BELIMO_P_22RTX_1U00X_2_EASY

BELIMO_P_22RTX_1U00X_2_EASY (FB)

FUNCTION_BLOCK BELIMO_P_22RTX_1U00X_2_EASY

Representation

Short description

Control of the device series P-22RT..-1U00..-2 from Belimo

Typical application: room operating device in a zone

Guidelines - Software creation

Supported Modbus function codes: 2, 3, 4, 6 and 16. For addressing, the address specifications must be used, not the register addresses. Registers from 111 onward are persistent in the device and must not be written cyclically. Unused registers contain the value 65535 (unsigned)(FFFF - hex) or -1 (signed). Unused registers within the defined ranges may be read / written.

In the constellation eEcoBoostOnOffIconMode = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.OPERATION_MODE is switched to ECO mode with the first rising edge at input xBoostIcon to On/Comfort mode. With the second rising edge, BOOST mode is then activated. When operating at the room operating device, switching from ECO to BOOST takes place immediately. Remedy: write address 30 with FC06 !!! with the desired value; do not write address 22 at the same time.

Measured values - calibration: Class 4

Interfaces

Inputs

Name
Data type
Value range
Initial value
Function

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enable)

byUnitId

BYTE

0

Device address (0 .. 255)

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge)

xUpdateSetp

BOOL

FALSE

Update of setpoints (on every rising edge)

xUpdateConfig

BOOL

FALSE

Update of the configuration (on every rising edge) (read access)

xUpdateStates

BOOL

FALSE

Update of states (on every rising edge)

xUpdateInfo

BOOL

FALSE

Update of the information (on every rising edge)

rSetpTempAbsNight

REAL

18.0

Absolute room setpoint temperature in night mode (unit depends on register address 122)

rSetpTempAbsBaseDay

REAL

22.0

Absolute base room setpoint temperature in day mode (unit depends on register address 120)

rSetpTempRelNight

REAL

0.0

Relative room setpoint temperature in night mode (unit depends on register address 122)

rSetpTempRelBaseDay

REAL

0.0

Relative base room setpoint temperature in day mode (unit depends on register address 122)

xMode

BOOL

FALSE

Input for operating mode/the On/Off icon (function depending on register addresses 139 - 141)

xEcoIcon

BOOL

FALSE

Input for operating mode/the Eco icon (function depending on register addresses 139 - 141)

xBoostIcon

BOOL

FALSE

Input for operating mode/the Boost icon (function depending on register addresses 139 - 141)

eSetpFanLevel

BELIMO_P_22RTX_1U00X_2_FAN_LEVEL

BELIMO_P_22RTX_1U00X_2_FAN_LEVEL.STAGE_0

Set fan level

eIconsHeatCool

BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL

BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL.NONE

Selection of the display of the icon for heating or cooling mode

xDsplIconWarn

BOOL

FALSE

Input for displaying the warning icon (TRUE = enable)

xDsplIconWind

BOOL

FALSE

Input for displaying the window icon (TRUE = enable)

xEnLocalAdj

BOOL

FALSE

Input for displaying the control elements on the room operating device (TRUE = display)

xResError

BOOL

FALSE

Input for resetting the output eErrorCodeCom (on every rising edge)

Outputs

Name
Data type
Value range
Initial value
Function

eOperationMode

BELIMO_P_22RTX_1U00X_2_OPERATION_MODE

Display of the current operating mode on the room operating device (register address 30)

eEcoBoostOnOffIconMode

BELIMO_P_22RTX_1U00X_2_ICON_MODE

Display of the current operating mode

xModeDev

BOOL

Operating mode of the zone controller on the room operating device (FALSE = night operation, TRUE = day operation)

xButtonPresence

BOOL

Pressing the presence button (pulse with duration tTimeButtonPulse) (RBG and/or VISU)

rSetpTempAbs

REAL

Current absolute setpoint temperature depending on the parameter eTemperatureUnit (e.g. +23.5 degrees Celsius) (register address 34) (unit depending on register address 120)

rOffset

REAL

Current difference between rSetpTempAbs and rAdjCenterSetpTemp (range: +/- rAdjOffsetSetpTemp) in day operation (unit depending on register address 120)

rSetpTempRel

REAL

Current relative setpoint temperature depending on the parameter eOffsetUnit (e.g. -2.0 Kelvin) (range: +/- rAdjOffsetSetpTemp) (register address 36) (unit depending on register address 122)

rTemp

REAL

Room temperature (unit depending on register address 120)

rRelHumidity

REAL

Relative room humidity in percent

rCO2

REAL

CO2 concentration (ppm)

eCO2Status

BELIMO_P_22RTX_1U00X_2_CO2_STATUS

Current status of the CO2 actual value monitoring

xSensorOffsetInDevice

BOOL

Display whether the sensors must be calibrated in the device (TRUE = calibration required in the device, FALSE = calibration required in the FB)

rDewPointTemp

REAL

Dew point temperature (unit depending on register address 120 in degrees Celsius or Fahrenheit)

eFanLevel

BELIMO_P_22RTX_1U00X_2_FAN_LEVEL

Current fan level depending on the parameter eFanLevelConfig (register address 22)

xDI1

BOOL

Status of digital input 1 depending on the parameter eDI1OutpMode (RAW: FALSE = Open, TRUE = Closed with +24VDC, PULSE: pulse with duration tTimeDIPulse at each rising edge at input DI1)

xEnLocalAdjFb

BOOL

Display whether local operation is possible (TRUE = local operation possible) — feedback

eBusTermin

BELIMO_P_22RTX_1U00X_2_BUS_TERMINATION

State of the Modbus termination resistor (Active = Enabled)

sSerialNum

STRING

Device serial number

wFirmwareVer

WORD

Firmware version of the device

xAlarmCom

BOOL

Collective fault - communication (TRUE = fault)

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

eErrorCodeDev

SPLUSS_ERROR_CODE_TYPE_2

Error code - device (0 = no error)

xBusy

BOOL

Communication indicator (TRUE = communication)

Inputs and outputs

Name
Data type
Value range
Initial value
Function

ModbusClient

ModbusClientBase

Client of the device

General information on setpoints / parameters (addresses 110 - 149)

The following setpoints / parameters (addresses 110 - 149) are for the function blocks with the index _EASY and _FULL valid in common. In the function block with the index _FULL additional setpoints / parameters can also be defined, which are shown in the table after the next one. These additional setpoints / parameters are only read in the function block with the index _EASY and stored in internal variables. These setpoints / parameters are defined externally there, e.g. using the 'Belimo Assistant' app.

Setpoints / parameters EASY / FULL

Name
Data type
Value range
Initial value
Address
Function

tTimeUpdateActual

TIME

T#3s

Update interval for the processes influenced by the input xUpdateActual are affected (0 = no automatic update, > 0 cyclical update)

tTimeUpdateSetp

TIME

T#0s

Update interval for the processes influenced by the input xUpdateSetp are affected (0 = no automatic update, > 0 cyclical update)

tTimeUpdateConfig

TIME

T#0s

Update interval for the processes influenced by the input xUpdateConfig are affected (0 = no automatic update, > 0 cyclical update)

tTimeUpdateStates

TIME

T#500ms

Update interval for the processes influenced by the input xUpdateStates are affected (0 = no automatic update, > 0 cyclical update)

tTimeUpdateInfo

TIME

T#0s

Update interval for the processes influenced by the input xUpdateInfo are affected (0 = no automatic update, > 0 cyclical update)

eDI1OutpMode

BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE

BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE.RAW

Operating mode of the output xDI1 (RAW, PULSE)

tTimeDIPulse

TIME

T#1s

Duration of the pulse at the output xDI1, if a rising edge is detected at the digital input (eDI1OutpMode = BELIMO_P_22RTX_1U00X_2_FULL_DIGITAL_INPUT_OUTP_MODE.PULSE)

eFanStageControlMode

BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE

BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE.AUTOMATIC_STAGES_CONTROL

31

Definition of the operating mode for controlling the fan stages

xVisuPresence

BOOL

FALSE

Actuation of the presence button in the visualization (affects the output xButtonPresence)

tTimeButtonPulse

TIME

T#1s

Duration of the pulse at output ‘xButton Presence’

Additional setpoints / parameters FULL

Name
Data type
Value range
Initial value
Address
Function

rTempOffset

REAL

+/- 15.0 K

0.0

110

Offset of the room temperature (for calibration of the temperature sensor) in K

rHumidityOffset

REAL

+/- 20.0 %

0.0

111

Offset of the room humidity (for calibration of the humidity sensor) in percent

rCO2Offset

REAL

+/- 500 ppm

0.0

112

Offset of the CO2 sensor (for calibration of the CO2 sensor) in ppm

rCO2_LED_ThresholdGreenYellow

REAL

600.0 - 1249.0 ppm, integer values only

1000.0

115

Threshold for changing the LED color from green to yellow

rCO2_LED_ThresholdYellowRed

REAL

1250.0 - 2000.0 ppm, integer values only

1500.0

116

Threshold for changing the LED color from yellow to red

xCO2_LED_Enable

BOOL

TRUE

117

Enable / disable the CO2 LED (TRUE = enable)

eTemperatureUnit

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE.DEGREES_CELSIUS

120

Definition of the unit for the temperature (influenced by: rTemp (address 1), rDewPointTemp (address 5) and rSetpTemp (address 34))

eTemperatureUnitDisplay

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE_DISPLAY

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE_DISPLAY.DEGREES_CELSIUS

121

Definition of the unit for the temperature display on the display (influences: display)

eOffsetUnit

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE

BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE.DEGREES_CELSIUS

122

Definition of the unit for the relative set temperature (influences: rSetpTempRel (address 36))

eColorScheme

BELIMO_P_22RTX_1U00X_2_COLOR_SCHEME

BELIMO_P_22RTX_1U00X_2_COLOR_SCHEME.WHITE_BACKGROUND

130

Definition of the display color scheme

eDsplIconsHeatCool

BELIMO_P_22RTX_1U00X_2_SYMBOL_VISIBILITY

BELIMO_P_22RTX_1U00X_2_SYMBOL_VISIBILITY.INVISIBLE

134

Display of the visibility of the icons for heating and cooling operation

eWarningIconFunct

BELIMO_P_22RTX_1U00X_2_WARNING_ICON_FUNCTION

BELIMO_P_22RTX_1U00X_2_WARNING_ICON_FUNCTION.DEVICE_ERROR_STATUS

135

Definition of the function of the icon Warning

eWindowIconFunct

BELIMO_P_22RTX_1U00X_2_WINDOW_ICON_FUNCTION

BELIMO_P_22RTX_1U00X_2_WINDOW_ICON_FUNCTION.INPUT_xDsplIconWind

136

Definition of the function of the icon Window

eEcoBoostOnOffIconMode

BELIMO_P_22RTX_1U00X_2_ICON_MODE

BELIMO_P_22RTX_1U00X_2_ICON_MODE.PRESENCE_BUTTON

139 - 141

Central definition of the functions of the icons Eco, Boost and OnOff

tBoostModeDuration

TIME

T#900s

142

Duration of the operating mode Boost

eSetpTempMode

BELIMO_P_22RTX_1U00X_2_SETP_TEMP_MODE

BELIMO_P_22RTX_1U00X_2_SETP_TEMP_MODE.ABSOLUTE_SETPOINT

145

Definition of the operating mode of the setpoint display (absolute / relative)

rAdjCenterSetpTempAbs

REAL

+15.0 … +35.0 degrees Celsius

22.0

146

Definition of the absolute base setpoint temperature (center value) for adjusting the setpoint temperature (+15.00 - 35.00 degrees Celsius) (automatic, internal conversion to other temperature units in the RBG) Affects the absolute setpoint temperature.

rAdjOffsetSetpTempAbs

REAL

-5.0 … +5.0 Kelvin

3.0

147

Definition of the adjustment range around the absolute base setpoint temperature (midpoint) (+/- 5.0 K) (automatic, internal conversion to other temperature units in the RBG). Affects the adjustment ranges of the absolute and relative setpoint temperature

eFanLevelConfig

BELIMO_P_22RTX_1U00X_2_FAN_LEVEL_CONFIG

BELIMO_P_22RTX_1U00X_2_FAN_LEVEL_CONFIG.SEVEN_STAGES

148

Definition of the number of fan stages

eFanControlMode

BELIMO_P_22RTX_1U00X_2_FAN_CONTROL_MODE

BELIMO_P_22RTX_1U00X_2_FAN_CONTROL_MODE.MANUAL_MODE_ONLY

1498

Definition of the operating mode for controlling the fan

Function description

General

This function block controls room operating devices of the P-22RT..-1U00..-2 device series from Belimo via Modbus communication. Configuration (addresses 110 - 149) is carried out in the function block with index _FULL internal, in the function block with the index _EASY external.

Operating modes - room operating device (address 30) — outputs eOperationMode and xModeDev

Four operating modes are distinguished:

0: Off/Protection (xModeDev = FALSE) 1: On/Comfort (xModeDev = TRUE) 2: Eco Mode (xModeDev = TRUE) 3: Boost Mode (xModeDev = TRUE)

Operating modes 2 and 3 can only be selected in addition to operating mode 1. Operating mode 3 is active for a limited time and requires approval of the highest fan stage for correct operation. The operating modes are automatically determined depending on the operating method (see below).

Central definition of the functions of the icons / operating elements OnOff, Eco and Boost (operating methods)

A total of four operating methods are distinguished, which are defined via addresses 139 - 141: (FULL: parameter eEcoBoostOnOffIconMode, EASY: define contents of addresses 139 - 141 externally according to the following list.)

Operating method INVISIBLE

Visibility
Operability
Function

Eco: NO

Eco: NO

Icons not visible or operable

Boost: NO

Boost: NO

Icons not visible or operable

OnOff: NO

OnOff: NO

Icons not visible or operable

Operating method DISPLAY_MODE

Visibility
Operability
Function

Eco: YES

Eco: NO

Display of the Eco and OnOff modes

Boost: NO

Boost: NO

Display of the Eco and OnOff modes

OnOff: YES

OnOff: NO

Display of the Eco and OnOff modes

Operating method OPERATION_MODE

Visibility
Operability
Function

Eco: YES

Eco: YES

Switching of the functions on the RBG as well as by rising edges at the icon inputs

Boost: YES

Boost: YES

Switching of the functions on the RBG as well as by rising edges at the icon inputs

OnOff: YES

OnOff: YES

Switching of the functions on the RBG as well as by rising edges at the icon inputs

Operating method PRESENCE_BUTTON

Visibility
Operability
Function

Eco: NO

Eco: NO

Extension of occupancy time with external HVAC.Button1 - FB

Boost: NO

Boost: NO

Extension of occupancy time with external HVAC.Button1 - FB

OnOff: YES

OnOff: YES

Extension of occupancy time with external HVAC.Button1 - FB

In DISPLAY mode, the operating modes Eco Mode and On/Comfort are defined by the inputs xEcoIcon and xMode (TRUE = On). If none of the inputs is active, operating mode Off/Protection is automatically selected.

In OPERATION mode, the operating modes ECO, Boost and OnOff are defined by the associated inputs (rising edges) and by operation at the room operating device.

In PRESENCE_BUTTON mode, the operating modes Off/Protection and On/Comfort are defined by the input xMode (rising edges: On / Comfort, falling edge: Off/Protection) and in parallel by operation at the room operating device. Each change from night mode to day mode and vice versa, triggered by the room operating device, generates a pulse of duration xButtonPresence at the output tTimeButtonPulse .

Day operation / night operation (output xModeDev)

At output xModeDev the current state of day operation at the room operating device is shown (TRUE = day operation).

Room setpoint temperatures

The room setpoint temperatures are defined in different ways depending on the parameter eSetpTempMode (address 145):

  1. Absolute setpoint (e.g. +23.5 degrees Celsius) (index Abs) (inputs rSetpTempAbsNight, rSetpTempAbsBaseDay) (output rSetpTempAbs)

  2. Relative setpoint (e.g. +1.0 Kelvin) (index Rel) (inputs rSetpTempRelNight, rSetpTempRelBaseDay) (output rSetpTempRel)

Changes to the assigned inputs are transferred immediately in the corresponding state, otherwise at the next transition into this state. Example: A change at input rSetpTempAbsNight is transferred immediately and becomes effective in night operation. Example: A change at input rSetpTempBaseDay does not take effect immediately in night operation, but only at the next transition to day operation.

Changes to the parameters rAdjCenterSetpTempAbs (address 146) or rAdjOffsetSetpTempAbs (address 147) are transferred immediately in the appropriate mState, otherwise delayed. (FULL). Changes to addresses 146 or 147 are captured after the configuration is read again and transferred accordingly (EASY). Changes to the content of address 146 affect only the absolute setpoint temperature, changes to the content of address 147 affect the absolute and relative setpoint temperature.

The current values at the inputs rSetpTempAbsNight and rSetpTempAbsBaseDay must be specified depending on the parameter eTemperatureUnit (address 120). At output output rSetpTempAbs the current setpoint value is then available in the selected unit. The current values at the inputs rSetpTempRelNight and rSetpTempRelBaseDay must be specified depending on the parameter eOffsetUnit (address 122). At output output rSetpTempRel the current setpoint value is then available in the selected unit.

Night operation - room setpoint temperature

When switching from day operation to night operation, the state at input rSetpTempAbsNight is transferred to the room operating device and displayed there (eSetpTempMode = absolute setpoint temperature). When switching from day operation to night operation, the state at input rSetpTempRelNight is transferred to the room operating device and displayed there (eSetpTempMode = relative setpoint temperature). Any change of state at input rSetpTempXXXNight is transferred to the room operating device during night operation.

Day operation - room setpoint temperature

Case 1 - There is not yet a valid room setpoint temperature in day operation

When switching from night operation to day operation, the state at input rSetpTempAbsBaseDay transferred to the room operating device and displayed there. Adjustment is possible on the room operating device in the symmetrical range defined by address 147. The increment is 0.5 K.

Case 2 - A valid room setpoint temperature in day operation already exists

When switching from night mode to day mode, the previous valid room setpoint temperature is transferred to the room operating device and displayed there. Adjustment is possible on the room operating device in the symmetrical range defined by address 147. The increment is 0.5 K.

Output xDI1

At output xDI1 the state at input DI1 of the room operating device is available in different ways (parameter xDI1OutpMode).

Operating modes

RAW

The output immediately adopts the state at input DI1 (FALSE: contact open, TRUE: contact closed with +24VDC)

PULSE

Each rising edge at input DI1 triggers a pulse of duration at the corresponding output xDI1 tTimeDIPulse (default: 1s).

Specification / display of fan level

The preselection of the number of fan stages is done via parameter eFanLevelConfig (address 148). In Boost Mode, the maximum fan stage is specified (independent of input eSetpFanLevel). The fan stage is selected and transmitted via input eSetpFanLevel within the permitted limits. The current fan stage is output via output eFanLevel within the permitted limits. The display of the current fan stage and the setting options is additionally defined by the parameters eFanStagesControlMode (address 31) eFanControlMode (address 149), eFanLevelConfig (address 148) and xDsplFanStages (address 138).

Evaluation of the current CO2 content using a multicolor LED

The evaluation of the current CO2 content is performed using a multicolor LED (off / green / yellow / red) and the output eCO2Status . The threshold for changing the LED color from green to yellow is defined by the parameter rCO2_LED_ThresholdwGreenYellow (address 115). The threshold for changing the LED color from yellow to red is defined by the parameter rCO2_LED_ThresholdYellowRed (address 116). The evaluation and the LED display can be defined by the parameter xCO2_LED_Enable (address 117) (TRUE = display).

Display of symbols / actual values

The display of the desired symbols in the room operating device display is triggered by the TRUE state of the assigned inputs. These inputs are marked with the index Dspl . Example: xDsplTemp = TRUE causes the current room temperature to be displayed on the screen.

Display of faults

Faults are displayed at the collective output xAlarm (= TRUE). It includes communication faults (time delay: gc_Parameters.gc_tOnDelayxAlarmCom, default = 60s) and device faults (direct). Here, the collective fault message, the collective warning message and the excessive CO2 content (LED = red) are output as device fault. At output eErrorCodeCom in the event of a communication error, an explanatory text for the cause is available. The cause of the last communication error is always displayed there.

Codesys

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enable)

Input

byUnitId

BYTE

0

Device address (1 .. 247) (via Belimo Assistant app using NFC)

Input

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge )

Input

xUpdateSetp

BOOL

FALSE

Update of setpoints (on every rising edge )

Input

xUpdateConfig

BOOL

FALSE

Update of the configuration (on every rising edge) (read access)

Input

xUpdateStates

BOOL

FALSE

Update of the states (on each rising edge)

Input

xUpdateInfo

BOOL

FALSE

Update of the information (on every rising edge)

Input

rSetpTempAbsNight

REAL

18.0

Absolute set temperature - night operation (unit depending on eTemperatureUnit)

Input

rSetpTempAbsBaseDay

REAL

22.0

Absolute base set temperature - day operation (unit depending on eTemperatureUnit)

Input

rSetpTempRelNight

REAL

0.0

Relative set temperature - night operation (unit depending on eTemperatureUnit)

Input

rSetpTempRelBaseDay

REAL

0.0

Relative base set temperature - day operation (unit depending on eTemperatureUnit)

Input

xMode

BOOL

FALSE

Display of the icon OnOff (eOnOffIconMode = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.DISPLAY_MODE)

Input

xEcoIcon

BOOL

FALSE

Display of the icon Eco (eEcoIconMode = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.DISPLAY_MODE)

Input

xBoostIcon

BOOL

FALSE

Operation of the icon Boost (eBoostIconMode = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.OPERATION_MODE)

Input

eSetpFanLevel

BELIMO_P_22RTX_1U00X_2_FAN_LEVEL

BELIMO_P_22RTX_1U00X_2_FAN_LEVEL.STAGE_0

(each rising edge switches the boost mode) Setpoint - Current fan stage depending on the parameter eFanLevelConfig Depending on the parameters eFanStagesControlMode (Register 31 - Setpoints_0) and eFanControlMode (Register 149 - Configuration_0), the following operating options are available: Register 31 = Automatic // Register 149 = Hybrid: If level 0 is selected on the RBG, the display of the current level is deactivated and an automatic symbol is shown. If a level greater than 0 is selected on the RBG, the display of the current level is activated and the automatic symbol is hidden. The level selection is possible on the RBG and via register 22. In all other configurations the following applies: The display of the current level is active, it can be changed on the RBG and via register 22, the last change made remains in effect.

Input

eIconsHeatCool

BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL

BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL.NONE

0.0 = Level 0 1.0 = Level 1 2.0 = Level 2 3.0 = Level 3 4.0 = Level 4 5.0 = Level 5 6.0 = Level 6 Selection of heating or cooling mode

Input

xDsplIconWarn

BOOL

FALSE

Display of the symbol Warning (TRUE = display)

Input

xDsplIconWind

BOOL

FALSE

Display of the symbol Window (TRUE = display)

Input

xEnLocalAdj

BOOL

TRUE

Definition whether local operation is possible (TRUE = enable)

Input

xResError

BOOL

FALSE

Reinitialization of the output eErrorCodeCom (with every rising edge)

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

eOperationMode

BELIMO_P_22RTX_1U00X_2_OPERATION_MODE

Current operating mode 0 = OFF_PROTECTION: night operation 1 = ON_COMFORT: day operation 2 = ECO_MODE: day operation — eco operation 3 = BOOST_MODE: day operation — boost operation

Output

eEcoBoostOnOffIconMode

BELIMO_P_22RTX_1U00X_2_ICON_MODE

Central definition of the functions of the icons Eco, Boost and OnOff INVISIBLE (icons not visible and not operable) > Visibility operability on the RBG Eco: no no Boost: no no OnOff: no no DISPLAY_MODE (display of Eco and OnOff modes) > Visibility operability on the RBG Eco: yes no Boost: no no OnOff: yes no OPERATION_MODE (switching the functions on the RBG as well as by rising edges at the icon inputs) > Visibility operability on the RBG Eco: yes yes Boost: yes yes OnOff: yes yes PRESENCE_BUTTON (extended occupancy time with external HVAC.Button1 - FB) > Visibility operability on the RBG Eco: no no Boost: no no OnOff: yes yes Address 139 Address 140 Address 141 Operating mode 0 0 0 INVISIBLE 1 0 1 DISPLAY_MODE 2 1 2 OPERATION_MODE 0 0 2 PRESENCE_BUTTON

Output

xModeDev

BOOL

Operating mode of the zone control from the device (FALSE = night operation, TRUE = day operation)

Output

xButtonPresence

BOOL

Pressing the presence button (pulse with duration tTimeButtonPulse) (RBG and/or VISU)

Output

rSetpTempAbs

REAL

Current absolute setpoint temperature depending on the parameter eTemperatureUnit (e.g. +23.5 degrees Celsius) ( Register 34)

Output

rOffset

REAL

Current difference between rSetpTempAbs and rAdjCenterSetpTemp (range: +/- rAdjOffsetSetpTemp) in day mode

Output

rSetpTempRel

REAL

Current relative setpoint temperature depending on the parameter eOffsetUnit (e.g. -2.0 Kelvin) (range: +/- rAdjOffsetSetpTemp) (register 36)

Output

rTemp

REAL

Current room temperature depending on the parameter eUnitTemperature

Output

rRelHumidity

REAL

Relative room humidity in percent

Output

rCO2

REAL

Current CO2 concentration in ppm

Output

eCO2Status

BELIMO_P_22RTX_1U00X_2_CO2_STATUS

Current status of the CO2 actual value monitoring

Output

xSensorOffsetInDevice

BOOL

Indication of whether the sensors must be calibrated in the device (TRUE = calibration in the device required, FALSE = calibration in the FB required)

Output

rDewPointTemp

REAL

Dew point temperature in degrees Celsius or Fahrenheit

Output

eFanLevel

BELIMO_P_22RTX_1U00X_2_FAN_LEVEL

Current fan level depending on the parameter eFanLevelConfig

Output

xDI1

BOOL

Status of digital input 1 depending on the parameter eDI1OutpMode:

Output

xEnLocalAdjFb

BOOL

Display whether local operation is possible (TRUE = local operation possible) — feedback

Output

eBusTermin

BELIMO_P_22RTX_1U00X_2_BUS_TERMINATION

State of the Modbus termination resistor (Active = Enabled)

Output

sSerialNum

STRING

Device serial number

Output

wFirmwareVer

WORD

Firmware version of the device

Output

xAlarm

BOOL

FALSE

Collective fault (TRUE = fault)

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication (TRUE = fault)

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

Output

xBusy

BOOL

Communication indicator (TRUE = communication)

Input Const

tTimeButtonPulse

TIME

TIME#1s0ms

Duration of the pulse at output ‘xButton Presence’

Input Const

xVisuPresence

BOOL

FALSE

Pressing the presence button in the visualization

Input Const

eFanStageControlMode

BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE

BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE.AUTOMATIC_STAGES_CONTROL

Definition of the operating mode for controlling the stages of the fan

Input Const

tTimeDIPulse

TIME

TIME#1s0ms

Duration of the pulse at the output xDI1, if a rising edge is detected at the digital input ( eDI1OutpMode = BELIMO_P_22RTX_1U00X_2_FULL_DIGITAL_INPUT_OUTP_MODE.PULSE)

Input Const

eDI1OutpMode

BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE

BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE.RAW

Operating mode of the output xDI1 (RAW, PULSE)

Input Const

tTimeUpdateInfo

TIME

TIME#0ms

Update interval for the processes influenced by the input xUpdateInfo influenced

Input Const

tTimeUpdateStates

TIME

TIME#500ms

Update interval for the processes influenced by the input xUpdateStates influenced

Input Const

tTimeUpdateConfig

TIME

TIME#0ms

Update interval for the processes influenced by the input xUpdateConfig influenced

Input Const

tTimeUpdateSetp

TIME

TIME#45s0ms

Update interval for the processes influenced by the input xUpdateSetp influenced

Input Const

tTimeUpdateActual

TIME

TIME#3s0ms

Update interval for the processes influenced by the input xUpdateActual influenced

Last updated