POWERIO_T1_R310

POWERIO_T1_R310 (FB)

FUNCTION_BLOCK POWERIO_T1_R310

Representation

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enabled)

Input

byUnitId

BYTE

0

Address of the device

Input

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge )

Input

xUpdateStates

BOOL

FALSE

Update of the states ( on every rising edge )

Input

xUpdateSetp

BOOL

FALSE

Update of setpoints (on every rising edge )

Input

xResError

BOOL

FALSE

Reinitialization of the outputs ‘eErrorCodeCom’ and ‘xErrorCodeDev’ to the error-free state (on each rising edge)

Input

xDO1

BOOL

FALSE

Setting the state of digital output 1 (FET) (FALSE = Off)

Input

xDO2

BOOL

FALSE

Setting the state of digital output 2 (FET) (FALSE = Off)

Input

xDO3

BOOL

FALSE

Setting the state of digital output 3 (FET) (FALSE = Off)

Input

xDO4

BOOL

FALSE

Setting the state of digital output 4 (FET) (FALSE = Off)

Input

xDO5

BOOL

FALSE

Setting the state of digital output 5 (FET) (FALSE = Off)

Input

xDO6

BOOL

FALSE

Setting the state of digital output 6 (FET) (FALSE = Off)

Input

xDO7

BOOL

FALSE

Setting the state of digital output 7 (FET) (FALSE = Off)

Input

xDO8

BOOL

FALSE

Setting the state of digital output 8 (FET) (FALSE = Off)

Input

xDO9

BOOL

FALSE

Setting the state of digital output 9 (FET) ( FALSE = Off )

Input

xDO10

BOOL

FALSE

Setting the state of digital output 10 (FET) ( FALSE = Off )

Input

xDO11

BOOL

FALSE

Setting the state of digital output 11 (FET) ( FALSE = Off )

Input

xDO12

BOOL

FALSE

Setting the state of digital output 12 (FET) ( FALSE = Off )

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

xDI1

BOOL

State of digital input DI1 (FALSE = Off)

Output

xDI2

BOOL

State of digital input DI2 (FALSE = Off)

Output

xDO1_Fb

BOOL

State of digital output DO1 (FALSE = Off)

Output

xDO2_Fb

BOOL

State of digital output DO2 (FALSE = Off)

Output

xDO3_Fb

BOOL

State of digital output DO3 (FALSE = Off)

Output

xDO4_Fb

BOOL

State of digital output DO4 (FALSE = Off)

Output

xDO5_Fb

BOOL

State of digital output DO5 (FALSE = Off)

Output

xDO6_Fb

BOOL

State of digital output DO6 (FALSE = Off)

Output

xDO7_Fb

BOOL

State of digital output DO7 (FALSE = Off)

Output

xDO8_Fb

BOOL

State of digital output DO8 (FALSE = Off)

Output

xDO9_Fb

BOOL

State of digital output DO9 (FALSE = Off )

Output

xDO10_Fb

BOOL

State of digital output D10 (FALSE = Off )

Output

xDO11_Fb

BOOL

State of digital output D11 (FALSE = Off )

Output

xDO12_Fb

BOOL

State of digital output D12 (FALSE = Off )

Output

eAOO_DO1

eManBin

State of manual override on digital output DO1

Output

eAOO_DO2

eManBin

State of manual override on digital output DO2

Output

eAOO_DO3

eManBin

State of manual override on digital output DO3

Output

eAOO_DO4

eManBin

State of manual override on digital output DO4

Output

eAOO_DO5

eManBin

State of manual override on digital output DO5

Output

eAOO_DO6

eManBin

State of manual override on digital output DO6

Output

eAOO_DO7

eManBin

State of manual override on digital output DO7

Output

eAOO_DO8

eManBin

State of manual override on digital output DO8

Output

eAOO_DO9

eManBin

State of manual override on digital output DO9

Output

eAOO_DO10

eManBin

State of manual override on digital output DO10

Output

eAOO_DO11

eManBin

State of manual override on digital output DO11

Output

eAOO_DO12

eManBin

State of manual override on digital output DO12

Output

rAI1_PT1000

REAL

Actual temperature value at analog input 1 (PT1000) (-30.0°C = short circuit / open circuit)

Output

xAlarm_AI1_PT1000

BOOL

FALSE

Fault - short circuit / open circuit of analog input 1 (PT1000) (TRUE = Fault)

Output

rAI2_PT1000

REAL

Actual temperature value at analog input 2 (PT1000) (-30.0°C = short circuit / open circuit)

Output

xAlarm_AI2_PT1000

BOOL

FALSE

Fault - short circuit / open circuit of analog input 2 (PT1000) (TRUE = Fault)

Output

xSensorOffsetInDevice

BOOL

Indicates whether sensor calibration must be performed in the device ( TRUE = calibration required in the device, FALSE = calibration required in the FB )

Output

wTypeID

WORD

Device identification

Output

wFirmwareVer

WORD

Firmware version of the device

Output

xAlarm

BOOL

FALSE

Collective fault (TRUE = fault)

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication (TRUE = fault)

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

Output

eErrorCodeDev

POWERIO_T1_R310_ERROR_CODE

POWERIO_T1_R310_ERROR_CODE.NO_ERROR

Error code - device (0 = no error)

Output

xBusy

BOOL

Communication indicator (TRUE = communication)

Input Const

rAI2_PT1000Offset

REAL

0.0

Constant measurement offset for the transmitted resistance - Actual value 2

Input Const

rAI1_PT1000Offset

REAL

0.0

Constant measurement offset for the transmitted resistance - Actual value 1

Input Const

xDO12_SafeState_Sta

BOOL

FALSE

State of digital output 12 in safe state operation (FALSE = Off )

Input Const

xDO11_SafeState_Sta

BOOL

FALSE

State of digital output 11 in safe state operation (FALSE = Off )

Input Const

xDO10_SafeState_Sta

BOOL

FALSE

State of digital output 10 in safe state operation (FALSE = Off )

Input Const

xDO9_SafeState_Sta

BOOL

FALSE

State of digital output 9 in safe state operation (FALSE = Off )

Input Const

xDO8_SafeState_Sta

BOOL

FALSE

State of digital output 8 in safestate operation (FALSE = Off)

Input Const

xDO7_SafeState_Sta

BOOL

FALSE

State of digital output 7 in safestate operation (FALSE = Off)

Input Const

xDO6_SafeState_Sta

BOOL

FALSE

State of digital output 6 in safestate operation (FALSE = Off)

Input Const

xDO5_SafeState_Sta

BOOL

FALSE

State of digital output 5 in safestate operation (FALSE = Off)

Input Const

xDO4_SafeState_Sta

BOOL

FALSE

State of digital output 4 in safestate operation (FALSE = Off)

Input Const

xDO3_SafeState_Sta

BOOL

FALSE

State of digital output 3 in safestate operation (FALSE = Off)

Input Const

xDO2_SafeState_Sta

BOOL

FALSE

State of digital output 2 in safestate operation (FALSE = Off)

Input Const

xDO1_SafeState_Sta

BOOL

FALSE

State of digital output 1 in safestate operation (FALSE = Off)

Input Const

xDO12_SafeState_En

BOOL

FALSE

Enable / disable digital output 12 for safe state operation (TRUE = Enable )

Input Const

xDO11_SafeState_En

BOOL

FALSE

Enable / disable digital output 11 for safe state operation (TRUE = Enable )

Input Const

xDO10_SafeState_En

BOOL

FALSE

Enable / disable digital output 10 for safe state operation (TRUE = Enable )

Input Const

xDO9_SafeState_En

BOOL

FALSE

Enable / disable digital output 9 for safe state- operation (TRUE = Enable )

Input Const

xDO8_SafeState_En

BOOL

FALSE

Enable/disable digital output 8 for safestate operation (TRUE = Enabled)

Input Const

xDO7_SafeState_En

BOOL

FALSE

Enable/disable digital output 7 for safestate operation (TRUE = Enabled)

Input Const

xDO6_SafeState_En

BOOL

FALSE

Enable/disable digital output 6 for safestate operation (TRUE = Enabled)

Input Const

xDO5_SafeState_En

BOOL

FALSE

Enable/disable digital output 5 for safestate operation (TRUE = Enabled)

Input Const

xDO4_SafeState_En

BOOL

FALSE

Enable/disable digital output 4 for safestate operation (TRUE = Enabled)

Input Const

xDO3_SafeState_En

BOOL

FALSE

Enable/disable digital output 3 for safestate operation (TRUE = Enabled)

Input Const

xDO2_SafeState_En

BOOL

FALSE

Enable/disable digital output 2 for safestate operation (TRUE = Enabled)

Input Const

xDO1_SafeState_En

BOOL

FALSE

Enable/disable digital output 1 for safestate operation (TRUE = Enabled)

Input Const

tTimeSafeState

TIME

TIME#0ms

Duration for activation of the ‘Safestate’ condition on communication failure (integer multiples of 1s)

Input Const

tTimeUpdateStates

TIME

TIME#500ms

Update interval for the processes influenced by the input ‘xUpdateStates’

Input Const

tTimeMinChangeValue

TIME

TIME#0ms

Minimum time duration before transmitting a setpoint due to a detected value change

Input Const

tTimeUpdateSetp

TIME

TIME#45s0ms

Update interval for the operations affected by the input 'xUpdateSetp'

Input Const

tTimeUpdateActual

TIME

TIME#3s0ms

Update interval for the operations affected by the input 'xUpdateActual'

Last updated