BELIMO_LMV_D3
BELIMO_LMV_D3 (FB)
BELIMO_LMV_D3 (FB)FUNCTION_BLOCK BELIMO_LMV_D3
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Address of the device
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoint values (on every rising edge )
Input
xResError
BOOL
FALSE
Reinitialization of the outputs ‘eErrorCodeCom’ and/or ‘stErrorCodeDev’ to the no-error state (on every rising edge)
Input
rSetpVolFlowPerc
REAL
0.0
Setpoint - volumetric flow in % (0.0 - 100.0 %) (0.0 % = Vmin, 100.0 % = Vmax)
Input
xEnDevice
BOOL
FALSE
Enable / disable of the volumetric flow controller (FALSE = forced control CLOSED, TRUE = forced control NONE)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rVminUnit
REAL
Minimum value - volumetric flow in the selected volumetric flow unit
Output
rVmaxUnit
REAL
Maximum value - volumetric flow in the selected volumetric flow unit
Output
rVnomUnit
REAL
Nominal volumetric flow in the selected volumetric flow unit
Output
rDamperPosPerc
REAL
Absolute position of the damper in percent (0.0% = Closed, 100.0% = Open)
Output
rDamperPosDegree
REAL
Absolute position of the damper in degrees
Output
rVolFlowPerc
REAL
Actual value of the volumetric flow in percent of the nominal volumetric flow
Output
rVolFlowUnit
REAL
Actual value of the volumetric flow in the selected volumetric flow unit
Output
rSetpVolFlowPercFb
REAL
Feedback of the setpoint - volumetric flow in % (0.0 - 100.0 % ) (0.0 % = Vmin, 100.0 % = Vmax)
Output
eCommandFb
BELIMO_LMV_D3_COMMAND
Feedback of the triggering of test functions (0 = none)
Output
eOverrideConFb
BELIMO_LMV_D3_OVERRIDE_CON
Feedback of the forced override of the damper (0 = none)
Output
eActuatorType
BELIMO_LMV_D3_ACTUATOR_TYPE
Type of the actuator
Output
eVolumeFlowUnitFb
BELIMO_LMV_D3_VOLUMEFLOW_UNIT
Feedback of the unit for the absolute volumetric flow values (1 = m3/h)
Output
eSetpSourceFb
BELIMO_LMV_D3_SETP_SOURCE
Feedback of the source for the setpoint (0 = Analog, 1 = Bus)
Output
eBusTermin
BELIMO_LMV_D3_BUS_TERMINATION
Status of the Modbus termination resistor ( 1 = Active )
Output
eSensorTypeFb
BELIMO_LMV_D3_SENSOR_TYPE
Feedback of the type of the connected sensor (0 = none )
Output
sSerialNum
STRING
Device serial number
Output
wFirmwareVer
WORD
Firmware version of the device
Output
rSensorValue
REAL
Current actual value of the sensor in mV
Output
rSetpAnalog
REAL
Setpoint in XXX.X % (0.0 - 100.0 %) based on the sensor
Output
xAlarm
BOOL
FALSE
General fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
General fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
stErrorCodeDev
STRING
String with the numbers of the active device errors
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
rSensorValueOffset
REAL
0.0
Constant measurement offset for the transmitted voltage actual value
Input Const
eSensorType
BELIMO_LMV_D3_SENSOR_TYPE
BELIMO_LMV_D3_SENSOR_TYPE.NO_SENSOR
Influence: Outputs: rSensorValue Type of the connected sensor (0 = none)
Input Const
eSetpSource
BELIMO_LMV_D3_SETP_SOURCE
BELIMO_LMV_D3_SETP_SOURCE.BUS
Source for the setpoint (0 = Analog, 1 = Bus)
Input Const
eControlMode
BELIMO_LMV_D3_CONTROL_MODE
BELIMO_LMV_D3_CONTROL_MODE.CLOSED_LOOP
Type of control / regulation (0 = Open Loop = position control, 1 = Closed Loop = volumetric flow control)
Input Const
eCommand
BELIMO_LMV_D3_COMMAND
BELIMO_LMV_D3_COMMAND.NO_COMMAND
Triggering of test functions (0 = none)
Input Const
eVolumeFlowUnit
BELIMO_LMV_D3_VOLUMEFLOW_UNIT
BELIMO_LMV_D3_VOLUMEFLOW_UNIT.M3_PER_H
Unit for the absolute volumetric flow values (1 = m3/h)
Input Const
xSetpVolumeFlowMinMax
BOOL
FALSE
Triggering the transmission of the parameters ‘rSetpVolumeFlowMin’ and ‘rSetpVolumeFlowMax’ (on every rising edge)
Input Const
rSetpVolumeFlowMax
REAL
180.0
Setpoint for the maximum volumetric flow in the selected volumetric flow unit (when rSetpVolFlowPerc = 100.0 %)
Input Const
rSetpVolumeFlowMin
REAL
0.0
Setpoint for the minimum volumetric flow in the selected volumetric flow unit (when rSetpVolFlowPerc = 0.0 %)
Input Const
tTimeOut
TIME
TIME#10s0ms
Time duration for the activation of the state ‘Communication failure’ (t = 0s = disabled, for t > 0s ( at least 10 s) the parameter ‘rSetpVolFlowPerc’ must be transmitted cyclically with a time interval < t )
Input Const
eBusFailureCommand
BELIMO_LMV_D3_BUS_FAILURE
BELIMO_LMV_D3_BUS_FAILURE.LAST_SETPOINT
Definition of the behavior in case of a bus failure (0 = last setpoint)
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for operations influenced by the input 'xUpdateSetp'
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for operations influenced by the input 'xUpdateActual'
Last updated

