POWERIO_T1_R300
POWERIO_T1_R300 (FB)
POWERIO_T1_R300 (FB)FUNCTION_BLOCK POWERIO_T1_R300
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Address of the device
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
xUpdateStates
BOOL
FALSE
Update of the states ( on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoint values (on every rising edge )
Input
xResError
BOOL
FALSE
Reinitialization of the outputs 'eErrorCodeCom' and 'xErrorCodeDev' to the error-free state (on each rising edge)
Input
xDO1
BOOL
FALSE
Set the state of digital output 1 (FET) ( FALSE = Off )
Input
xDO2
BOOL
FALSE
Set the state of digital output 2 (FET) ( FALSE = Off )
Input
xDO3
BOOL
FALSE
Set the state of digital output 3 (FET) ( FALSE = Off )
Input
xDO4
BOOL
FALSE
Set the state of digital output 4 (FET) ( FALSE = Off )
Input
xDO5
BOOL
FALSE
Set the state of digital output 5 (FET) ( FALSE = Off )
Input
xDO6
BOOL
FALSE
Set the state of digital output 6 (FET) ( FALSE = Off )
Input
xDO7
BOOL
FALSE
Set the state of digital output 7 (FET) ( FALSE = Off )
Input
xDO8
BOOL
FALSE
Set the state of digital output 8 (FET) ( FALSE = Off )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
xDI1
BOOL
State of digital input DI1 ( FALSE = Off )
Output
xDI2
BOOL
State of digital input DI2 ( FALSE = Off )
Output
xDO1_Fb
BOOL
State of digital output DO1 ( FALSE = Off )
Output
xDO2_Fb
BOOL
State of digital output DO2 ( FALSE = Off )
Output
xDO3_Fb
BOOL
State of digital output DO3 ( FALSE = Off )
Output
xDO4_Fb
BOOL
State of digital output DO4 ( FALSE = Off )
Output
xDO5_Fb
BOOL
State of digital output DO5 ( FALSE = Off )
Output
xDO6_Fb
BOOL
State of digital output DO6 ( FALSE = Off )
Output
xDO7_Fb
BOOL
State of digital output DO7 ( FALSE = Off )
Output
xDO8_Fb
BOOL
State of digital output DO8 ( FALSE = Off )
Output
xStateDevGreen
BOOL
State of the status LED green ( TRUE = On )
Output
xStateDevRed
BOOL
State of the status LED red ( TRUE = On )
Output
rAI1_PT1000
REAL
Actual temperature value at analog input 1 (PT1000) ( -30.0°C = short circuit / open circuit )
Output
xAlarm_AI1_PT1000
BOOL
FALSE
Fault - short circuit / open circuit of analog input 1 ( PT1000) ( TRUE = Fault )
Output
rAI2_PT1000
REAL
Actual temperature value at analog input 2 (PT1000) ( -30.0°C = short circuit / open circuit )
Output
xAlarm_AI2_PT1000
BOOL
FALSE
Fault - short circuit / open circuit of analog input 2 ( PT1000) ( TRUE = Fault )
Output
xSensorOffsetInDevice
BOOL
Indicator whether the calibration of the sensors must be performed in the device (TRUE = calibration in device required, FALSE = calibration in FB required)
Output
wTypeID
WORD
Identification of the device
Output
wFirmwareVer
WORD
Firmware version of the device
Output
xAlarm
BOOL
FALSE
General fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
General fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
eErrorCodeDev
POWERIO_T1_R300_ERROR_CODE
POWERIO_T1_R300_ERROR_CODE.NO_ERROR
Error code - device (0 = no error)
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
rAI2_PT1000Offset
REAL
0.0
Constant measurement offset for the transmitted resistance - Actual value 2
Input Const
rAI1_PT1000Offset
REAL
0.0
Constant measurement offset for the transmitted resistance - Actual value 1
Input Const
xDO8_SafeState_Sta
BOOL
FALSE
State of digital output 8 in safestate operation ( FALSE = Off )
Input Const
xDO7_SafeState_Sta
BOOL
FALSE
State of digital output 7 in safestate operation ( FALSE = Off )
Input Const
xDO6_SafeState_Sta
BOOL
FALSE
State of digital output 6 in safestate operation ( FALSE = Off )
Input Const
xDO5_SafeState_Sta
BOOL
FALSE
State of digital output 5 in safestate operation ( FALSE = Off )
Input Const
xDO4_SafeState_Sta
BOOL
FALSE
State of digital output 4 in safestate operation ( FALSE = Off )
Input Const
xDO3_SafeState_Sta
BOOL
FALSE
State of digital output 3 in safestate operation ( FALSE = Off )
Input Const
xDO2_SafeState_Sta
BOOL
FALSE
State of digital output 2 in safestate operation ( FALSE = Off )
Input Const
xDO1_SafeState_Sta
BOOL
FALSE
State of digital output 1 in safestate operation ( FALSE = Off )
Input Const
xDO8_SafeState_En
BOOL
FALSE
Enable / disable digital output 8 for safestate operation ( TRUE = Enabled )
Input Const
xDO7_SafeState_En
BOOL
FALSE
Enable / disable digital output 7 for safestate operation ( TRUE = Enabled )
Input Const
xDO6_SafeState_En
BOOL
FALSE
Enable / disable digital output 6 for safestate operation ( TRUE = Enabled )
Input Const
xDO5_SafeState_En
BOOL
FALSE
Enable / disable digital output 5 for safestate operation ( TRUE = Enabled )
Input Const
xDO4_SafeState_En
BOOL
FALSE
Enable / disable digital output 4 for safestate operation ( TRUE = Enabled )
Input Const
xDO3_SafeState_En
BOOL
FALSE
Enable / disable digital output 3 for safestate operation ( TRUE = Enabled )
Input Const
xDO2_SafeState_En
BOOL
FALSE
Enable / disable digital output 2 for safestate operation ( TRUE = Enabled )
Input Const
xDO1_SafeState_En
BOOL
FALSE
Enable / disable digital output 1 for safestate operation ( TRUE = Enabled )
Input Const
tTimeSafeState
TIME
TIME#0ms
Duration for activation of the 'safestate' condition in case of communication loss (integer multiples of 1s )
Input Const
tTimeUpdateStates
TIME
TIME#500ms
Update interval for the processes influenced by the input ‘xUpdateStates’
Input Const
tTimeMinChangeValue
TIME
TIME#0ms
Minimum duration before transmitting a setpoint due to a detected value change
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for operations influenced by the input 'xUpdateSetp'
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for operations influenced by the input 'xUpdateActual'