POWERIO_T1_R300
POWERIO_T1_R300 (FB)
POWERIO_T1_R300 (FB)FUNCTION_BLOCK POWERIO_T1_R300
Representation

InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
Input
byUnitId
BYTE
0
Device address
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
xUpdateStates
BOOL
FALSE
Update of the states (on each rising edge)
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints (on every rising edge )
Input
xResError
BOOL
FALSE
Reinitialization of the outputs eErrorCodeCom or
xErrorCodeDev to the fault-free state (on every rising edge)
Input
xDO1
BOOL
FALSE
Definition of the state of digital output 1 (FET) ( FALSE = Off)
Input
xDO2
BOOL
FALSE
Definition of the state of digital output 2 (FET) ( FALSE = Off)
Input
xDO3
BOOL
FALSE
Definition of the state of digital output 3 (FET) ( FALSE = Off)
Input
xDO4
BOOL
FALSE
Definition of the state of digital output 4 (FET) ( FALSE = Off)
Input
xDO5
BOOL
FALSE
Definition of the state of digital output 5 (FET) ( FALSE = Off)
Input
xDO6
BOOL
FALSE
Definition of the state of digital output 6 (FET) ( FALSE = Off)
Input
xDO7
BOOL
FALSE
Definition of the state of digital output 7 (FET) ( FALSE = Off)
Input
xDO8
BOOL
FALSE
Definition of the state of digital output 8 (FET) ( FALSE = Off)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
xDI1
BOOL
State of digital input DI1 (FALSE = Off)
Output
xDI2
BOOL
State of digital input DI2 (FALSE = Off)
Output
xDO1_Fb
BOOL
State of digital output DO1 (FALSE = Off)
Output
xDO2_Fb
BOOL
State of digital output DO2 (FALSE = Off)
Output
xDO3_Fb
BOOL
State of digital output DO3 (FALSE = Off)
Output
xDO4_Fb
BOOL
State of digital output DO4 (FALSE = Off)
Output
xDO5_Fb
BOOL
State of digital output DO5 (FALSE = Off)
Output
xDO6_Fb
BOOL
State of digital output DO6 (FALSE = Off)
Output
xDO7_Fb
BOOL
State of digital output DO7 (FALSE = Off)
Output
xDO8_Fb
BOOL
State of digital output DO8 (FALSE = Off)
Output
xStateDevGreen
BOOL
State of status LED green (TRUE = On)
Output
xStateDevRed
BOOL
State of status LED red (TRUE = On)
Output
rAI1_PT1000
REAL
Actual temperature value at analog input 1 (PT1000) ( -30.0°C = short circuit / interruption)
Output
xAlarm_AI1_PT1000
BOOL
FALSE
Fault - short circuit / interruption of analog input 1 ( PT1000) (TRUE = fault)
Output
rAI2_PT1000
REAL
Actual temperature value at analog input 2 (PT1000) ( -30.0°C = short circuit / interruption)
Output
xAlarm_AI2_PT1000
BOOL
FALSE
Fault - short circuit / interruption of analog input 2 ( PT1000) (TRUE = fault)
Output
xSensorOffsetInDevice
BOOL
Indication of whether the sensors must be calibrated in the device (TRUE = calibration in the device required, FALSE = calibration in the FB required)
Output
wTypeID
WORD
Device identification
Output
wFirmwareVer
WORD
Firmware version of the device
Output
xAlarm
BOOL
FALSE
Collective fault (TRUE = fault)
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication (TRUE = fault)
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
Output
eErrorCodeDev
POWERIO_T1_R300_ERROR_CODE
POWERIO_T1_R300_ERROR_CODE.NO_ERROR
Error code - device (0 = no error)
Output
xBusy
BOOL
Communication indicator (TRUE = communication)
Input Const
rAI2_PT1000Offset
REAL
0.0
Constant measured value offset for the transmitted resistance - actual value 2
Input Const
rAI1_PT1000Offset
REAL
0.0
Constant measured value offset for the transmitted resistance - actual value 1
Input Const
xDO8_SafeState_Sta
BOOL
FALSE
State of digital output 8 in safe state mode (FALSE = Off)
Input Const
xDO7_SafeState_Sta
BOOL
FALSE
State of digital output 7 in safe state mode (FALSE = Off)
Input Const
xDO6_SafeState_Sta
BOOL
FALSE
State of digital output 6 in safe state mode (FALSE = Off)
Input Const
xDO5_SafeState_Sta
BOOL
FALSE
State of digital output 5 in safe state mode (FALSE = Off)
Input Const
xDO4_SafeState_Sta
BOOL
FALSE
State of digital output 4 in safe state mode (FALSE = Off)
Input Const
xDO3_SafeState_Sta
BOOL
FALSE
State of digital output 3 in safe state mode (FALSE = Off)
Input Const
xDO2_SafeState_Sta
BOOL
FALSE
State of digital output 2 in safe state mode (FALSE = Off)
Input Const
xDO1_SafeState_Sta
BOOL
FALSE
State of digital output 1 in safe state mode (FALSE = Off)
Input Const
xDO8_SafeState_En
BOOL
FALSE
Enable / lock digital output 8 for safe state mode (TRUE = enable)
Input Const
xDO7_SafeState_En
BOOL
FALSE
Enable / lock digital output 7 for safe state mode (TRUE = enable)
Input Const
xDO6_SafeState_En
BOOL
FALSE
Enable / lock digital output 6 for safe state mode (TRUE = enable)
Input Const
xDO5_SafeState_En
BOOL
FALSE
Enable / lock digital output 5 for safe state mode (TRUE = enable)
Input Const
xDO4_SafeState_En
BOOL
FALSE
Enable / lock digital output 4 for safe state mode (TRUE = enable)
Input Const
xDO3_SafeState_En
BOOL
FALSE
Enable / lock digital output 3 for safe state mode (TRUE = enable)
Input Const
xDO2_SafeState_En
BOOL
FALSE
Enable / lock digital output 2 for safe state mode (TRUE = enable)
Input Const
xDO1_SafeState_En
BOOL
FALSE
Enable / lock digital output 1 for safe state mode (TRUE = enable)
Input Const
tTimeSafeState
TIME
TIME#0ms
Duration for activation of the state Safestate in the event of
communication failure (integer multiples of 1s)
Input Const
tTimeUpdateStates
TIME
TIME#500ms
Update interval for the processes influenced by the input
xUpdateStates influenced
Input Const
tTimeMinChangeValue
TIME
TIME#0ms
Minimum time before transmitting a setpoint based on a detected value change
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the processes influenced by the input
xUpdateSetp influenced
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes influenced by the input
xUpdateActual influenced