BELIMO_P_22RTX_1U00X_2_EASY
BELIMO_P_22RTX_1U00X_2_EASY (FB)
FUNCTION_BLOCK BELIMO_P_22RTX_1U00X_2_EASY
Representation

Short description
Control of device series P-22RT..-1U00..-2 from Belimo
Typical application: room operating unit in one zone
Guidelines - software creation
Supported Modbus function codes: 2, 3, 4, 6 and 16. For addressing, the address values are to be used, not the register addresses. Registers from 111 onward are persistent in the device and must not be written cyclically. Unused registers contain the value 65535 (unsigned)(FFFF - hex) or -1 (signed). Unused registers within the defined ranges may be read/written.
In the constellation eEcoBoostOnOffIconMode = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.OPERATION_MODE in ECO mode with the first rising edge at input xBoostIcon switched to On/Comfort mode. With the second rising edge, BOOST mode is then activated. When operated on the room operating unit, switching from ECO to BOOST takes place immediately.
Measured values - calibration: Class 4
Interfaces
Inputs
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
byUnitId
BYTE
0
Device address (0 .. 255)
xUpdateActual
BOOL
FALSE
Update of the actual values (on every rising edge)
xUpdateSetp
BOOL
FALSE
Update of setpoints (on every rising edge)
xUpdateConfig
BOOL
FALSE
Update of the configuration (on every rising edge) (read access)
xUpdateStates
BOOL
FALSE
Update of the states (on every rising edge)
xUpdateInfo
BOOL
FALSE
Update of the information (on every rising edge)
rSetpTempAbsNight
REAL
18.0
Absolute room setpoint temperature in night mode (unit depends on register address 122)
rSetpTempAbsBaseDay
REAL
22.0
Absolute base room setpoint temperature in day mode (unit depends on register address 120)
rSetpTempRelNight
REAL
0.0
Relative room setpoint temperature in night mode (unit depends on register address 122)
rSetpTempRelBaseDay
REAL
0.0
Relative base room setpoint temperature in day mode (unit depends on register address 122)
xMode
BOOL
FALSE
Input for operating mode/the On/Off icon (function depending on register addresses 139 - 141)
xEcoIcon
BOOL
FALSE
Input for operating mode/the Eco icon (function depending on register addresses 139 - 141)
xBoostIcon
BOOL
FALSE
Input for operating mode/the Boost icon (function depending on register addresses 139 - 141)
eSetpFanLevel
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL.STAGE_0
Set fan stage
eIconsHeatCool
BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL
BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL.NONE
Selection of the icon display for heating or cooling operation
xDsplIconWarn
BOOL
FALSE
Input for displaying the warning icon (TRUE = enabled)
xDsplIconWind
BOOL
FALSE
Input for displaying the window icon (TRUE = enabled)
xEnLocalAdj
BOOL
FALSE
Input for displaying the controls on the room operating unit (TRUE = display)
xResError
BOOL
FALSE
Input for resetting the output eErrorCodeCom (on every rising edge)
Outputs
eOperationMode
BELIMO_P_22RTX_1U00X_2_OPERATION_MODE
Display of the current operating mode on the room operating unit (register address 30)
eEcoBoostOnOffIconMode
BELIMO_P_22RTX_1U00X_2_ICON_MODE
Display of the current operating mode
xModeDev
BOOL
Operating mode of zone control on the room operating unit (FALSE = night mode, TRUE = day mode)
xButtonPresence
BOOL
Actuation of the presence button (pulse with duration tTimeButtonPulse) (RBG and/or VISU)
rSetpTempAbs
REAL
Current absolute setpoint temperature depending on the parameter eTemperatureUnit (e.g. +23.5 degrees Celsius) (register address 34) (unit depends on register address 120)
rOffset
REAL
Current difference between rSetpTempAbs and rAdjCenterSetpTemp (range: +/- rAdjOffsetSetpTemp) in day mode (unit depends on register address 120)
rSetpTempRel
REAL
Current relative setpoint temperature depending on the parameter eOffsetUnit (e.g. -2.0 Kelvin) (range: +/- rAdjOffsetSetpTemp) (register address 36) (unit depends on register address 122)
rTemp
REAL
Room temperature (unit depends on register address 120)
rRelHumidity
REAL
Relative room humidity in percent
rCO2
REAL
CO2 concentration (ppm)
eCO2Status
BELIMO_P_22RTX_1U00X_2_CO2_STATUS
Current status of the CO2 actual-value monitoring
xSensorOffsetInDevice
BOOL
Indication whether the sensor calibration must be performed in the device (TRUE = calibration required in the device, FALSE = calibration required in the FB)
rDewPointTemp
REAL
Dew point temperature (unit depends on register address 120 in degrees Celsius or Fahrenheit)
eFanLevel
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL
Current fan stage depending on the parameter eFanLevelConfig (register address 22)
xDI1
BOOL
State of digital input 1 depending on the parameter eDI1OutpMode (RAW: FALSE = open, TRUE = closed with +24VDC, PULSE: pulse with duration tTimeDIPulse on every rising edge at input DI1)
xEnLocalAdjFb
BOOL
Indication whether local operation is possible (TRUE = local operation possible) — feedback
eBusTermin
BELIMO_P_22RTX_1U00X_2_BUS_TERMINATION
Status of the Modbus termination resistor (Active = Enabled)
sSerialNum
STRING
Serial number of the device
wFirmwareVer
WORD
Firmware version of the device
xAlarmCom
BOOL
Collective fault - communication (TRUE = fault)
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
eErrorCodeDev
SPLUSS_ERROR_CODE_TYPE_2
Error code - device (0 = no error)
xBusy
BOOL
Communication display (TRUE = communication)
Inputs and outputs
ModbusClient
ModbusClientBase
Client of the device
General information on setpoints / parameters (addresses 110 - 149)
The following setpoints / parameters (addresses 110 - 149) are common to the function blocks with index _EASY and _FULL . In the function block with index _FULL additional setpoints / parameters can also be defined, which are shown in the table after next. These additional setpoints / parameters are only read in the function block with index _EASY and stored in internal variables. These setpoints / parameters are defined externally there, e.g. using the 'Belimo Assistant' app.
Setpoints / parameters EASY / FULL
tTimeUpdateActual
TIME
T#3s
Update interval for the processes influenced by the input xUpdateActual can be influenced (0 = no automatic update, > 0 cyclic update)
tTimeUpdateSetp
TIME
T#0s
Update interval for the processes influenced by the input xUpdateSetp can be influenced (0 = no automatic update, > 0 cyclic update)
tTimeUpdateConfig
TIME
T#0s
Update interval for the processes influenced by the input xUpdateConfig can be influenced (0 = no automatic update, > 0 cyclic update)
tTimeUpdateStates
TIME
T#500ms
Update interval for the processes influenced by the input xUpdateStates can be influenced (0 = no automatic update, > 0 cyclic update)
tTimeUpdateInfo
TIME
T#0s
Update interval for the processes influenced by the input xUpdateInfo can be influenced (0 = no automatic update, > 0 cyclic update)
eDI1OutpMode
BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE
BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE.RAW
Operating mode of the output xDI1 (RAW, PULSE)
tTimeDIPulse
TIME
T#1s
Duration of the pulse at the output xDI1, if a rising edge is detected at the digital input (eDI1OutpMode = BELIMO_P_22RTX_1U00X_2_FULL_DIGITAL_INPUT_OUTP_MODE.PULSE)
eFanStageControlMode
BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE
BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE.AUTOMATIC_STAGES_CONTROL
31
Definition of the operating mode for controlling the fan stages
xVisuPresence
BOOL
FALSE
Actuation of the presence button in the visualization (affects the output xButtonPresence)
tTimeButtonPulse
TIME
T#1s
Duration of the pulse at the output 'xButton Presence'
Additional setpoints / parameters FULL
rTempOffset
REAL
+/- 15.0 K
0.0
110
Room temperature offset (for calibration of the temperature sensor) in K
rHumidityOffset
REAL
+/- 20.0 %
0.0
111
Room humidity offset (for calibration of the humidity sensor) in percent
rCO2Offset
REAL
+/- 500 ppm
0.0
112
Offset of the CO2 sensor (for calibration of the CO2 sensor) in ppm
rCO2_LED_ThresholdGreenYellow
REAL
600.0 - 1249.0 ppm, integer values only
1000.0
115
Threshold for switching the LED color from green to yellow
rCO2_LED_ThresholdYellowRed
REAL
1250.0 - 2000.0 ppm, integer values only
1500.0
116
Threshold for switching the LED color from yellow to red
xCO2_LED_Enable
BOOL
TRUE
117
Enable / disable the CO2 LED (TRUE = enable)
eTemperatureUnit
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE.DEGREES_CELSIUS
120
Definition of the unit for the temperature (influence: rTemp (address 1), rDewPointTemp (address 5) and rSetpTemp (address 34))
eTemperatureUnitDisplay
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE_DISPLAY
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE_DISPLAY.DEGREES_CELSIUS
121
Definition of the unit for the temperature display on the display (influence: display)
eOffsetUnit
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE.DEGREES_CELSIUS
122
Definition of the unit for the relative setpoint temperature (influence: rSetpTempRel (address 36))
eColorScheme
BELIMO_P_22RTX_1U00X_2_COLOR_SCHEME
BELIMO_P_22RTX_1U00X_2_COLOR_SCHEME.WHITE_BACKGROUND
130
Definition of the color scheme of the display
eDsplIconsHeatCool
BELIMO_P_22RTX_1U00X_2_SYMBOL_VISIBILITY
BELIMO_P_22RTX_1U00X_2_SYMBOL_VISIBILITY.INVISIBLE
134
Display of the visibility of the icons for heating and cooling operation
eWarningIconFunct
BELIMO_P_22RTX_1U00X_2_WARNING_ICON_FUNCTION
BELIMO_P_22RTX_1U00X_2_WARNING_ICON_FUNCTION.DEVICE_ERROR_STATUS
135
Definition of the function of the icon Warning
eWindowIconFunct
BELIMO_P_22RTX_1U00X_2_WINDOW_ICON_FUNCTION
BELIMO_P_22RTX_1U00X_2_WINDOW_ICON_FUNCTION.INPUT_xDsplIconWind
136
Definition of the function of the icon Window
eEcoBoostOnOffIconMode
BELIMO_P_22RTX_1U00X_2_ICON_MODE
BELIMO_P_22RTX_1U00X_2_ICON_MODE.PRESENCE_BUTTON
139 - 141
Central definition of the icon functions Eco, Boost and OnOff
tBoostModeDuration
TIME
T#900s
142
Duration of the operating mode Boost
eSetpTempMode
BELIMO_P_22RTX_1U00X_2_SETP_TEMP_MODE
BELIMO_P_22RTX_1U00X_2_SETP_TEMP_MODE.ABSOLUTE_SETPOINT
145
Definition of the operating mode of the setpoint display (absolute / relative)
rAdjCenterSetpTempAbs
REAL
+15.0 … +35.0 degrees Celsius
22.0
146
Definition of the absolute base setpoint temperature (center value) for adjusting the setpoint temperature (+15.00 - 35.00 degrees Celsius) (automatic, internal conversion to other temperature units in the RBG) Affects the absolute setpoint temperature.
rAdjOffsetSetpTempAbs
REAL
-5.0 … +5.0 Kelvin
3.0
147
Definition of the adjustment range around the absolute base setpoint temperature (center value) (+/- 5.0 K) (automatic, internal conversion to other temperature units in the RBG). Affects the adjustment ranges of the absolute and relative setpoint temperature
eFanLevelConfig
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL_CONFIG
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL_CONFIG.SEVEN_STAGES
148
Definition of the number of fan stages
eFanControlMode
BELIMO_P_22RTX_1U00X_2_FAN_CONTROL_MODE
BELIMO_P_22RTX_1U00X_2_FAN_CONTROL_MODE.MANUAL_MODE_ONLY
1498
Definition of the operating mode for controlling the fan
Function description
General
This function block controls room operating units of the device series P-22RT..-1U00..-2 from Belimo via Modbus communication. Configuration (addresses 110 - 149) is carried out in the function block with index _FULL internally, in the function block with index _EASY externally.
Operating modes - room operating unit (address 30) — outputs eOperationMode and xModeDev
Four operating modes are distinguished:
0: Off/Protection (xModeDev = FALSE) 1: On/Comfort (xModeDev = TRUE) 2: Eco Mode (xModeDev = TRUE) 3: Boost Mode (xModeDev = TRUE)
Operating modes 2 and 3 can only be selected in addition to operating mode 1. Operating mode 3 is active for a limited time and requires enablement of the highest fan stage for correct operation. The operating modes are automatically determined depending on the operating mode (see below).
Central definition of the functions of the icons / controls OnOff, Eco and Boost (operating modes)
A total of four operating modes are distinguished, which are defined via addresses 139 - 141: (FULL: parameter eEcoBoostOnOffIconMode, EASY: define the contents of addresses 139 - 141 externally according to the following list.)
Operating mode INVISIBLE
Eco: NO
Eco: NO
Icons not visible or operable
Boost: NO
Boost: NO
Icons not visible or operable
OnOff: NO
OnOff: NO
Icons not visible or operable
Operating mode DISPLAY_MODE
Eco: YES
Eco: NO
Display of the Eco and OnOff modes
Boost: NO
Boost: NO
Display of the Eco and OnOff modes
OnOff: YES
OnOff: NO
Display of the Eco and OnOff modes
Operating mode OPERATION_MODE
Eco: YES
Eco: YES
Switching of the functions on the RBG as well as through rising edges at the icon inputs
Boost: YES
Boost: YES
Switching of the functions on the RBG as well as through rising edges at the icon inputs
OnOff: YES
OnOff: YES
Switching of the functions on the RBG as well as through rising edges at the icon inputs
Operating mode PRESENCE_BUTTON
Eco: NO
Eco: NO
Usage time extension with external HVAC.Button1 FB
Boost: NO
Boost: NO
Usage time extension with external HVAC.Button1 FB
OnOff: YES
OnOff: YES
Usage time extension with external HVAC.Button1 FB
In DISPLAY mode, the operating modes Eco Mode and On/Comfort are defined by the inputs xEcoIcon and xMode (TRUE = On). If none of the inputs is active, operating mode Off/Protection is selected automatically.
In OPERATION mode, the operating modes ECO, Boost and OnOff are defined by the corresponding inputs (rising edges) and by operation on the room operating unit.
In PRESENCE_BUTTON mode, the operating modes Off/Protection and On/Comfort are defined by the input xMode (rising edges: On / Comfort, falling edge: Off/Protection) and in parallel by operation on the room operating unit. With every change from night mode to day mode and vice versa triggered by the room operating unit, an impulse of duration xButtonPresence is generated at output tTimeButtonPulse .
Day mode / night mode (output xModeDev)
At output xModeDev the current state of day mode on the room operating unit is displayed (TRUE = day mode).
Room setpoint temperatures
The room setpoint temperatures are defined in different ways depending on the parameter eSetpTempMode (address 145):
Absolute setpoint (e.g. +23.5 degrees Celsius) (index
Abs) (inputsrSetpTempAbsNight,rSetpTempAbsBaseDay) (outputrSetpTempAbs)Relative setpoint (e.g. +1.0 Kelvin) (index
Rel) (inputsrSetpTempRelNight,rSetpTempRelBaseDay) (outputrSetpTempRel)
Changes to the associated inputs are transferred immediately in the corresponding state, otherwise at the next transition to this state. Example: A change at input rSetpTempAbsNight is transferred and becomes effective immediately in night mode. Example: A change at input rSetpTempBaseDay does not take effect immediately in night mode, but only at the next transition to day mode.
Changes to the parameters rAdjCenterSetpTempAbs (address 146) or rAdjOffsetSetpTempAbs (address 147) are transferred immediately in the appropriate state, otherwise with a delay. (FULL). Changes to addresses 146 and 147 are recorded after the configuration has been read again and transferred accordingly (EASY). Changes to the content of address 146 affect only the absolute setpoint temperature; changes to the content of address 147 affect the absolute and relative setpoint temperature.
The current values at inputs rSetpTempAbsNight and rSetpTempAbsBaseDay are to be specified depending on the parameter eTemperatureUnit (address 120). At output output rSetpTempAbs the current setpoint value is then available in the selected unit. The current values at inputs rSetpTempRelNight and rSetpTempRelBaseDay are to be specified depending on the parameter eOffsetUnit (address 122). At output output rSetpTempRel the current setpoint value is then available in the selected unit.
Night mode - room setpoint temperature
When switching from day mode to night mode, the state at input rSetpTempAbsNight is transferred to the room operating unit and displayed there (eSetpTempMode = absolute setpoint temperature). When switching from day mode to night mode, the state at input rSetpTempRelNight is transferred to the room operating unit and displayed there (eSetpTempMode = relative setpoint temperature). Any change of state at input rSetpTempXXXNight is transferred to the room operating unit during night mode.
Day mode - room setpoint temperature
Case 1 - There is not yet a valid room setpoint temperature in day mode
When switching from night mode to day mode, the state at input rSetpTempAbsBaseDay is transferred to the room operating unit and displayed there. On the room operating unit, adjustment is possible in the symmetrical range defined by address 147. The step size is 0.5K.
Case 2 - There is already a valid room setpoint temperature in day mode
When switching from night mode to day mode, the previous valid room setpoint temperature is transferred to the room operating unit and displayed there. On the room operating unit, adjustment is possible in the symmetrical range defined by address 147. The step size is 0.5K.
Output xDI1
At output xDI1 the state at input DI1 of the room operating unit is available in different ways (parameter xDI1OutpMode).
Operating modes
RAW
The output immediately adopts the state at input DI1 (FALSE: contact open, TRUE: contact closed with +24VDC)
PULSE
Each rising edge at input DI1 triggers a pulse of duration tTimeDIPulse (default: 1s) at the corresponding output xDI1.
Specification / display of the fan stage
The preselection of the number of fan stages is made via the parameter eFanLevelConfig (address 148). In Boost Mode, the maximum fan stage is specified (independent of input eSetpFanLevel). The fan stage is selected and transferred via input eSetpFanLevel within the permissible limits. The current fan stage is output via output eFanLevel within the permissible limits. The display of the current fan stage and the setting options are additionally defined by the parameters eFanStagesControlMode (address 31) eFanControlMode (address 149), eFanLevelConfig (address 148) and xDsplFanStages (address 138).
Assessment of the current CO2 content using a multicolor LED
The assessment of the current CO2 content is performed using a multicolor LED (off / green / yellow / red) and output eCO2Status . The threshold for the transition of the LED color from green to yellow is defined by the parameter rCO2_LED_ThresholdwGreenYellow (address 115). The threshold for the transition of the LED color from yellow to red is defined by the parameter rCO2_LED_ThresholdYellowRed (address 116). The assessment and the LED display can be defined by the parameter xCO2_LED_Enable (address 117) (TRUE = display).
Display of symbols / actual values
The display of the desired symbols in the room operating unit display is triggered by the TRUE state of the associated inputs. These inputs are identified with the index Dspl . Example: xDsplTemp = TRUE causes the current room temperature to be displayed on the screen.
Display of faults
Faults are displayed at the collective output xAlarm (= TRUE). It includes communication faults (time delay: gc_Parameters.gc_tOnDelayxAlarmCom, default = 60s) and device faults (direct). The collective error message, the collective warning message and the CO2 level that is too high (LED = red) are output here as device fault. At output eErrorCodeCom an explanatory text for the cause is available in the event of a communication error. The cause of the last communication error is always displayed there.
Codesys
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
Input
byUnitId
BYTE
0
Device address (1 .. 247) (via Belimo Assistant app via NFC)
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints (on every rising edge )
Input
xUpdateConfig
BOOL
FALSE
Update of the configuration (on every rising edge) (read access)
Input
xUpdateStates
BOOL
FALSE
Update of the states (on every rising edge)
Input
xUpdateInfo
BOOL
FALSE
Update of the information (on every rising edge)
Input
rSetpTempAbsNight
REAL
18.0
Absolute setpoint temperature - night mode (unit depending on eTemperatureUnit)
Input
rSetpTempAbsBaseDay
REAL
22.0
Absolute base setpoint temperature - day mode (unit depending on eTemperatureUnit)
Input
rSetpTempRelNight
REAL
0.0
Relative setpoint temperature - night mode (unit depending on eTemperatureUnit)
Input
rSetpTempRelBaseDay
REAL
0.0
Relative base setpoint temperature - day mode (unit depending on eTemperatureUnit)
Input
xMode
BOOL
FALSE
Display of the icon OnOff (eOnOffIconMode = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.DISPLAY_MODE)
Input
xEcoIcon
BOOL
FALSE
Display of the icon Eco (eEcoIconMode = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.DISPLAY_MODE)
Input
xBoostIcon
BOOL
FALSE
Operation of the icon Boost (eBoostIconMode = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.OPERATION_MODE)
Input
eSetpFanLevel
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL.STAGE_0
(each rising edge toggles Boost mode)
Setpoint - current fan stage depending on the parameter eFanLevelConfig
Depending on the parameters eFanStagesControlMode (register 31 - setpoints_0) and eFanControlMode (register 149 - configuration_0), the following operating options are available:
Register 31 = Automatic // Register 149 = Hybrid:
If stage 0 is selected on the RBG, the display of the current stage is deactivated and an automatic symbol is shown.
If a stage greater than 0 is selected on the RBG, the display of the current stage is activated and the automatic symbol is hidden.
Stage selection is possible on the RBG and via register 22.
In all other constellations, the following applies:
The display of the current stage is active, it can be changed on the RBG and via register 22, and the last change made remains in effect.
Input
eIconsHeatCool
BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL
BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL.NONE
0.0 = stage 0 1.0 = stage 1 2.0 = stage 2 3.0 = stage 3 4.0 = stage 4 5.0 = stage 5 6.0 = stage 6 Selection of heating or cooling operation
Input
xDsplIconWarn
BOOL
FALSE
Display of the symbol Warning (TRUE = display)
Input
xDsplIconWind
BOOL
FALSE
Display of the symbol Window (TRUE = display)
Input
xEnLocalAdj
BOOL
TRUE
Definition of whether local operation is possible (TRUE = enable)
Input
xResError
BOOL
FALSE
Reinitialization of the output eErrorCodeCom (on every
rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
eOperationMode
BELIMO_P_22RTX_1U00X_2_OPERATION_MODE
Current operating mode 0 = OFF_PROTECTION: night mode 1 = ON_COMFORT: day mode 2 = ECO_MODE: day mode — eco mode 3 = BOOST_MODE: day mode — boost mode
Output
eEcoBoostOnOffIconMode
BELIMO_P_22RTX_1U00X_2_ICON_MODE
Central definition of the icon functions Eco, Boost and OnOff
INVISIBLE (icons not visible or operable)
> Visibility Operability on the RBG
Eco: no no
Boost: no no
OnOff: no no
DISPLAY_MODE (display of the Eco and OnOff modes)
> Visibility Operability on the RBG
Eco: yes no
Boost: no no
OnOff: yes no
OPERATION_MODE (switching of the functions on the RBG as well as by rising edges at the icon inputs)
> Visibility Operability on the RBG
Eco: yes yes
Boost: yes yes
OnOff: yes yes
PRESENCE_BUTTON (usage time extension with external HVAC.Button1 FB)
> Visibility Operability on the RBG
Eco: no no
Boost: no no
OnOff: yes yes
Address 139 Address 140 Address 141 Operating mode
0 0 0 INVISIBLE
1 0 1 DISPLAY_MODE
2 1 2 OPERATION_MODE
0 0 2 PRESENCE_BUTTON
Output
xModeDev
BOOL
Operating mode of zone control from the device (FALSE = night mode, TRUE = day mode)
Output
xButtonPresence
BOOL
Actuation of the presence button (pulse with duration
tTimeButtonPulse) (RBG and/or VISU)
Output
rSetpTempAbs
REAL
Current absolute setpoint temperature depending on the
parameter eTemperatureUnit (e.g. +23.5 degrees Celsius) (
register 34)
Output
rOffset
REAL
Current difference between rSetpTempAbs and
rAdjCenterSetpTemp (range: +/- rAdjOffsetSetpTemp)
in day mode
Output
rSetpTempRel
REAL
Current relative setpoint temperature depending on the
parameter eOffsetUnit (e.g. -2.0 Kelvin) (range: +/-
rAdjOffsetSetpTemp) (register 36)
Output
rTemp
REAL
Current room temperature depending on the parameter
eUnitTemperature
Output
rRelHumidity
REAL
Relative room humidity in percent
Output
rCO2
REAL
Current CO2 level in ppm
Output
eCO2Status
BELIMO_P_22RTX_1U00X_2_CO2_STATUS
Current status of the CO2 actual-value monitoring
Output
xSensorOffsetInDevice
BOOL
Indication whether the sensor calibration must be carried out in the device (TRUE = calibration required in the device, FALSE = calibration required in the FB)
Output
rDewPointTemp
REAL
Dew point temperature in degrees Celsius or Fahrenheit
Output
eFanLevel
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL
Current fan stage depending on the parameter
eFanLevelConfig
Output
xDI1
BOOL
State of digital input 1 depending on the
parameter eDI1OutpMode:
Output
xEnLocalAdjFb
BOOL
Indication whether local operation is possible (TRUE = local operation possible) — feedback
Output
eBusTermin
BELIMO_P_22RTX_1U00X_2_BUS_TERMINATION
Status of the Modbus termination resistor (Active = Enabled)
Output
sSerialNum
STRING
Serial number of the device
Output
wFirmwareVer
WORD
Firmware version of the device
Output
xAlarm
BOOL
FALSE
Collective fault (TRUE = fault)
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication (TRUE = fault)
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
Output
xBusy
BOOL
Communication display (TRUE = communication)
Input Const
tTimeButtonPulse
TIME
TIME#1s0ms
Duration of the pulse at the output 'xButton Presence'
Input Const
xVisuPresence
BOOL
FALSE
Actuation of the presence button in the visualization
Input Const
eFanStageControlMode
BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE
BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE.AUTOMATIC_STAGES_CONTROL
Definition of the operating mode for controlling the fan stages of the fan
Input Const
tTimeDIPulse
TIME
TIME#1s0ms
Duration of the pulse at the output xDI1, if a rising edge is detected at the digital
input (
eDI1OutpMode = BELIMO_P_22RTX_1U00X_2_FULL_DIGITAL_INPUT_OUTP_MODE.PULSE)

