFanControlMode

BELIMO_P_22RTX_1U00X_2_FAN_CONTROL_MODE

BELIMO_P_22RTX_1U00X_2_FAN_CONTROL_MODE.MANUAL_MODE_ONLY

Definition of the operating mode of the fan control

Input Const

eFanLevelConfig

BELIMO_P_22RTX_1U00X_2_FAN_LEVEL_CONFIG

BELIMO_P_22RTX_1U00X_2_FAN_LEVEL_CONFIG.SEVEN_STAGES

Definition of the number of fan stages

Input Const

rAdjOffsetSetpTempAbs

REAL

3.0

Definition of the adjustment range around the absolute base setpoint (center value) (+/- 5.0 K) (automatic internal conversion to other temperature units in the ROU)

Input Const

eSetpTempMode

BELIMO_P_22RTX_1U00X_2_SETP_TEMP_MODE

BELIMO_P_22RTX_1U00X_2_SETP_TEMP_MODE.ABSOLUTE_SETPOINT

Affects the adjustment ranges of the absolute and the relative setpoint Definition of the operating mode of the setpoint display

Input Const

tBoostModeDuration

TIME

TIME#15m0s0ms

Duration of the 'Boost' operating mode

Input Const

eEcoBoostOnOffIconMode

BELIMO_P_22RTX_1U00X_2_ICON_MODE

BELIMO_P_22RTX_1U00X_2_ICON_MODE.PRESENCE_BUTTON

Central definition of the functions of the icons ‘Eco’, ‘Boost’ and ‘OnOff’ INVISIBLE (icons not visible and not operable) > Visibility Operability at ROU Eco: no no Boost: no no OnOff: no no DISPLAY_MODE (display of the Eco and OnOff modes) > Visibility Operability at ROU Eco: yes no Boost: no no OnOff: yes no OPERATION_MODE (switching of the functions at the ROU as well as by rising edges at the icon inputs) > Visibility Operability at ROU Eco: yes yes Boost: yes yes OnOff: yes yes PRESENCE_BUTTON (occupancy time extension with external HVAC.Button1 function block) > Visibility Operability at ROU Eco: no no Boost: no no OnOff: yes yes

Input Const

eWindowIconFunct

BELIMO_P_22RTX_1U00X_2_WINDOW_ICON_FUNCTION

BELIMO_P_22RTX_1U00X_2_WINDOW_ICON_FUNCTION.INPUT_xDsplIconWind

Definition of the function of the 'Window' icon

Input Const

eWarningIconFunct

BELIMO_P_22RTX_1U00X_2_WARNING_ICON_FUNCTION

BELIMO_P_22RTX_1U00X_2_WARNING_ICON_FUNCTION.DEVICE_ERROR_STATUS

Definition of the function of the 'Warning' icon

Input Const

eDsplIconsHeatCool

BELIMO_P_22RTX_1U00X_2_SYMBOL_VISIBILITY

BELIMO_P_22RTX_1U00X_2_SYMBOL_VISIBILITY.INVISIBLE

Display of the visibility of the icons for heating and cooling operation

Input Const

eColorScheme

BELIMO_P_22RTX_1U00X_2_COLOR_SCHEME

BELIMO_P_22RTX_1U00X_2_COLOR_SCHEME.WHITE_BACKGROUND

Definition of the display color scheme

Input Const

eOffsetUnit

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE.DEGREES_CELSIUS

Definition of the unit for the offset temperature ( affects: ‘rSetpTempRel’ (register 36))

Input Const

eTemperatureUnitDisplay

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE_DISPLAY

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE_DISPLAY.DEGREES_CELSIUS

Definition of the unit for the temperature display on the display (affects: Display)

Input Const

eTemperatureUnit

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE.DEGREES_CELSIUS

Definition of the unit for temperature (affects: ‘rTemp’ (register 1), ‘rDewPointTemp’ (register 5) and ‘rSetpTemp’ (register 34))

Input Const

xCO2_LED_Enable

BOOL

TRUE

Enable/disable of the CO2 LED (TRUE = enabled)

Input Const

rCO2_LED_ThresholdYellowRed

REAL

1500.0

Threshold for changing the LED color from yellow to red (1250.0 - 2000.0 ppm, integer values only)

Input Const

rCO2_LED_ThresholdGreenYellow

REAL

1000.0

Threshold for changing the LED color from green to yellow (600.0 - 1249.0 ppm, integer values only)

Input Const

rCO2Offset

REAL

0.0

Offset of the CO2 sensor (for calibration of the CO2 sensor) in ppm (+/- 500 ppm)

Input Const

rHumidityOffset

REAL

0.0

Offset of the room humidity (for calibration of the humidity sensor) in percent (+/- 20.0 %)

Input Const

rTempOffset

REAL

0.0

Offset of the room temperature (for calibration of the temperature sensor) in K (+/- 15.0 K)

Input Const

tTimeDIPulse

TIME

TIME#1s0ms

Duration of the pulse at output ‘xDI1’ if a rising edge is detected at the digital input ( ‘eDI1OutpMode’ = BELIMO_P_22RTX_1U00X_2_FULL_DIGITAL_INPUT_OUTP_MODE.PULSE )

Input Const

eDI1OutpMode

BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE

BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE.RAW

Operating mode of the output ‘xDI1’ (RAW, PULSE)

Input Const

tTimeUpdateInfo

TIME

TIME#0ms

Update interval for operations affected by the input 'xUpdateInfo'

Input Const

tTimeUpdateStates

TIME

TIME#500ms

Update interval for the operations influenced by the input ‘xUpdateStates’

Input Const

tTimeUpdateSetp

TIME

TIME#45s0ms

Update interval for the operations influenced by the input ‘xUpdateSetp’

Input Const

tTimeUpdateActual

TIME

TIME#3s0ms

Update interval for the operations influenced by the input ‘xUpdateActual’

Last updated