BELIMO_P_22RTX_1U00X_2_FULL
BELIMO_P_22RTX_1U00X_2_FULL (FB)
BELIMO_P_22RTX_1U00X_2_FULL (FB)FUNCTION_BLOCK BELIMO_P_22RTX_1U00X_2_FULL
Representation

Short description
Control of the P-22RT..-1U00..-2 device series from Belimo
Typical application: room operating device in one zone
Guidelines - software creation
Supported Modbus function codes: 2, 3, 4, 6 and 16. For addressing, use the address specifications, not the register addresses. Registers from 111 are persistent in the device and must not be written cyclically!!! Unused registers contain the value 65535 (unsigned) (FFFF - hex) or -1 (signed). Unused registers within the defined ranges may be read / written.
In the configuration eEcoBoostOnOffIconMode = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.OPERATION_MODE is switched in ECO mode with the first rising edge at input xBoostIcon to On/Comfort mode. With the second rising edge, BOOST mode is then activated. When operating on the room operating device, the switch from ECO to BOOST occurs immediately.
Remedy: write address 30 with FC06!!! with the desired value, do not write address 22 at the same time.
Measured values - calibration: Class 4
Interfaces
Inputs
Outputs
eOperationMode
BELIMO_P_22RTX_1U00X_2_OPERATION_MODE
Display of the current operating mode on the room operating device (register address 30)
xModeDev
BOOL
Operating mode of the zone control on the room operating device (FALSE = night mode, TRUE = day mode)
xButtonPresence
BOOL
Actuation of the presence button (pulse with duration tTimeButtonPulse) (RBG and/or VISU)
rSetpTempAbs
REAL
Current absolute setpoint temperature depending on the parameter eTemperatureUnit (e.g. +23.5 degrees Celsius) (register address 34) (unit depending on register address 120)
rOffset
REAL
Current difference between rSetpTempAbs and rAdjCenterSetpTemp (range: +/- rAdjOffsetSetpTemp) in day mode (unit depending on register address 120)
rSetpTempRel
REAL
Current relative setpoint temperature depending on the parameter eOffsetUnit (e.g. -2.0 Kelvin) (range: +/- rAdjOffsetSetpTemp) (register address 36) (unit depending on register address 122)
rTemp
REAL
Room temperature (unit depending on register address 120)
rRelHumidity
REAL
Relative room humidity in percent
rCO2
REAL
CO2 concentration (ppm)
eCO2Status
BELIMO_P_22RTX_1U00X_2_CO2_STATUS
Current status of CO2 actual-value monitoring
xSensorOffsetInDevice
BOOL
Display indicating whether the sensors must be calibrated in the device (TRUE = calibration required in the device, FALSE = calibration required in the FB)
rDewPointTemp
REAL
Dew point temperature (unit depending on register address 120 in degrees Celsius or Fahrenheit)
eFanLevel
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL
Current fan stage depending on the parameter eFanLevelConfig (register address 22)
xDI1
BOOL
State of digital input 1 depending on the parameter eDI1OutpMode (RAW: FALSE = open, TRUE = closed with +24VDC, PULSE: pulse with duration tTimeDIPulse at each rising edge at input DI1)
xEnLocalAdjFb
BOOL
Display indicating whether local operation is possible (TRUE = local operation possible) — feedback
eBusTermin
BELIMO_P_22RTX_1U00X_2_BUS_TERMINATION
Status of the Modbus termination resistor (Active = Enabled)
sSerialNum
STRING
Serial number of the device
wFirmwareVer
WORD
Firmware version of the device
xAlarmCom
BOOL
Collective fault - communication (TRUE = fault)
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
eErrorCodeDev
SPLUSS_ERROR_CODE_TYPE_2
Error code - device (0 = no error)
xBusy
BOOL
Communication display (TRUE = communication)
Inputs and outputs
ModbusClient
ModbusClientBase
Client of the device
General information on setpoints / parameters (addresses 110 - 149)
The following setpoints / parameters (addresses 110 - 149) are valid for the function block with index _FULL valid.
Setpoints / parameters FULL
tTimeUpdateActual
TIME
T#3s
Update interval for the processes influenced by the input xUpdateActual can be influenced (0 = no automatic update, > 0 cyclic update)
tTimeUpdateSetp
TIME
T#45s
Update interval for the processes influenced by the input xUpdateSetp can be influenced (0 = no automatic update, > 0 cyclic update)
tTimeUpdateStates
TIME
T#500ms
Update interval for the processes influenced by the input xUpdateStates can be influenced (0 = no automatic update, > 0 cyclic update)
tTimeUpdateInfo
TIME
T#0s
Update interval for the processes influenced by the input xUpdateInfo can be influenced (0 = no automatic update, > 0 cyclic update)
eDI1OutpMode
BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE
BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE.RAW
Operating mode of the output xDI1 (RAW, PULSE)
tTimeDIPulse
TIME
T#1s
Duration of the pulse at the output xDI1, if a rising edge is detected at the digital input (eDI1OutpMode = BELIMO_P_22RTX_1U00X_2_FULL_DIGITAL_INPUT_OUTP_MODE.PULSE)
eFanStageControlMode
BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE
BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE.AUTOMATIC_STAGES_CONTROL
31
Definition of the operating mode for fan stage control
tTimeButtonPulse
TIME
T#1s
Duration of the pulse at output ‘xButton Presence’
Additional setpoints / parameters FULL
rTempOffset
REAL
+/- 15.0 K
0.0
110
Offset of the room temperature (for calibration of the temperature sensor) in K
rHumidityOffset
REAL
+/- 20.0 %
0.0
111
Offset of the room humidity (for calibration of the humidity sensor) in percent
rCO2Offset
REAL
+/- 500 ppm
0.0
112
Offset of the CO2 sensor (for calibration of the CO2 sensor) in ppm
rCO2_LED_ThresholdGreenYellow
REAL
600.0 - 1249.0 ppm, integer values only
1000.0
115
Threshold for changing the LED color from green to yellow
rCO2_LED_ThresholdYellowRed
REAL
1250.0 - 2000.0 ppm, integer values only
1500.0
116
Threshold for changing the LED color from yellow to red
xCO2_LED_Enable
BOOL
TRUE
117
Enable / disable the CO2 LED (TRUE = enable)
eTemperatureUnit
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE.DEGREES_CELSIUS
120
Definition of the temperature unit (effect on: rTemp (address 1), rDewPointTemp (address 5) and rSetpTemp (address 34))
eTemperatureUnitDisplay
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE_DISPLAY
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE_DISPLAY.DEGREES_CELSIUS
121
Definition of the temperature unit for the display on the screen (effect on: display)
eOffsetUnit
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE.DEGREES_CELSIUS
122
Definition of the unit for the relative setpoint temperature (effect on: rSetpTempRel (address 36))
eColorScheme
BELIMO_P_22RTX_1U00X_2_COLOR_SCHEME
BELIMO_P_22RTX_1U00X_2_COLOR_SCHEME.WHITE_BACKGROUND
130
Definition of the display color scheme
eDsplIconsHeatCool
BELIMO_P_22RTX_1U00X_2_SYMBOL_VISIBILITY
BELIMO_P_22RTX_1U00X_2_SYMBOL_VISIBILITY.INVISIBLE
134
Display of the visibility of the icons for heating and cooling mode
eWarningIconFunct
BELIMO_P_22RTX_1U00X_2_WARNING_ICON_FUNCTION
BELIMO_P_22RTX_1U00X_2_WARNING_ICON_FUNCTION.DEVICE_ERROR_STATUS
135
Definition of the icon function Warning
eWindowIconFunct
BELIMO_P_22RTX_1U00X_2_WINDOW_ICON_FUNCTION
BELIMO_P_22RTX_1U00X_2_WINDOW_ICON_FUNCTION.INPUT_xDsplIconWind
136
Definition of the icon function Window
eEcoBoostOnOffIconMode
BELIMO_P_22RTX_1U00X_2_ICON_MODE
BELIMO_P_22RTX_1U00X_2_ICON_MODE.PRESENCE_BUTTON
139 - 141
Central definition of the icon functions Eco, Boost and OnOff
tBoostModeDuration
TIME
T#900s
142
Duration of the operating mode Boost
eSetpTempMode
BELIMO_P_22RTX_1U00X_2_SETP_TEMP_MODE
BELIMO_P_22RTX_1U00X_2_SETP_TEMP_MODE.ABSOLUTE_SETPOINT
145
Definition of the operating mode of the setpoint display (absolute / relative)
rAdjOffsetSetpTempAbs
REAL
-5.0 … +5.0 Kelvin
3.0
147
Definition of the adjustment range around the absolute base setpoint temperature (center value) (+/- 5.0 K) (automatic, internal conversion to other temperature units in the RBG). Influences the adjustment ranges of the absolute and relative setpoint temperatures
eFanLevelConfig
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL_CONFIG
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL_CONFIG.SEVEN_STAGES
148
Definition of the number of fan stages
eFanControlMode
BELIMO_P_22RTX_1U00X_2_FAN_CONTROL_MODE
BELIMO_P_22RTX_1U00X_2_FAN_CONTROL_MODE.MANUAL_MODE_ONLY
1498
Definition of the operating mode for fan control
Functional description
General
This function block controls room operating devices of the P-22RT..-1U00..-2 device series from Belimo via Modbus communication. Configuration (addresses 110 - 149) is carried out in the function block with index _FULL internally.
Operating modes - room operating device (address 30) — outputs eOperationMode and xModeDev
eOperationMode and xModeDevFour operating modes are distinguished:
0: Off/Protection (xModeDev = FALSE) 1: On/Comfort (xModeDev = TRUE) 2: Eco Mode (xModeDev = TRUE) 3: Boost Mode (xModeDev = TRUE)
Operating modes 2 and 3 can only be selected in addition to operating mode 1. Operating mode 3 is active for a limited time and requires approval of the highest fan stage for correct operation. The operating modes are set automatically depending on the operating mode (see below).
Central definition of the functions of the icons / controls OnOff, Eco and Boost (operating modes)
OnOff, Eco and Boost (operating modes)A total of four operating modes are distinguished, which are defined via addresses 139 - 141: (FULL: parameter eEcoBoostOnOffIconMode)
Operating mode INVISIBLE
Eco: NO
Eco: NO
Icons not visible or operable
Boost: NO
Boost: NO
Icons not visible or operable
OnOff: NO
OnOff: NO
Icons not visible or operable
Operating mode DISPLAY_MODE
Eco: YES
Eco: NO
Display of Eco and OnOff mode
Boost: NO
Boost: NO
Display of Eco and OnOff mode
OnOff: YES
OnOff: NO
Display of Eco and OnOff mode
Operating mode OPERATION_MODE
Eco: YES
Eco: YES
Switching the functions on the RBG as well as via rising edges at the icon inputs
Boost: YES
Boost: YES
Switching the functions on the RBG as well as via rising edges at the icon inputs
OnOff: YES
OnOff: YES
Switching the functions on the RBG as well as via rising edges at the icon inputs
Operating mode PRESENCE_BUTTON
Eco: NO
Eco: NO
Extension of usage time with external HVAC.Button1 - FB
Boost: NO
Boost: NO
Extension of usage time with external HVAC.Button1 - FB
OnOff: YES
OnOff: YES
Extension of usage time with external HVAC.Button1 - FB
In DISPLAY mode, the operating modes Eco Mode and On/Comfort are defined by the inputs xEcoIcon and xMode (TRUE = On). If none of the inputs is active, the Off/Protection operating mode is selected automatically.
In OPERATION mode, the ECO, Boost and OnOff operating modes are defined by the associated inputs (rising edges) and by operation on the room operating device.
In PRESENCE-BUTTON mode, the operating modes Off/Protection and On/Comfort are defined by the input xMode (rising edges: On / Comfort, falling edge: Off/Protection) and in parallel by operation on the room operating device. With every change from night mode to day mode and vice versa triggered by the room operating device, a pulse of duration xButtonPresence is generated at the output tTimeButtonPulse Additionally, with every rising edge at input xVisuPresence a pulse of duration xButtonPresence is generated at the output tTimeButtonPulse is generated at the output.
Restrictions in PRESENCE-BUTTON mode
In the function block
HVAC.Button1the parametersxEnClockButtonandxEnTogglemust not be set to FALSE.In the function block
HVAC.Button1the parametersxEnClockButtonandxEnTogglemust not be changed ONLINE.
Day mode / night mode (output xModeDev)
xModeDev)At the output xModeDev the current state of day mode on the room operating device is displayed (TRUE = day mode).
Room setpoint temperatures
The room setpoint temperatures are defined in different ways depending on the parameter eSetpTempMode (address 145):
Absolute setpoint (e.g. +23.5 degrees Celsius) (index
Abs) (inputsrSetpTempAbsNight,rSetpTempAbsBaseDay) (outputrSetpTempAbs)Relative setpoint (e.g. +1.0 Kelvin) (index
Rel) (inputsrSetpTempRelNight,rSetpTempRelBaseDay) (outputrSetpTempRel)
Changes to the assigned inputs are transferred immediately in the corresponding state, otherwise at the next transition into this state. Example: A change at input rSetpTempAbsNight is transferred and becomes effective immediately in night mode. Example: A change at input rSetpTempBaseDay is not effective immediately in night mode, but only at the next transition to day mode.
Changes to parameter rAdjOffsetSetpTempAbs (address 147) are transferred immediately in the appropriate state, otherwise with delay. (FULL). Changes to the content of address 147 affect the absolute and relative setpoint temperatures.
The current values at inputs rSetpTempAbsNight and rSetpTempAbsBaseDay must be specified depending on parameter eTemperatureUnit (address 120). At output output rSetpTempAbs the current setpoint value is then available in the selected unit. The current values at inputs rSetpTempRelNight and rSetpTempRelBaseDay must be specified depending on parameter eOffsetUnit (address 122). At output output rSetpTempRel the current setpoint value is then available in the selected unit.
Night mode - room setpoint temperature
When switching from day mode to night mode, the state at input rSetpTempAbsNight is transferred to the room operating device and displayed there (eSetpTempMode = absolute setpoint temperature). When switching from day mode to night mode, the state at input rSetpTempRelNight is transferred to the room operating device and displayed there (eSetpTempMode = relative setpoint temperature). Every change of the state at input rSetpTempXXXNight is transferred to the room operating device during night mode.
Day mode - room setpoint temperature
Case 1 - No valid room setpoint temperature is yet available in day mode
When switching from night mode to day mode, the state at input rSetpTempAbsBaseDay is transferred to the room operating device and displayed there. Adjustment within the symmetrical range defined by address 147 is possible on the room operating device. The step size is fixed at 0.5K and changes only in the sequence X.0 - X.5 - X.0, etc.
Case 2 - A valid room setpoint temperature is already available in day mode
When switching from night mode to day mode, the previous valid room setpoint temperature is transferred to the room operating device and displayed there. Adjustment within the symmetrical range defined by address 147 is possible on the room operating device. The step size is fixed at 0.5K and changes only in the sequence X.0 - X.5 - X.0, etc.
Output xDI1
xDI1At the output xDI1 the state at digital input DI1 of the room operating device is available in different ways (parameter xDI1OutpMode).
Operating modes
RAW
The output directly adopts the state at input DI1 (FALSE: contact open, TRUE: contact closed with +24VDC)
PULSE
Every rising edge at input DI1 triggers a pulse of duration tTimeDIPulse (default: 1s) at the corresponding output xDI1.
Specification / display of fan stage
The preselection of the number of fan stages is done via parameter eFanLevelConfig (address 148). In Boost Mode, the maximum fan stage is specified (independent of input eSetpFanLevel). The fan stage is selected and transferred via input eSetpFanLevel within the permitted limits. The current fan stage is output via output eFanLevel within the permitted limits. The display of the current fan stage and the adjustment options are additionally defined by the parameters eFanStagesControlMode (address 31) eFanControlMode (address 149), eFanLevelConfig (address 148) and xDsplFanStages (address 138).
Evaluation of the current CO2 level using a multicolor LED
The evaluation of the current CO2 level is carried out using a multicolor LED (off / green / yellow / red) and output eCO2Status is performed. The threshold for the transition of the LED color from green to yellow is defined by the parameter rCO2_LED_ThresholdwGreenYellow (address 115). The threshold for the transition of the LED color from yellow to red is defined by the parameter rCO2_LED_ThresholdYellowRed (address 116). The evaluation and the LED display can be defined by the parameter xCO2_LED_Enable (address 117) (TRUE = display).
Display of symbols / actual values
The display of the desired symbols on the room operating device display is triggered by the TRUE state of the assigned inputs. These inputs are marked with index Dspl . Example: xDsplTemp = TRUE causes the current room temperature to be displayed on the screen.
Display of faults
Faults are displayed at the aggregate output xAlarm (= TRUE). It includes communication faults (time delay: gc_Parameters.gc_tOnDelayxAlarmCom, default = 60s) and device faults (direct). The aggregate fault message, aggregate warning message and excessively high CO2 level (LED = red) are output here as a device fault. At output eErrorCodeCom an explanatory text for the cause is available in the event of a communication error. The cause of the last communication error is always displayed there.
Codesys
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
Input
byUnitId
BYTE
0
Device address (1 .. 247) (via Belimo Assistant app via NFC)
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints (on every rising edge )
Input
xUpdateConfig
BOOL
FALSE
Update of the configuration (at every rising edge)
Input
xUpdateStates
BOOL
FALSE
Update of the states (at every rising edge)
Input
xUpdateInfo
BOOL
FALSE
Update of the information (on every rising edge)
Input
rSetpTempAbsNight
REAL
18.0
Absolute set temperature - night mode (unit depending on eTemperatureUnit)
Input
rSetpTempAbsBaseDay
REAL
22.0
Absolute base set temperature - day mode (unit depending on eTemperatureUnit)
Input
rSetpTempRelNight
REAL
0.0
Relative set temperature - night mode (unit depending on eTemperatureUnit)
Input
rSetpTempRelBaseDay
REAL
0.0
Relative base set temperature - day mode (unit depending on eTemperatureUnit)
Input
xMode
BOOL
FALSE
Display of the icon OnOff (eEcoBoostOnOffIconMode =
BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.DISPLAY_MODE)
Input
xEcoIcon
BOOL
FALSE
Display of the icon Eco (eEcoIconMode =
BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.DISPLAY_MODE)
Input
xBoostIcon
BOOL
FALSE
Operation of the icon Boost (eBoostIconMode =
BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.OPERATION_MODE)
Input
eSetpFanLevel
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL.STAGE_0
(each rising edge switches the Boost mode)
Setpoint - Current fan stage depending on the parameter eFanLevelConfig
Depending on the parameters eFanStagesControlMode (Register 31 - Setpoints_0) and eFanControlMode (Register 149 - Configuration_0), the following operating options are available:
Register 31 = Automatic // Register 149 = Hybrid:
If stage 0 is selected on the RBG, the display of the current stage is deactivated and an automatic symbol is displayed.
If a stage greater than 0 is selected on the RBG, the display of the current stage is activated and the automatic symbol is hidden.
Stage selection is possible on the RBG and via register 22.
In all other configurations, the following applies:
The display of the current stage is active, it can be changed on the RBG and via register 22, the last change made remains in effect.
Input
xDsplTemp
BOOL
TRUE
Display of the room temperature (TRUE = display)
Input
xDsplRelHumidity
BOOL
TRUE
Display of the relative room humidity (TRUE = display)
Input
xDsplCO2
BOOL
TRUE
Display of the CO2 concentration (TRUE = display)
Input
xDsplFanStages
BOOL
FALSE
Display of the controls for the fan (TRUE = display)
Input
eTempDsplMode
BELIMO_P_22RTX_1U00X_2_MODE_DISPLAY_TEMP
BELIMO_P_22RTX_1U00X_2_MODE_DISPLAY_TEMP.SETP_TEMPERATURE
Definition of the function of the central temperature display area
Input
eIconsHeatCool
BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL
BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL.NONE
Selection of heating or cooling mode
Input
xDsplIconWarn
BOOL
FALSE
Display of the symbol Warning (TRUE = display)
Input
xDsplIconWind
BOOL
FALSE
Display of the symbol Window (TRUE = display)
Input
xEnLocalAdj
BOOL
TRUE
Definition of whether local operation is possible (TRUE = enable)
Input
xVisuPresence
BOOL
FALSE
Actuation of the presence button in the visualization action (eEcoBoostOnOffIconMode = BELIMO_P_22RTX_1U00X_2_ICON_MODE.PRESENCE_BUTTON)
Input
xResError
BOOL
FALSE
Reinitialization of the output eErrorCodeCom (at every
rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
eOperationMode
BELIMO_P_22RTX_1U00X_2_OPERATION_MODE
Current operating mode 0 = OFF_PROTECTION: night mode 1 = ON_COMFORT: day mode 2 = ECO_MODE: day mode — eco mode 3 = BOOST_MODE: day mode — boost mode
Output
xModeDev
BOOL
Operating mode of zone control from the device (FALSE = night mode, TRUE = day mode)
Output
xButtonPresence
BOOL
Actuation of the presence button (pulse with duration
tTimeButtonPulse) (RBG and/or VISU)
Output
rSetpTempAbs
REAL
Current absolute setpoint temperature depending on the
parameter eTemperatureUnit (e.g. +23.5 degrees Celsius) (
register 34)
Output
rOffset
REAL
Current difference between rSetpTempAbs and
rAdjCenterSetpTemp depending on the parameter
eTemperatureUnit (range: +/- rAdjOffsetSetpTemp) in
day mode
Output
rSetpTempRel
REAL
Current relative setpoint temperature depending on the
parameter eOffsetUnit (e.g. -2.0 Kelvin) (range: +/-
rAdjOffsetSetpTemp) (register 36)
Output
rTemp
REAL
Current room temperature depending on the parameter
eUnitTemperature
Output
rRelHumidity
REAL
Relative room humidity in percent
Output
rCO2
REAL
Current CO2 level in ppm
Output
eCO2Status
BELIMO_P_22RTX_1U00X_2_CO2_STATUS
Current status of CO2 actual-value monitoring
Output
xSensorOffsetInDevice
BOOL
Display indicating whether the sensors must be calibrated in the device (TRUE = calibration required in the device, FALSE = calibration required in the FB)
Output
rDewPointTemp
REAL
Dew point temperature in degrees Celsius or Fahrenheit
Output
eFanLevel
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL
Current fan stage depending on the parameter
eFanLevelConfig
Output
xDI1
BOOL
State of digital input 1 depending on the
parameter eDI1OutpMode:
Output
xEnLocalAdjFb
BOOL
Display indicating whether local operation is possible (TRUE = local operation possible) — feedback
Output
eBusTermin
BELIMO_P_22RTX_1U00X_2_BUS_TERMINATION
Status of the Modbus termination resistor (Active = Enabled)
Output
sSerialNum
STRING
Serial number of the device
Output
wFirmwareVer
WORD
Firmware version of the device
Output
xAlarm
BOOL
FALSE
Collective fault (TRUE = fault)
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication (TRUE = fault)
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
Output
xBusy
BOOL
Communication display (TRUE = communication)
Input Const
xEcoIconPresenceButtonMode
BOOL
FALSE
Enable / disable display / operation of the ECO
icon / button in operating mode PRESENCE_BUTTON
Input Const
tTimeButtonPulse
TIME
TIME#1s0ms
Duration of the pulse at output ‘xButton Presence’
Input Const
eFanStageControlMode
BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE
BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE.AUTOMATIC_STAGES_CONTROL
Definition of the operating mode for fan stage control
Input Const
eFanControlMode
BELIMO_P_22RTX_1U00X_2_FAN_CONTROL_MODE
BELIMO_P_22RTX_1U00X_2_FAN_CONTROL_MODE.MANUAL_MODE_ONLY
Definition of the operating mode for fan control
Input Const
eFanLevelConfig
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL_CONFIG
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL_CONFIG.SEVEN_STAGES
Definition of the number of fan stages
Input Const
rAdjOffsetSetpTempAbs
REAL
3.0
Definition of the adjustment range around the absolute base setpoint temperature (center value) (+/- 5.0 K) (automatic, internal conversion to other temperature units in the RBG)
Input Const
eSetpTempMode
BELIMO_P_22RTX_1U00X_2_SETP_TEMP_MODE
BELIMO_P_22RTX_1U00X_2_SETP_TEMP_MODE.ABSOLUTE_SETPOINT
Affects the adjustment ranges of the absolute and relative setpoint temperature Definition of the operating mode of the setpoint display
Input Const
tBoostModeDuration
TIME
TIME#15m0s0ms
Duration of the operating mode Boost
Input Const
eEcoBoostOnOffIconMode
BELIMO_P_22RTX_1U00X_2_ICON_MODE
BELIMO_P_22RTX_1U00X_2_ICON_MODE.PRESENCE_BUTTON
Central definition of the icon functions Eco, Boost and OnOff
INVISIBLE (icons not visible or operable)
> Visibility Operability on the RBG
Eco: no no
Boost: no no
OnOff: no no
DISPLAY_MODE (display of Eco and OnOff mode)
> Visibility Operability on the RBG
Eco: yes no
Boost: no no
OnOff: yes no
OPERATION_MODE (switching the functions on the RBG as well as via rising edges at the icon inputs)
> Visibility Operability on the RBG
Eco: yes yes
Boost: yes yes
OnOff: yes yes
PRESENCE_BUTTON (extension of usage time with external HVAC.Button1 - FB)
> Visibility Operability on the RBG
Eco: no no
Boost: no no
OnOff: yes yes
Input Const
eWindowIconFunct
BELIMO_P_22RTX_1U00X_2_WINDOW_ICON_FUNCTION
BELIMO_P_22RTX_1U00X_2_WINDOW_ICON_FUNCTION.INPUT_xDsplIconWind
Definition of the icon function Window
Input Const
eWarningIconFunct
BELIMO_P_22RTX_1U00X_2_WARNING_ICON_FUNCTION
BELIMO_P_22RTX_1U00X_2_WARNING_ICON_FUNCTION.DEVICE_ERROR_STATUS
Definition of the icon function Warning
Input Const
eDsplIconsHeatCool
BELIMO_P_22RTX_1U00X_2_SYMBOL_VISIBILITY
BELIMO_P_22RTX_1U00X_2_SYMBOL_VISIBILITY.INVISIBLE
Display of the visibility of the icons for heating and cooling mode
Input Const
eColorScheme
BELIMO_P_22RTX_1U00X_2_COLOR_SCHEME
BELIMO_P_22RTX_1U00X_2_COLOR_SCHEME.WHITE_BACKGROUND
Definition of the display color scheme
Input Const
eOffsetUnit
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE.DEGREES_CELSIUS
Definition of the unit for the offset temperature (
impact: rSetpTempRel (register 36))
Input Const
eTemperatureUnitDisplay
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE_DISPLAY
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE_DISPLAY.DEGREES_CELSIUS
Definition of the unit for the temperature display on the display (effect on: display)
Input Const
eTemperatureUnit
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE.DEGREES_CELSIUS
Definition of the temperature unit (effect on:
rTemp (register 1), rDewPointTemp (register 5) and
rSetpTemp (register 34))
Input Const
xCO2_LED_Enable
BOOL
TRUE
Enable / disable the CO2 LED (TRUE = enable)
Input Const
rCO2_LED_ThresholdYellowRed
REAL
1500.0

