BELIMO_P_22RTX_1U00X_2_EASY
BELIMO_P_22RTX_1U00X_2_EASY (FB)
BELIMO_P_22RTX_1U00X_2_EASY (FB)FUNCTION_BLOCK BELIMO_P_22RTX_1U00X_2_EASY
Representation

Short description
Control of the device series P-22RT..-1U00..-2 from Belimo Typical application: Room operating unit in a zone\
Guidelines - Software creation
Supported Modbus - Function Codes: 2, 3, 4, 6 and 16. For addressing use the address specifications, not the register addresses. Registers from 111 are persistent in the device and must not be written cyclically. Unused registers contain the value 65535 (unsigned) (FFFF - hex) or -1 (signed). Unused registers within the defined ranges may be read/written. In the constellation ‘eEcoBoostOnOffIconMode = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.OPERATION_MODE’ the ECO mode switches to On/Comfort mode on the first rising edge at the input ‘xBoostIcon’. On the second rising edge the BOOST mode is then activated. When operated at the room control unit the switch from ECO to BOOST happens immediately. Workaround: Write address 30 with FC06 !!! with the desired value, do not write address 22 at the same time. Measured values - Adjustment: Class 4\
Interfaces
Inputs
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
byUnitId
BYTE
0
Device address (0 .. 255)
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge)
xUpdateSetp
BOOL
FALSE
Update of setpoints (on every rising edge)
xUpdateConfig
BOOL
FALSE
Updating the configuration (on every rising edge) (read access)
xUpdateStates
BOOL
FALSE
Update of states (on every rising edge)
xUpdateInfo
BOOL
FALSE
Updating the information (on every rising edge)
rSetpTempAbsNight
REAL
18.0
Absolute room setpoint temperature in night mode (unit depends on register address 122)
rSetpTempAbsBaseDay
REAL
22.0
Absolute base room setpoint temperature in day mode (unit depends on register address 120)
rSetpTempRelNight
REAL
0.0
Relative room setpoint temperature in night mode (unit depends on register address 122)
rSetpTempRelBaseDay
REAL
0.0
Relative base room setpoint temperature in day mode (unit depends on register address 122)
xMode
BOOL
FALSE
Input for the operating mode / the On/Off icon (function depending on register addresses 139 - 141)
xEcoIcon
BOOL
FALSE
Input for the operating mode / the Eco icon (function depending on register addresses 139 - 141)
xBoostIcon
BOOL
FALSE
Input for the operating mode / the Boost icon (function depending on register addresses 139 - 141)
eSetpFanLevel
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL.STAGE_0
Target fan level
eIconsHeatCool
BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL
BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL.NONE
Selection of the display of the icon for heating or cooling operation
xDsplIconWarn
BOOL
FALSE
Input for displaying the warning icon (TRUE = enabled)
xDsplIconWind
BOOL
FALSE
Input for displaying the window icon (TRUE = enabled)
xEnLocalAdj
BOOL
FALSE
Input for displaying the controls at the room control unit (TRUE = display)
xResError
BOOL
FALSE
Input for resetting the output ‘eErrorCodeCom’ (on every rising edge)
Outputs
eOperationMode
BELIMO_P_22RTX_1U00X_2_OPERATION_MODE
Display of the current operating mode on the room operating unit (register address 30)
eEcoBoostOnOffIconMode
BELIMO_P_22RTX_1U00X_2_ICON_MODE
Display of the current operating mode
xModeDev
BOOL
Operating mode of the zone control on the room operating unit (FALSE = night operation, TRUE = day operation)
xButtonPresence
BOOL
Actuation of the presence button (pulse with duration ‘tTimeButtonPulse’) (ROU and/or VISU)
rSetpTempAbs
REAL
Current absolute setpoint temperature depending on the parameter ‘eTemperatureUnit’ (e.g. +23.5 degrees Celsius) (register address 34) (unit depends on register address 120)
rOffset
REAL
Current difference between ‘rSetpTempAbs’ and ‘rAdjCenterSetpTemp’ (range: +/- ‘rAdjOffsetSetpTemp’) in day operation (unit depends on register address 120)
rSetpTempRel
REAL
Current relative setpoint temperature depending on the parameter ‘eOffsetUnit’ (e.g. -2.0 Kelvin) (range: +/- ‘rAdjOffsetSetpTemp’) (register address 36) (unit depends on register address 122)
rTemp
REAL
Room temperature (unit depends on register address 120)
rRelHumidity
REAL
Relative room humidity in percent
rCO2
REAL
CO2 concentration (ppm)
eCO2Status
BELIMO_P_22RTX_1U00X_2_CO2_STATUS
Current status of the CO2 measured-value monitoring
xSensorOffsetInDevice
BOOL
Indicates whether sensor calibration must be performed in the device (TRUE = calibration required in device, FALSE = calibration required in FB)
rDewPointTemp
REAL
Dew point temperature (unit depends on register address 120 in degrees Celsius or Fahrenheit)
eFanLevel
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL
Current fan level depending on the parameter ‘eFanLevelConfig’ (register address 22)
xDI1
BOOL
State of digital input 1 depending on the parameter ‘eDI1OutpMode’ (RAW: FALSE = open, TRUE = closed with +24VDC, PULSE: pulse with duration ‘tTimeDIPulse’ at each rising edge on input DI1)
xEnLocalAdjFb
BOOL
Indication whether local operation is possible (TRUE = local operation possible) — feedback
eBusTermin
BELIMO_P_22RTX_1U00X_2_BUS_TERMINATION
State of the Modbus termination resistor (Active = Enabled)
sSerialNum
STRING
Device serial number
wFirmwareVer
WORD
Firmware version of the device
xAlarmCom
BOOL
Collective fault - communication ( TRUE = Fault )
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
eErrorCodeDev
SPLUSS_ERROR_CODE_TYPE_2
Error code - device (0 = no error)
xBusy
BOOL
Communication indicator ( TRUE = Communication )
Inputs and outputs
ModbusClient
ModbusClientBase
Client of the device
General information about setpoints / parameters (addresses 110 - 149)
The following setpoints / parameters (addresses 110 - 149) apply jointly for the function blocks with the index ‘_EASY’ and ‘_FULL’. In the function block with the index ‘_FULL’ additional setpoints / parameters can be defined, which are shown in the table after next. These additional setpoints / parameters are only read and stored in internal variables in the function block with the index ‘_EASY’. The specification of these setpoints / parameters is done externally there, e.g. using the app ‘Belimo Assistant’.\
Setpoints / Parameters EASY / FULL
tTimeUpdateActual
TIME
T#3s
Update interval for processes influenced by the input ‘xUpdateActual’ (0 = no automatic update, > 0 cyclic update)
tTimeUpdateSetp
TIME
T#0s
Update interval for processes influenced by the input ‘xUpdateSetp’ (0 = no automatic update, > 0 cyclic update)
tTimeUpdateConfig
TIME
T#0s
Update interval for the processes affected by the input ‘xUpdateConfig’ (0 = no automatic update, > 0 cyclic update)
tTimeUpdateStates
TIME
T#500ms
Update interval for processes influenced by the input ‘xUpdateStates’ (0 = no automatic update, > 0 cyclic update)
tTimeUpdateInfo
TIME
T#0s
Update interval for processes influenced by the input ‘xUpdateInfo’ (0 = no automatic update, > 0 cyclic update)
eDI1OutpMode
BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE
BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE.RAW
Operating mode of the output ‘xDI1’ (RAW, PULSE)
tTimeDIPulse
TIME
T#1s
Duration of the pulse at output ‘xDI1’ if a rising edge is detected at the digital input (‘eDI1OutpMode’ = BELIMO_P_22RTX_1U00X_2_FULL_DIGITAL_INPUT_OUTP_MODE.PULSE)
eFanStageControlMode
BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE
BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE.AUTOMATIC_STAGES_CONTROL
31
Definition of the operating mode of the control of the fan stages
xVisuPresence
BOOL
FALSE
Actuation of the presence button in the visualization (affects the output ‘xButtonPresence’)
tTimeButtonPulse
TIME
T#1s
Duration of the pulse at output ‘xButton Presence’
Additional setpoints / parameters FULL
rTempOffset
REAL
+/- 15.0 K
0.0
110
Offset of the room temperature (for calibration of the temperature sensor) in K
rHumidityOffset
REAL
+/- 20.0 %
0.0
111
Offset of the room humidity (for calibration of the humidity sensor) in percent
rCO2Offset
REAL
+/- 500 ppm
0.0
112
Offset of the CO2 sensor (for calibration of the CO2 sensor) in ppm
rCO2_LED_ThresholdGreenYellow
REAL
600.0 - 1249.0 ppm, integer values only
1000.0
115
Threshold for changing the LED color from green to yellow
rCO2_LED_ThresholdYellowRed
REAL
1250.0 - 2000.0 ppm, integer values only
1500.0
116
Threshold for changing the LED color from yellow to red
xCO2_LED_Enable
BOOL
TRUE
117
Enable/disable of the CO2 LED (TRUE = enabled)
eTemperatureUnit
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE.DEGREES_CELSIUS
120
Definition of the unit for temperature (affects: ‘rTemp’ (address 1), ‘rDewPointTemp’ (address 5) and ‘rSetpTemp’ (address 34))
eTemperatureUnitDisplay
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE_DISPLAY
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE_DISPLAY.DEGREES_CELSIUS
121
Definition of the unit for the temperature display on the display (affects: Display)
eOffsetUnit
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE
BELIMO_P_22RTX_1U00X_2_UNIT_TEMPERATURE.DEGREES_CELSIUS
122
Definition of the unit for the relative set temperature (affects: ‘rSetpTempRel’ (address 36))
eColorScheme
BELIMO_P_22RTX_1U00X_2_COLOR_SCHEME
BELIMO_P_22RTX_1U00X_2_COLOR_SCHEME.WHITE_BACKGROUND
130
Definition of the display color scheme
eDsplIconsHeatCool
BELIMO_P_22RTX_1U00X_2_SYMBOL_VISIBILITY
BELIMO_P_22RTX_1U00X_2_SYMBOL_VISIBILITY.INVISIBLE
134
Display of the visibility of the icons for heating and cooling operation
eWarningIconFunct
BELIMO_P_22RTX_1U00X_2_WARNING_ICON_FUNCTION
BELIMO_P_22RTX_1U00X_2_WARNING_ICON_FUNCTION.DEVICE_ERROR_STATUS
135
Definition of the function of the 'Warning' icon
eWindowIconFunct
BELIMO_P_22RTX_1U00X_2_WINDOW_ICON_FUNCTION
BELIMO_P_22RTX_1U00X_2_WINDOW_ICON_FUNCTION.INPUT_xDsplIconWind
136
Definition of the function of the 'Window' icon
eEcoBoostOnOffIconMode
BELIMO_P_22RTX_1U00X_2_ICON_MODE
BELIMO_P_22RTX_1U00X_2_ICON_MODE.PRESENCE_BUTTON
139 - 141
Central definition of the functions of the icons ‘Eco’, ‘Boost’ and ‘OnOff’
tBoostModeDuration
TIME
T#900s
142
Duration of the 'Boost' operating mode
eSetpTempMode
BELIMO_P_22RTX_1U00X_2_SETP_TEMP_MODE
BELIMO_P_22RTX_1U00X_2_SETP_TEMP_MODE.ABSOLUTE_SETPOINT
145
Definition of the operating mode of the setpoint display (absolute / relative)
rAdjCenterSetpTempAbs
REAL
+15.0 … +35.0 degrees Celsius
22.0
146
Definition of the absolute base setpoint temperature (center value) for the adjustment of the setpoint temperature (+15.00 - 35.00 degrees Celsius) (automatic, internal conversion to other temperature units in the RBG). Influences the absolute setpoint temperature.
rAdjOffsetSetpTempAbs
REAL
-5.0 … +5.0 Kelvin
3.0
147
Definition of the adjustment range around the absolute base setpoint (center value) (+/- 5.0 K) (automatic internal conversion to other temperature units in the ROU). Affects the adjustment ranges of the absolute and the relative setpoint
eFanLevelConfig
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL_CONFIG
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL_CONFIG.SEVEN_STAGES
148
Definition of the number of fan stages
eFanControlMode
BELIMO_P_22RTX_1U00X_2_FAN_CONTROL_MODE
BELIMO_P_22RTX_1U00X_2_FAN_CONTROL_MODE.MANUAL_MODE_ONLY
1498
Definition of the operating mode of the fan control
Function description
General
This function block controls room control units of the device series P-22RT..-1U00..-2 from Belimo via Modbus communication. The configuration (addresses 110 - 149) is done internally in the function block with the index ‘_FULL’, externally in the function block with the index ‘_EASY’.\
Operating modes - Room operating unit (address 30) — Outputs ‘eOperationMode’ and ‘xModeDev’
Four operating modes are distinguished: 0: Off/Protection (‘xModeDev’ = FALSE) 1: On/Comfort (‘xModeDev’ = TRUE) 2: Eco Mode (‘xModeDev’ = TRUE) 3: Boost Mode (‘xModeDev’ = TRUE) Operating modes 2 and 3 can only be selected additionally to operating mode 1. Operating mode 3 is active for a limited time and requires enabling of the highest fan stage for correct function. The operating modes are set automatically depending on the operating method (see below). \
Central definition of the functions of the icons / controls ‘OnOff’, ‘Eco’ and ‘Boost’ (operating methods)
A total of four operating modes are distinguished, which are defined via addresses 139 - 141: (FULL: parameter ‘eEcoBoostOnOffIconMode’, EASY: contents of addresses 139 - 141 to be specified externally according to the following list.) \
Operating method INVISIBLE
Eco: NO
Eco: NO
Icons not visible and not operable
Boost: NO
Boost: NO
Icons not visible and not operable
OnOff: NO
OnOff: NO
Icons not visible and not operable
Operating method DISPLAY_MODE
Eco: YES
Eco: NO
Display of the Eco and OnOff modes
Boost: NO
Boost: NO
Display of the Eco and OnOff modes
OnOff: YES
OnOff: NO
Display of the Eco and OnOff modes
Operating method OPERATION_MODE
Eco: YES
Eco: YES
Switching of the functions at the ROU as well as by rising edges at the icon inputs
Boost: YES
Boost: YES
Switching of the functions at the ROU as well as by rising edges at the icon inputs
OnOff: YES
OnOff: YES
Switching of the functions at the ROU as well as by rising edges at the icon inputs
Operating method PRESENCE_BUTTON
Eco: NO
Eco: NO
Occupancy time extension with external HVAC.Button1 function block
Boost: NO
Boost: NO
Occupancy time extension with external HVAC.Button1 function block
OnOff: YES
OnOff: YES
Occupancy time extension with external HVAC.Button1 function block
In DISPLAY mode the operating modes Eco Mode and On/Comfort are determined by the inputs ‘xEcoIcon’ and ‘xMode’ (TRUE = On). If none of the inputs is active, Off/Protection operating mode is automatically selected. In OPERATION mode the operating modes ECO, Boost and OnOff are determined by the associated inputs (rising edges) and by the operation at the room control unit. In PRESENCE-BUTTON mode the operating modes Off/Protection and On/Comfort are determined by the input ‘xMode’ (rising edges: On / Comfort, falling edge: Off/Protection) and in parallel by the operation at the room control unit. On every change from night to day mode and vice versa, which was triggered by the room control unit, an impulse with the duration ‘tTimeButtonPulse’ is generated at the output ‘xButtonPresence’. \
Day operation / Night operation (output ‘xModeDev’)
The output ‘xModeDev’ indicates the current state of day operation on the room operating unit (TRUE = day operation).\
Room setpoint temperatures
Room setpoint temperatures are defined in different ways depending on the parameter ‘eSetpTempMode’ (address 145): \
Absolute setpoint (e.g. +23.5 degrees Celsius) (index ‘Abs’) (inputs ‘rSetpTempAbsNight’, ‘rSetpTempAbsBaseDay’) (output ‘rSetpTempAbs’)\
Relative setpoint (e.g. +1.0 Kelvin) (index ‘Rel’) (inputs ‘rSetpTempRelNight’, ‘rSetpTempRelBaseDay’) (output ‘rSetpTempRel’)\
Changes to the assigned inputs are transferred immediately in the respective state, otherwise on the next transition into that state. Example: A change at the input ‘rSetpTempAbsNight’ is transferred and effective immediately in night mode. Example: A change at the input ‘rSetpTempBaseDay’ is not effective in night mode, but only on the next transition into day mode. Changes to the parameters ‘rAdjCenterSetpTempAbs’ (address 146) or ‘rAdjOffsetSetpTempAbs’ (address 147) are transferred immediately in the suitable mState, otherwise delayed. (FULL). Changes to addresses 146 or 147 are recorded and transferred after re-reading the configuration (EASY). Changes to the content of address 146 only affect the absolute setpoint temperature, changes to the content of address 147 affect the absolute and relative setpoint temperature. The current values at the inputs ‘rSetpTempAbsNight’ and ‘rSetpTempAbsBaseDay’ must be specified depending on the parameter ‘eTemperatureUnit’ (address 120). The current setpoint is then available at the output ‘rSetpTempAbs’ in the chosen unit. The current values at the inputs ‘rSetpTempRelNight’ and ‘rSetpTempRelBaseDay’ must be specified depending on the parameter ‘eOffsetUnit’ (address 122). The current setpoint is then available at the output ‘rSetpTempRel’ in the chosen unit. Night mode - room setpoint temperature When switching from day mode to night mode the state at the input ‘rSetpTempAbsNight’ is transferred to the room control unit and displayed there (‘eSetpTempMode’ = absolute setpoint temperature). When switching from day mode to night mode the state at the input ‘rSetpTempRelNight’ is transferred to the room control unit and displayed there (‘eSetpTempMode’ = relative setpoint temperature). Any change of the state at the input ‘rSetpTempXXXNight’ is transferred to the room control unit during night mode. Day mode - room setpoint temperature Case 1 - There is not yet a valid room setpoint temperature in day mode When switching from night mode to day mode the state at the input ‘rSetpTempAbsBaseDay’ is transferred to the room control unit and displayed there. At the room control unit an adjustment within the symmetric range defined by address 147 is possible. The step size is 0.5K. Case 2 - There is already a valid room setpoint temperature in day mode When switching from night mode to day mode the previously valid room setpoint temperature is transferred to the room control unit and displayed there. At the room control unit an adjustment within the symmetric range defined by address 147 is possible. The step size is 0.5K.\
Output ‘xDI1’
At the output ‘xDI1’ the state at the input DI1 of the room operating unit is available in different ways (parameter ‘xDI1OutpMode’). Operating modes RAW The output immediately adopts the state at input DI1 (FALSE: contact open, TRUE: contact closed with +24VDC) PULSE Each rising edge at input DI1 triggers a pulse of duration ‘tTimeDIPulse’ (default: 1s) at the corresponding output xDI1. \
Preset / display of the fan stage
The preselection of the number of fan stages is done via the parameter ‘eFanLevelConfig’ (address 148). In Boost Mode the maximum fan stage (independent of the input ‘eSetpFanLevel’) is applied. The fan stage is selected and transmitted via the input ‘eSetpFanLevel’ within the permitted limits. The current fan stage is output via the output ‘eFanLevel’ within the permitted limits. The representation of the current fan stage and the adjustment options are additionally defined by the parameters ‘eFanStagesControlMode’ (address 31) ‘eFanControlMode’ (address 149), ‘eFanLevelConfig’ (address 148) and ‘xDsplFanStages’ (address 138).\
Assessment of the current CO2 level using a multicolored LED
The assessment of the current CO2 level is done using a multicolored LED (off / green / yellow / red) and the output ‘eCO2Status’. The threshold for the transition of the LED color from green to yellow is set by parameter ‘rCO2_LED_ThresholdwGreenYellow’ (address 115). The threshold for the transition of the LED color from yellow to red is set by parameter ‘rCO2_LED_ThresholdYellowRed’ (address 116). The assessment and the LED display can be defined by parameter ‘xCO2_LED_Enable’ (address 117) (TRUE = display).\
Display of symbols / measured values
The display of the desired symbols on the room operating unit display is triggered by the TRUE state of the assigned inputs. These inputs are marked with the index ‘Dspl’. Example: xDsplTemp = TRUE causes the current room temperature to be displayed on the display.\
Display of faults
Faults are indicated at the collective output ‘xAlarm’ ( = TRUE ). It includes communication faults (time delay: gc_Parameters.gc_tOnDelayxAlarmCom, default = 60s) and device faults (direct). Here the collective error message, the collective warning message and excessive CO2 level (LED = red) are output as device fault. At the output ‘eErrorCodeCom’ an explanatory text for the cause is available in case of a communication error. It always shows the cause of the last communication error.
Codesys
InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Device address (1 .. 247) (via Belimo Assistant - App via NFC)
Input
xUpdateActual
BOOL
FALSE
Update of actual values ( on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoint values ( on every rising edge )
Input
xUpdateConfig
BOOL
FALSE
Update of the configuration ( on each rising edge ) ( read access )
Input
xUpdateStates
BOOL
FALSE
Updating of states (on every rising edge )
Input
xUpdateInfo
BOOL
FALSE
Update of information (on every rising edge)
Input
rSetpTempAbsNight
REAL
18.0
Absolute set temperature - night operation (unit depending on ‘eTemperatureUnit’)
Input
rSetpTempAbsBaseDay
REAL
22.0
Absolute base set temperature - day operation (unit depending on ‘eTemperatureUnit’)
Input
rSetpTempRelNight
REAL
0.0
Relative set temperature - night operation (unit depending on ‘eTemperatureUnit’)
Input
rSetpTempRelBaseDay
REAL
0.0
Relative base set temperature - day operation (unit depending on ‘eTemperatureUnit’)
Input
xMode
BOOL
FALSE
Display of the ‘OnOff’ icon (‘eOnOffIconMode’ = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.DISPLAY_MODE )
Input
xEcoIcon
BOOL
FALSE
Display of the 'Eco' icon (‘eEcoIconMode’ = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.DISPLAY_MODE)
Input
xBoostIcon
BOOL
FALSE
Operation of the 'Boost' icon (‘eBoostIconMode’ = BELIMO_P_22RTX_1U00X_2_FULL_ICON_MODE.OPERATION_MODE)
Input
eSetpFanLevel
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL.STAGE_0
(each rising edge toggles the Boost mode) Setpoint - Current fan stage depending on the parameter ‘eFanLevelConfig’ Depending on the parameters ‘eFanStagesControlMode’ (Register 31 - Setpoints_0) and ‘eFanControlMode’ (Register 149 - Configuration_0) the following operation options are available: Register 31 = Automatic // Register 149 = Hybrid: If stage 0 is selected at the RBG, the display of the current stage is deactivated and an automatic symbol is shown. If a stage greater than 0 is selected at the RBG, the display of the current stage is activated and the automatic symbol is hidden. Stage selection is possible at the RBG and via register 22. In all other constellations the following applies: The display of the current stage is active, it can be changed at the RBG and via register 22, the last change remains in effect.
Input
eIconsHeatCool
BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL
BELIMO_P_22RTX_1U00X_2_MODE_HEAT_COOL.NONE
0.0 = Stage 0 1.0 = Stage 1 2.0 = Stage 2 3.0 = Stage 3 4.0 = Stage 4 5.0 = Stage 5 6.0 = Stage 6 Selection of heating or cooling operation
Input
xDsplIconWarn
BOOL
FALSE
Display of the 'Warning' symbol (TRUE = display)
Input
xDsplIconWind
BOOL
FALSE
Display of the 'Window' symbol (TRUE = display)
Input
xEnLocalAdj
BOOL
TRUE
Definition of whether local operation is possible (TRUE = enabled)
Input
xResError
BOOL
FALSE
Reinitialization of the output 'eErrorCodeCom' ( on each rising edge )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
eOperationMode
BELIMO_P_22RTX_1U00X_2_OPERATION_MODE
Current operating mode 0 = OFF_PROTECTION: Night operation 1 = ON_COMFORT: Day operation 2 = ECO_MODE: Day operation — Eco mode 3 = BOOST_MODE: Day operation — Boost mode
Output
eEcoBoostOnOffIconMode
BELIMO_P_22RTX_1U00X_2_ICON_MODE
Central definition of the functions of the icons ‘Eco’, ‘Boost’ and ‘OnOff’ INVISIBLE (icons not visible and not operable) > Visibility Operability at RBG Eco: no no Boost: no no OnOff: no no DISPLAY_MODE (display of Eco and OnOff modes) > Visibility Operability at RBG Eco: yes no Boost: no no OnOff: yes no OPERATION_MODE (switching of functions at the RBG as well as by rising edges at the icon inputs) > Visibility Operability at RBG Eco: yes yes Boost: yes yes OnOff: yes yes PRESENCE_BUTTON (occupancy extension with external HVAC.Button1 - FB) > Visibility Operability at RBG Eco: no no Boost: no no OnOff: yes yes Address 139 Address 140 Address 141 Operating mode 0 0 0 INVISIBLE 1 0 1 DISPLAY_MODE 2 1 2 OPERATION_MODE 0 0 2 PRESENCE_BUTTON
Output
xModeDev
BOOL
Operating mode of the zone control from the device (FALSE = night operation, TRUE = day operation)
Output
xButtonPresence
BOOL
Actuation of the presence button (pulse with duration ‘tTimeButtonPulse’) (ROU and/or VISU)
Output
rSetpTempAbs
REAL
Current absolute setpoint temperature depending on the parameter ‘eTemperatureUnit’ (e.g. +23.5 degrees Celsius) ( register 34)
Output
rOffset
REAL
Current difference between ‘rSetpTempAbs’ and ‘rAdjCenterSetpTemp’ (range: +/- ‘rAdjOffsetSetpTemp’) in day mode
Output
rSetpTempRel
REAL
Current relative setpoint temperature depending on the parameter ‘eOffsetUnit’ (e.g. -2.0 Kelvin) (range: +/- ‘rAdjOffsetSetpTemp’) (register 36)
Output
rTemp
REAL
Current room temperature depending on the parameter ‘eUnitTemperature’
Output
rRelHumidity
REAL
Relative room humidity in percent
Output
rCO2
REAL
Current CO2 concentration in ppm
Output
eCO2Status
BELIMO_P_22RTX_1U00X_2_CO2_STATUS
Current status of the CO2 measured-value monitoring
Output
xSensorOffsetInDevice
BOOL
Indicates whether the sensor calibration must be performed in the device ( TRUE = calibration required in device, FALSE = calibration required in FB )
Output
rDewPointTemp
REAL
Dew point temperature in degrees Celsius or Fahrenheit
Output
eFanLevel
BELIMO_P_22RTX_1U00X_2_FAN_LEVEL
Current fan stage depending on the parameter ‘eFanLevelConfig’
Output
xDI1
BOOL
State of digital input 1 depending on the parameter ‘eDI1OutpMode’:
Output
xEnLocalAdjFb
BOOL
Indication whether local operation is possible (TRUE = local operation possible) — feedback
Output
eBusTermin
BELIMO_P_22RTX_1U00X_2_BUS_TERMINATION
State of the Modbus termination resistor (Active = Enabled)
Output
sSerialNum
STRING
Device serial number
Output
wFirmwareVer
WORD
Firmware version of the device
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = Fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = Fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
xBusy
BOOL
Communication indicator ( TRUE = Communication )
Input Const
tTimeButtonPulse
TIME
TIME#1s0ms
Duration of the pulse at output ‘xButton Presence’
Input Const
xVisuPresence
BOOL
FALSE
Actuation of the presence button in the visualization
Input Const
eFanStageControlMode
BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE
BELIMO_P_22RTX_1U00X_2_FAN_STAGES_CONTROL_MODE.AUTOMATIC_STAGES_CONTROL
Definition of the operating mode of the control of the fan stages
Input Const
tTimeDIPulse
TIME
TIME#1s0ms
Duration of the pulse at output ‘xDI1’ if a rising edge is detected at the digital input ( ‘eDI1OutpMode’ = BELIMO_P_22RTX_1U00X_2_FULL_DIGITAL_INPUT_OUTP_MODE.PULSE )
Input Const
eDI1OutpMode
BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE
BELIMO_P_22RTX_1U00X_2_DIGITAL_INPUT_OUTP_MODE.RAW
Operating mode of the output ‘xDI1’ (RAW, PULSE)
Input Const
tTimeUpdateInfo
TIME
TIME#0ms
Update interval for operations affected by the input 'xUpdateInfo'
Input Const
tTimeUpdateStates
TIME
TIME#500ms
Update interval for the operations influenced by the input ‘xUpdateStates’
Input Const
tTimeUpdateConfig
TIME
TIME#0ms
Update interval for operations affected by the input 'xUpdateConfig'
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the operations influenced by the input ‘xUpdateSetp’
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the operations influenced by the input ‘xUpdateActual’
Last updated

