BELIMO_P_22RTX_1U00X_2_EASY
BELIMO_P_22RTX_1U00X_2_EASY (FB)
BELIMO_P_22RTX_1U00X_2_EASY (FB)FUNCTION_BLOCK BELIMO_P_22RTX_1U00X_2_EASY
Representation

Short description
Control of the device series P-22RT..-1U00..-2 from Belimo
Typical application: room operating device in a zone
Guidelines - Software creation
Supported Modbus function codes: 2, 3, 4, 6 and 16. For addressing, the address specifications must be used, not the register addresses. Registers from 111 onward are persistent in the device and must not be written cyclically. Unused registers contain the value 65535 (unsigned)(FFFF - hex) or -1 (signed). Unused registers within the defined ranges may be read / written.
In the constellation eEcoBoostOnOffIconMode = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.OPERATION_MODE is switched to ECO mode with the first rising edge at input xBoostIcon to On/Comfort mode. With the second rising edge, BOOST mode is then activated. When operating at the room operating device, switching from ECO to BOOST takes place immediately. Remedy: write address 30 with FC06 !!! with the desired value; do not write address 22 at the same time.
Measured values - calibration: Class 4
Interfaces
Inputs
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
byUnitId
BYTE
0
Device address (0 .. 255)
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge)
xUpdateSetp
BOOL
FALSE
Update of setpoints (on every rising edge)
xUpdateConfig
BOOL
FALSE
Update of the configuration (on every rising edge) (read access)
xUpdateStates
BOOL
FALSE
Update of states (on every rising edge)
xUpdateInfo
BOOL
FALSE
Update of the information (on every rising edge)
rSetpTempAbsNight
REAL
18.0
Absolute room setpoint temperature in night mode (unit depends on register address 122)
rSetpTempAbsBaseDay
REAL
22.0
Absolute base room setpoint temperature in day mode (unit depends on register address 120)
rSetpTempRelNight
REAL
0.0
Relative room setpoint temperature in night mode (unit depends on register address 122)
rSetpTempRelBaseDay
REAL
0.0
Relative base room setpoint temperature in day mode (unit depends on register address 122)
xMode
BOOL
FALSE
Input for operating mode/the On/Off icon (function depending on register addresses 139 - 141)
xEcoIcon
BOOL
FALSE
Input for operating mode/the Eco icon (function depending on register addresses 139 - 141)
xBoostIcon
BOOL
FALSE
Input for operating mode/the Boost icon (function depending on register addresses 139 - 141)
eSetpFanLevel
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL.STAGE_0
Set fan level
eIconsHeatCool
BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL
BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL.NONE
Selection of the display of the icon for heating or cooling mode
xDsplIconWarn
BOOL
FALSE
Input for displaying the warning icon (TRUE = enable)
xDsplIconWind
BOOL
FALSE
Input for displaying the window icon (TRUE = enable)
xEnLocalAdj
BOOL
FALSE
Input for displaying the control elements on the room operating device (TRUE = display)
xResError
BOOL
FALSE
Input for resetting the output eErrorCodeCom (on every rising edge)
Outputs
eOperationMode
BELIMO_P_22RTX_1U00X_2_OPERATION_MODE
Display of the current operating mode on the room operating device (register address 30)
eEcoBoostOnOffIconMode
BELIMO_P_22RTX_1U00X_2_ICON_MODE
Display of the current operating mode
xModeDev
BOOL
Operating mode of the zone controller on the room operating device (FALSE = night operation, TRUE = day operation)
xButtonPresence
BOOL
Pressing the presence button (pulse with duration tTimeButtonPulse) (RBG and/or VISU)
rSetpTempAbs
REAL
Current absolute setpoint temperature depending on the parameter eTemperatureUnit (e.g. +23.5 degrees Celsius) (register address 34) (unit depending on register address 120)
rOffset
REAL
Current difference between rSetpTempAbs and rAdjCenterSetpTemp (range: +/- rAdjOffsetSetpTemp) in day operation (unit depending on register address 120)
rSetpTempRel
REAL
Current relative setpoint temperature depending on the parameter eOffsetUnit (e.g. -2.0 Kelvin) (range: +/- rAdjOffsetSetpTemp) (register address 36) (unit depending on register address 122)
rTemp
REAL
Room temperature (unit depending on register address 120)
rRelHumidity
REAL
Relative room humidity in percent
rCO2
REAL
CO2 concentration (ppm)
eCO2Status
BELIMO_P_22RTX_1U00X_2_CO2_STATUS
Current status of the CO2 actual value monitoring
xSensorOffsetInDevice
BOOL
Display whether the sensors must be calibrated in the device (TRUE = calibration required in the device, FALSE = calibration required in the FB)
rDewPointTemp
REAL
Dew point temperature (unit depending on register address 120 in degrees Celsius or Fahrenheit)
eFanLevel
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL
Current fan level depending on the parameter eFanLevelConfig (register address 22)
xDI1
BOOL
Status of digital input 1 depending on the parameter eDI1OutpMode (RAW: FALSE = Open, TRUE = Closed with +24VDC, PULSE: pulse with duration tTimeDIPulse at each rising edge at input DI1)
xEnLocalAdjFb
BOOL
Display whether local operation is possible (TRUE = local operation possible) — feedback
eBusTermin
BELIMO_P_22RTX_1U00X_2_BUS_TERMINATION
State of the Modbus termination resistor (Active = Enabled)
sSerialNum
STRING
Device serial number
wFirmwareVer
WORD
Firmware version of the device
xAlarmCom
BOOL
Collective fault - communication (TRUE = fault)
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
eErrorCodeDev
SPLUSS_ERROR_CODE_TYPE_2
Error code - device (0 = no error)
xBusy
BOOL
Communication indicator (TRUE = communication)
Inputs and outputs
ModbusClient
ModbusClientBase
Client of the device
General information on setpoints / parameters (addresses 110 - 149)
The following setpoints / parameters (addresses 110 - 149) are for the function blocks with the index _EASY and _FULL valid in common. In the function block with the index _FULL additional setpoints / parameters can also be defined, which are shown in the table after the next one. These additional setpoints / parameters are only read in the function block with the index _EASY and stored in internal variables. These setpoints / parameters are defined externally there, e.g. using the 'Belimo Assistant' app.
Setpoints / parameters EASY / FULL
tTimeUpdateActual
TIME
T#3s
Update interval for the processes influenced by the input xUpdateActual are affected (0 = no automatic update, > 0 cyclical update)
tTimeUpdateSetp
TIME
T#0s
Update interval for the processes influenced by the input xUpdateSetp are affected (0 = no automatic update, > 0 cyclical update)
tTimeUpdateConfig
TIME
T#0s
Update interval for the processes influenced by the input xUpdateConfig are affected (0 = no automatic update, > 0 cyclical update)
tTimeUpdateStates
TIME
T#500ms
Update interval for the processes influenced by the input xUpdateStates are affected (0 = no automatic update, > 0 cyclical update)
tTimeUpdateInfo
TIME
T#0s
Update interval for the processes influenced by the input xUpdateInfo are affected (0 = no automatic update, > 0 cyclical update)
eDI1OutpMode
BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE
BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE.RAW
Operating mode of the output xDI1 (RAW, PULSE)
tTimeDIPulse
TIME
T#1s
Duration of the pulse at the output xDI1, if a rising edge is detected at the digital input (eDI1OutpMode = BELIMO_P_22RTX_1U00X_2_FULL_DIGITAL_INPUT_OUTP_MODE.PULSE)
eFanStageControlMode
BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE
BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE.AUTOMATIC_STAGES_CONTROL
31
Definition of the operating mode for controlling the fan stages
xVisuPresence
BOOL
FALSE
Actuation of the presence button in the visualization (affects the output xButtonPresence)
tTimeButtonPulse
TIME
T#1s
Duration of the pulse at output ‘xButton Presence’
Additional setpoints / parameters FULL
rTempOffset
REAL
+/- 15.0 K
0.0
110
Offset of the room temperature (for calibration of the temperature sensor) in K
rHumidityOffset
REAL
+/- 20.0 %
0.0
111
Offset of the room humidity (for calibration of the humidity sensor) in percent
rCO2Offset
REAL
+/- 500 ppm
0.0
112
Offset of the CO2 sensor (for calibration of the CO2 sensor) in ppm
rCO2_LED_ThresholdGreenYellow
REAL
600.0 - 1249.0 ppm, integer values only
1000.0
115
Threshold for changing the LED color from green to yellow
rCO2_LED_ThresholdYellowRed
REAL
1250.0 - 2000.0 ppm, integer values only
1500.0
116
Threshold for changing the LED color from yellow to red
xCO2_LED_Enable
BOOL
TRUE
117
Enable / disable the CO2 LED (TRUE = enable)
eTemperatureUnit
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE.DEGREES_CELSIUS
120
Definition of the unit for the temperature (influenced by: rTemp (address 1), rDewPointTemp (address 5) and rSetpTemp (address 34))
eTemperatureUnitDisplay
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE_DISPLAY
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE_DISPLAY.DEGREES_CELSIUS
121
Definition of the unit for the temperature display on the display (influences: display)
eOffsetUnit
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE.DEGREES_CELSIUS
122
Definition of the unit for the relative set temperature (influences: rSetpTempRel (address 36))
eColorScheme
BELIMO_P_22RTX_1U00X_2_COLOR_SCHEME
BELIMO_P_22RTX_1U00X_2_COLOR_SCHEME.WHITE_BACKGROUND
130
Definition of the display color scheme
eDsplIconsHeatCool
BELIMO_P_22RTX_1U00X_2_SYMBOL_VISIBILITY
BELIMO_P_22RTX_1U00X_2_SYMBOL_VISIBILITY.INVISIBLE
134
Display of the visibility of the icons for heating and cooling operation
eWarningIconFunct
BELIMO_P_22RTX_1U00X_2_WARNING_ICON_FUNCTION
BELIMO_P_22RTX_1U00X_2_WARNING_ICON_FUNCTION.DEVICE_ERROR_STATUS
135
Definition of the function of the icon Warning
eWindowIconFunct
BELIMO_P_22RTX_1U00X_2_WINDOW_ICON_FUNCTION
BELIMO_P_22RTX_1U00X_2_WINDOW_ICON_FUNCTION.INPUT_xDsplIconWind
136
Definition of the function of the icon Window
eEcoBoostOnOffIconMode
BELIMO_P_22RTX_1U00X_2_ICON_MODE
BELIMO_P_22RTX_1U00X_2_ICON_MODE.PRESENCE_BUTTON
139 - 141
Central definition of the functions of the icons Eco, Boost and OnOff
tBoostModeDuration
TIME
T#900s
142
Duration of the operating mode Boost
eSetpTempMode
BELIMO_P_22RTX_1U00X_2_SETP_TEMP_MODE
BELIMO_P_22RTX_1U00X_2_SETP_TEMP_MODE.ABSOLUTE_SETPOINT
145
Definition of the operating mode of the setpoint display (absolute / relative)
rAdjCenterSetpTempAbs
REAL
+15.0 … +35.0 degrees Celsius
22.0
146
Definition of the absolute base setpoint temperature (center value) for adjusting the setpoint temperature (+15.00 - 35.00 degrees Celsius) (automatic, internal conversion to other temperature units in the RBG) Affects the absolute setpoint temperature.
rAdjOffsetSetpTempAbs
REAL
-5.0 … +5.0 Kelvin
3.0
147
Definition of the adjustment range around the absolute base setpoint temperature (midpoint) (+/- 5.0 K) (automatic, internal conversion to other temperature units in the RBG). Affects the adjustment ranges of the absolute and relative setpoint temperature
eFanLevelConfig
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL_CONFIG
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL_CONFIG.SEVEN_STAGES
148
Definition of the number of fan stages
eFanControlMode
BELIMO_P_22RTX_1U00X_2_FAN_CONTROL_MODE
BELIMO_P_22RTX_1U00X_2_FAN_CONTROL_MODE.MANUAL_MODE_ONLY
1498
Definition of the operating mode for controlling the fan
Function description
General
This function block controls room operating devices of the P-22RT..-1U00..-2 device series from Belimo via Modbus communication. Configuration (addresses 110 - 149) is carried out in the function block with index _FULL internal, in the function block with the index _EASY external.
Operating modes - room operating device (address 30) — outputs eOperationMode and xModeDev
eOperationMode and xModeDevFour operating modes are distinguished:
0: Off/Protection (xModeDev = FALSE) 1: On/Comfort (xModeDev = TRUE) 2: Eco Mode (xModeDev = TRUE) 3: Boost Mode (xModeDev = TRUE)
Operating modes 2 and 3 can only be selected in addition to operating mode 1. Operating mode 3 is active for a limited time and requires approval of the highest fan stage for correct operation. The operating modes are automatically determined depending on the operating method (see below).
Central definition of the functions of the icons / operating elements OnOff, Eco and Boost (operating methods)
OnOff, Eco and Boost (operating methods)A total of four operating methods are distinguished, which are defined via addresses 139 - 141: (FULL: parameter eEcoBoostOnOffIconMode, EASY: define contents of addresses 139 - 141 externally according to the following list.)
Operating method INVISIBLE
Eco: NO
Eco: NO
Icons not visible or operable
Boost: NO
Boost: NO
Icons not visible or operable
OnOff: NO
OnOff: NO
Icons not visible or operable
Operating method DISPLAY_MODE
Eco: YES
Eco: NO
Display of the Eco and OnOff modes
Boost: NO
Boost: NO
Display of the Eco and OnOff modes
OnOff: YES
OnOff: NO
Display of the Eco and OnOff modes
Operating method OPERATION_MODE
Eco: YES
Eco: YES
Switching of the functions on the RBG as well as by rising edges at the icon inputs
Boost: YES
Boost: YES
Switching of the functions on the RBG as well as by rising edges at the icon inputs
OnOff: YES
OnOff: YES
Switching of the functions on the RBG as well as by rising edges at the icon inputs
Operating method PRESENCE_BUTTON
Eco: NO
Eco: NO
Extension of occupancy time with external HVAC.Button1 - FB
Boost: NO
Boost: NO
Extension of occupancy time with external HVAC.Button1 - FB
OnOff: YES
OnOff: YES
Extension of occupancy time with external HVAC.Button1 - FB
In DISPLAY mode, the operating modes Eco Mode and On/Comfort are defined by the inputs xEcoIcon and xMode (TRUE = On). If none of the inputs is active, operating mode Off/Protection is automatically selected.
In OPERATION mode, the operating modes ECO, Boost and OnOff are defined by the associated inputs (rising edges) and by operation at the room operating device.
In PRESENCE_BUTTON mode, the operating modes Off/Protection and On/Comfort are defined by the input xMode (rising edges: On / Comfort, falling edge: Off/Protection) and in parallel by operation at the room operating device. Each change from night mode to day mode and vice versa, triggered by the room operating device, generates a pulse of duration xButtonPresence at the output tTimeButtonPulse .
Day operation / night operation (output xModeDev)
xModeDev)At output xModeDev the current state of day operation at the room operating device is shown (TRUE = day operation).
Room setpoint temperatures
The room setpoint temperatures are defined in different ways depending on the parameter eSetpTempMode (address 145):
Absolute setpoint (e.g. +23.5 degrees Celsius) (index
Abs) (inputsrSetpTempAbsNight,rSetpTempAbsBaseDay) (outputrSetpTempAbs)Relative setpoint (e.g. +1.0 Kelvin) (index
Rel) (inputsrSetpTempRelNight,rSetpTempRelBaseDay) (outputrSetpTempRel)
Changes to the assigned inputs are transferred immediately in the corresponding state, otherwise at the next transition into this state. Example: A change at input rSetpTempAbsNight is transferred immediately and becomes effective in night operation. Example: A change at input rSetpTempBaseDay does not take effect immediately in night operation, but only at the next transition to day operation.
Changes to the parameters rAdjCenterSetpTempAbs (address 146) or rAdjOffsetSetpTempAbs (address 147) are transferred immediately in the appropriate mState, otherwise delayed. (FULL). Changes to addresses 146 or 147 are captured after the configuration is read again and transferred accordingly (EASY). Changes to the content of address 146 affect only the absolute setpoint temperature, changes to the content of address 147 affect the absolute and relative setpoint temperature.
The current values at the inputs rSetpTempAbsNight and rSetpTempAbsBaseDay must be specified depending on the parameter eTemperatureUnit (address 120). At output output rSetpTempAbs the current setpoint value is then available in the selected unit. The current values at the inputs rSetpTempRelNight and rSetpTempRelBaseDay must be specified depending on the parameter eOffsetUnit (address 122). At output output rSetpTempRel the current setpoint value is then available in the selected unit.
Night operation - room setpoint temperature
When switching from day operation to night operation, the state at input rSetpTempAbsNight is transferred to the room operating device and displayed there (eSetpTempMode = absolute setpoint temperature). When switching from day operation to night operation, the state at input rSetpTempRelNight is transferred to the room operating device and displayed there (eSetpTempMode = relative setpoint temperature). Any change of state at input rSetpTempXXXNight is transferred to the room operating device during night operation.
Day operation - room setpoint temperature
Case 1 - There is not yet a valid room setpoint temperature in day operation
When switching from night operation to day operation, the state at input rSetpTempAbsBaseDay transferred to the room operating device and displayed there. Adjustment is possible on the room operating device in the symmetrical range defined by address 147. The increment is 0.5 K.
Case 2 - A valid room setpoint temperature in day operation already exists
When switching from night mode to day mode, the previous valid room setpoint temperature is transferred to the room operating device and displayed there. Adjustment is possible on the room operating device in the symmetrical range defined by address 147. The increment is 0.5 K.
Output xDI1
xDI1At output xDI1 the state at input DI1 of the room operating device is available in different ways (parameter xDI1OutpMode).
Operating modes
RAW
The output immediately adopts the state at input DI1 (FALSE: contact open, TRUE: contact closed with +24VDC)
PULSE
Each rising edge at input DI1 triggers a pulse of duration at the corresponding output xDI1 tTimeDIPulse (default: 1s).
Specification / display of fan level
The preselection of the number of fan stages is done via parameter eFanLevelConfig (address 148). In Boost Mode, the maximum fan stage is specified (independent of input eSetpFanLevel). The fan stage is selected and transmitted via input eSetpFanLevel within the permitted limits. The current fan stage is output via output eFanLevel within the permitted limits. The display of the current fan stage and the setting options is additionally defined by the parameters eFanStagesControlMode (address 31) eFanControlMode (address 149), eFanLevelConfig (address 148) and xDsplFanStages (address 138).
Evaluation of the current CO2 content using a multicolor LED
The evaluation of the current CO2 content is performed using a multicolor LED (off / green / yellow / red) and the output eCO2Status . The threshold for changing the LED color from green to yellow is defined by the parameter rCO2_LED_ThresholdwGreenYellow (address 115). The threshold for changing the LED color from yellow to red is defined by the parameter rCO2_LED_ThresholdYellowRed (address 116). The evaluation and the LED display can be defined by the parameter xCO2_LED_Enable (address 117) (TRUE = display).
Display of symbols / actual values
The display of the desired symbols in the room operating device display is triggered by the TRUE state of the assigned inputs. These inputs are marked with the index Dspl . Example: xDsplTemp = TRUE causes the current room temperature to be displayed on the screen.
Display of faults
Faults are displayed at the collective output xAlarm (= TRUE). It includes communication faults (time delay: gc_Parameters.gc_tOnDelayxAlarmCom, default = 60s) and device faults (direct). Here, the collective fault message, the collective warning message and the excessive CO2 content (LED = red) are output as device fault. At output eErrorCodeCom in the event of a communication error, an explanatory text for the cause is available. The cause of the last communication error is always displayed there.
Codesys
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
Input
byUnitId
BYTE
0
Device address (1 .. 247) (via Belimo Assistant app using NFC)
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints (on every rising edge )
Input
xUpdateConfig
BOOL
FALSE
Update of the configuration (on every rising edge) (read access)
Input
xUpdateStates
BOOL
FALSE
Update of the states (on each rising edge)
Input
xUpdateInfo
BOOL
FALSE
Update of the information (on every rising edge)
Input
rSetpTempAbsNight
REAL
18.0
Absolute set temperature - night operation (unit depending on eTemperatureUnit)
Input
rSetpTempAbsBaseDay
REAL
22.0
Absolute base set temperature - day operation (unit depending on eTemperatureUnit)
Input
rSetpTempRelNight
REAL
0.0
Relative set temperature - night operation (unit depending on eTemperatureUnit)
Input
rSetpTempRelBaseDay
REAL
0.0
Relative base set temperature - day operation (unit depending on eTemperatureUnit)
Input
xMode
BOOL
FALSE
Display of the icon OnOff (eOnOffIconMode =
BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.DISPLAY_MODE)
Input
xEcoIcon
BOOL
FALSE
Display of the icon Eco (eEcoIconMode =
BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.DISPLAY_MODE)
Input
xBoostIcon
BOOL
FALSE
Operation of the icon Boost (eBoostIconMode =
BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.OPERATION_MODE)
Input
eSetpFanLevel
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL.STAGE_0
(each rising edge switches the boost mode)
Setpoint - Current fan stage depending on the parameter eFanLevelConfig
Depending on the parameters eFanStagesControlMode (Register 31 - Setpoints_0) and eFanControlMode (Register 149 - Configuration_0), the following operating options are available:
Register 31 = Automatic // Register 149 = Hybrid:
If level 0 is selected on the RBG, the display of the current level is deactivated and an automatic symbol is shown.
If a level greater than 0 is selected on the RBG, the display of the current level is activated and the automatic symbol is hidden.
The level selection is possible on the RBG and via register 22.
In all other configurations the following applies:
The display of the current level is active, it can be changed on the RBG and via register 22, the last change made remains in effect.
Input
eIconsHeatCool
BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL
BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL.NONE
0.0 = Level 0 1.0 = Level 1 2.0 = Level 2 3.0 = Level 3 4.0 = Level 4 5.0 = Level 5 6.0 = Level 6 Selection of heating or cooling mode
Input
xDsplIconWarn
BOOL
FALSE
Display of the symbol Warning (TRUE = display)
Input
xDsplIconWind
BOOL
FALSE
Display of the symbol Window (TRUE = display)
Input
xEnLocalAdj
BOOL
TRUE
Definition whether local operation is possible (TRUE = enable)
Input
xResError
BOOL
FALSE
Reinitialization of the output eErrorCodeCom (with every
rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
eOperationMode
BELIMO_P_22RTX_1U00X_2_OPERATION_MODE
Current operating mode 0 = OFF_PROTECTION: night operation 1 = ON_COMFORT: day operation 2 = ECO_MODE: day operation — eco operation 3 = BOOST_MODE: day operation — boost operation
Output
eEcoBoostOnOffIconMode
BELIMO_P_22RTX_1U00X_2_ICON_MODE
Central definition of the functions of the icons Eco, Boost and OnOff
INVISIBLE (icons not visible and not operable)
> Visibility operability on the RBG
Eco: no no
Boost: no no
OnOff: no no
DISPLAY_MODE (display of Eco and OnOff modes)
> Visibility operability on the RBG
Eco: yes no
Boost: no no
OnOff: yes no
OPERATION_MODE (switching the functions on the RBG as well as by rising edges at the icon inputs)
> Visibility operability on the RBG
Eco: yes yes
Boost: yes yes
OnOff: yes yes
PRESENCE_BUTTON (extended occupancy time with external HVAC.Button1 - FB)
> Visibility operability on the RBG
Eco: no no
Boost: no no
OnOff: yes yes
Address 139 Address 140 Address 141 Operating mode
0 0 0 INVISIBLE
1 0 1 DISPLAY_MODE
2 1 2 OPERATION_MODE
0 0 2 PRESENCE_BUTTON
Output
xModeDev
BOOL
Operating mode of the zone control from the device (FALSE = night operation, TRUE = day operation)
Output
xButtonPresence
BOOL
Pressing the presence button (pulse with duration
tTimeButtonPulse) (RBG and/or VISU)
Output
rSetpTempAbs
REAL
Current absolute setpoint temperature depending on the
parameter eTemperatureUnit (e.g. +23.5 degrees Celsius) (
Register 34)
Output
rOffset
REAL
Current difference between rSetpTempAbs and
rAdjCenterSetpTemp (range: +/- rAdjOffsetSetpTemp) in day mode
Output
rSetpTempRel
REAL
Current relative setpoint temperature depending on the
parameter eOffsetUnit (e.g. -2.0 Kelvin) (range: +/-
rAdjOffsetSetpTemp) (register 36)
Output
rTemp
REAL
Current room temperature depending on the parameter
eUnitTemperature
Output
rRelHumidity
REAL
Relative room humidity in percent
Output
rCO2
REAL
Current CO2 concentration in ppm
Output
eCO2Status
BELIMO_P_22RTX_1U00X_2_CO2_STATUS
Current status of the CO2 actual value monitoring
Output
xSensorOffsetInDevice
BOOL
Indication of whether the sensors must be calibrated in the device (TRUE = calibration in the device required, FALSE = calibration in the FB required)
Output
rDewPointTemp
REAL
Dew point temperature in degrees Celsius or Fahrenheit
Output
eFanLevel
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL
Current fan level depending on the parameter
eFanLevelConfig
Output
xDI1
BOOL
Status of digital input 1 depending on the
parameter eDI1OutpMode:
Output
xEnLocalAdjFb
BOOL
Display whether local operation is possible (TRUE = local operation possible) — feedback
Output
eBusTermin
BELIMO_P_22RTX_1U00X_2_BUS_TERMINATION
State of the Modbus termination resistor (Active = Enabled)
Output
sSerialNum
STRING
Device serial number
Output
wFirmwareVer
WORD
Firmware version of the device
Output
xAlarm
BOOL
FALSE
Collective fault (TRUE = fault)
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication (TRUE = fault)
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
Output
xBusy
BOOL
Communication indicator (TRUE = communication)
Input Const
tTimeButtonPulse
TIME
TIME#1s0ms
Duration of the pulse at output ‘xButton Presence’
Input Const
xVisuPresence
BOOL
FALSE
Pressing the presence button in the visualization
Input Const
eFanStageControlMode
BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE
BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE.AUTOMATIC_STAGES_CONTROL
Definition of the operating mode for controlling the stages of the fan
Input Const
tTimeDIPulse
TIME
TIME#1s0ms
Duration of the pulse at the output xDI1, if a rising
edge is detected at the digital input (
eDI1OutpMode =
BELIMO_P_22RTX_1U00X_2_FULL_DIGITAL_INPUT_OUTP_MODE.PULSE)
Input Const
eDI1OutpMode
BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE
BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE.RAW
Operating mode of the output xDI1 (RAW, PULSE)
Input Const
tTimeUpdateInfo
TIME
TIME#0ms
Update interval for the processes influenced by the input
xUpdateInfo influenced
Input Const
tTimeUpdateStates
TIME
TIME#500ms
Update interval for the processes influenced by the input
xUpdateStates influenced
Input Const
tTimeUpdateConfig
TIME
TIME#0ms
Update interval for the processes influenced by the input
xUpdateConfig influenced
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the processes influenced by the input
xUpdateSetp influenced
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes influenced by the input
xUpdateActual influenced
Last updated

