POWERIO_T1_R100

POWERIO_T1_R100 (FB)

FUNCTION_BLOCK POWERIO_T1_R100

Representation

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enable)

Input

byUnitId

BYTE

0

Device address

Input

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge )

Input

xUpdateStates

BOOL

FALSE

Update of the states (on each rising edge)

Input

xUpdateSetp

BOOL

FALSE

Update of setpoints (on every rising edge )

Input

xResError

BOOL

FALSE

Reinitialization of the outputs eErrorCodeCom or xErrorCodeDev to the fault-free state (on every rising edge)

Input

xDO1

BOOL

FALSE

Definition of the state of digital output 1 (FET) ( FALSE = Off)

Input

xDO2

BOOL

FALSE

Definition of the state of digital output 2 (FET) ( FALSE = Off)

Input

xDO3

BOOL

FALSE

Definition of the state of digital output 3 (FET) ( FALSE = Off)

Input

xDO4

BOOL

FALSE

Definition of the state of digital output 4 (FET) ( FALSE = Off)

Input

xDO5

BOOL

FALSE

Setting the state of digital output 5 (relay) ( FALSE = Off)

Input

xDO6

BOOL

FALSE

Setting the state of digital output 6 (relay) ( FALSE = Off)

Input

xDO7

BOOL

FALSE

Setting the state of digital output 7 (relay) ( FALSE = Off)

Input

rAO1

REAL

0.0

Setting the state at analog output 1 (0.0 - 100.0% corresponding to 0.000 - 10.000 V))

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

xDI1

BOOL

State of digital input DI1 (FALSE = Off)

Output

xDI2

BOOL

State of digital input DI2 (FALSE = Off)

Output

xDI3

BOOL

State of digital input DI3 (FALSE = Off)

Output

xDI4

BOOL

State of digital input DI4 (FALSE = Off)

Output

xDI5

BOOL

State of digital input DI5 (FALSE = Off)

Output

xDI6

BOOL

State of digital input DI6 (FALSE = Off)

Output

xDO1_Fb

BOOL

State of digital output DO1 (FALSE = Off)

Output

xDO2_Fb

BOOL

State of digital output DO2 (FALSE = Off)

Output

xDO3_Fb

BOOL

State of digital output DO3 (FALSE = Off)

Output

xDO4_Fb

BOOL

State of digital output DO4 (FALSE = Off)

Output

xDO5_Fb

BOOL

State of digital output DO5 (FALSE = Off)

Output

xDO6_Fb

BOOL

State of digital output DO6 (FALSE = Off)

Output

xDO7_Fb

BOOL

State of digital output DO7 (FALSE = Off)

Output

eAOO_DO1

eManBin

State of the manual override at digital output DO1

Output

eAOO_DO2

eManBin

State of the manual override at digital output DO2

Output

eAOO_DO3

eManBin

State of the manual override at digital output DO3

Output

eAOO_DO4

eManBin

State of the manual override at digital output DO4

Output

eAOO_DO5

eManBin

State of the manual override at digital output DO5

Output

eAOO_DO6

eManBin

State of the manual override at digital output DO6

Output

eAOO_DO7

eManBin

State of the manual override at digital output DO7

Output

eAO_AO1

eManNum

State of the manual override at analog output AO1

Output

xStateDevGreen

BOOL

State of status LED green (TRUE = On)

Output

xStateDevRed

BOOL

State of status LED red (TRUE = On)

Output

rAI1

REAL

Actual value of the voltage at analog input 1 (0.0 - 10.0 V)

Output

rAI2_PT1000

REAL

Actual temperature value at analog input 2 (PT1000) ( -30.0°C = short circuit / interruption)

Output

xAlarm_AI2_PT1000

BOOL

FALSE

Fault - short circuit / interruption of analog input 2 ( PT1000) (TRUE = fault)

Output

rAI2_Resist

REAL

Actual value of the resistance at analog input 2 (XXXX Ohm)

Output

xSensorOffsetInDevice

BOOL

Indication of whether the sensors must be calibrated in the device (TRUE = calibration in the device required, FALSE = calibration in the FB required)

Output

wTypeID

WORD

Device identification

Output

wFirmwareVer

WORD

Firmware version of the device

Output

xAlarm

BOOL

FALSE

Collective fault (TRUE = fault)

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication (TRUE = fault)

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

Output

eErrorCodeDev

POWERIO_T1_R100_ERROR_CODE

POWERIO_T1_R100_ERROR_CODE.NO_ERROR

Error code - device (0 = no error)

Output

xBusy

BOOL

Communication indicator (TRUE = communication)

Input Const

rAI2_ResistOffset

REAL

0.0

Constant measurement offset for the transmitted resistance actual value

Input Const

rAI2_PT1000Offset

REAL

0.0

Constant measured-value offset for the transmitted temperature actual value

Input Const

rAO1_SafeState_Sta

REAL

0.0

State of analog output 1 in safe state mode (0.000 … +10.000 V)

Input Const

xDO7_SafeState_Sta

BOOL

FALSE

State of digital output 7 in safe state mode (FALSE = Off)

Input Const

xDO6_SafeState_Sta

BOOL

FALSE

State of digital output 6 in safe state mode (FALSE = Off)

Input Const

xDO5_SafeState_Sta

BOOL

FALSE

State of digital output 5 in safe state mode (FALSE = Off)

Input Const

xDO4_SafeState_Sta

BOOL

FALSE

State of digital output 4 in safe state mode (FALSE = Off)

Input Const

xDO3_SafeState_Sta

BOOL

FALSE

State of digital output 3 in safe state mode (FALSE = Off)

Input Const

xDO2_SafeState_Sta

BOOL

FALSE

State of digital output 2 in safe state mode (FALSE = Off)

Input Const

xDO1_SafeState_Sta

BOOL

FALSE

State of digital output 1 in safe state mode (FALSE = Off)

Input Const

xAO1_SafeState_En

BOOL

FALSE

Enable / disable analog output 1 for safe state mode (TRUE = enable)

Input Const

xDO7_SafeState_En

BOOL

FALSE

Enable / lock digital output 7 for safe state mode (TRUE = enable)

Input Const

xDO6_SafeState_En

BOOL

FALSE

Enable / lock digital output 6 for safe state mode (TRUE = enable)

Input Const

xDO5_SafeState_En

BOOL

FALSE

Enable / lock digital output 5 for safe state mode (TRUE = enable)

Input Const

xDO4_SafeState_En

BOOL

FALSE

Enable / lock digital output 4 for safe state mode (TRUE = enable)

Input Const

xDO3_SafeState_En

BOOL

FALSE

Enable / lock digital output 3 for safe state mode (TRUE = enable)

Input Const

xDO2_SafeState_En

BOOL

FALSE

Enable / lock digital output 2 for safe state mode (TRUE = enable)

Input Const

xDO1_SafeState_En

BOOL

FALSE

Enable / lock digital output 1 for safe state mode (TRUE = enable)

Input Const

tTimeSafeState

TIME

TIME#0ms

Duration for activation of the state Safestate in the event of communication failure (integer multiples of 1s, minimum 5s)

Input Const

tTimeMinChangeValue

TIME

TIME#0ms

Minimum time before transmitting a setpoint based on a detected value change

Input Const

tTimeUpdateSetp

TIME

TIME#45s0ms

Update interval for the processes influenced by the input xUpdateSetp influenced

Input Const

tTimeUpdateStates

TIME

TIME#500ms

Update interval for the processes influenced by the input xUpdateStates influenced

Input Const

tTimeUpdateActual

TIME

TIME#3s0ms

Update interval for the processes influenced by the input xUpdateActual influenced