POWERIO_T1_BSK1_XXX_EASY
POWERIO_T1_BSK1_XXX_EASY (FB)
POWERIO_T1_BSK1_XXX_EASY (FB)FUNCTION_BLOCK POWERIO_T1_BSK1_XXX_EASY
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Address of the device
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoint values (on every rising edge )
Input
xResError
BOOL
FALSE
Reinitialization of the output 'eErrorCodeCom' to the error-free state / reset of the fault status of the fire dampers (on every rising edge )
Input
xFD1
BOOL
FALSE
Set the state of the output for fire damper 1 ( FALSE = closed )
Input
xResAutoFDx
BOOL
FALSE
Switch the manual override of the outputs for the fire dampers to automatic mode (on every rising edge )
Input
xSendSysCommand
BOOL
FALSE
Activate transmission of the system command ( register 6 ) ( on every rising edge AND wSysCommand > 0 )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
xFD1_Open
BOOL
Feedback - fire damper 1 open ( TRUE = open )
Output
xFD1_Closed
BOOL
Feedback - fire damper 1 closed ( TRUE = closed )
Output
xFD1_Fb
BOOL
Feedback - state of the output of fire damper 1 ( FALSE = closed )
Output
eAOO_FD1
eManBin
State of the manual override at the output of fire damper 1
Output
xAlarm
BOOL
FALSE
General fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
General fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
stErrorCodeFD1
STRING
String with the bit numbers of the active errors of fire damper 1 ( '' = no error )
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
xDIxInversion
BOOL
FALSE
Set the inversion of the digital inputs DIx ( FALSE: no inversion // TRUE = inversion )
Input Const
wSysCommand
WORD
0
Value of the system command to be transmitted ( FC06 - register 6 ) ( 0 = no function, values > 0 see documentation T1_BSK1_XXX )
Input Const
xFD1_SafeState_Sta
BOOL
TRUE
State of the digital output for fire damper 1 in safestate operation ( TRUE = open )
Input Const
xFD1_SafeState_En
BOOL
FALSE
Enable / disable the digital output for fire damper 1 for safestate operation ( TRUE = enabled )
Input Const
tTimeSafeState
TIME
TIME#0ms
Duration for activation of the 'Safestate' condition in case of communication failure ( 0 = no timeout/safe-state function, integer multiples of 1s, minimum 5s )
Input Const
tTimeUpdateSetp
TIME
TIME#0ms
Update interval for operations influenced by the input 'xUpdateSetp'
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for operations influenced by the input 'xUpdateActual'
Last updated