POWERIO_T1_BSK1_XXX_EASY

POWERIO_T1_BSK1_XXX_EASY (FB)

FUNCTION_BLOCK POWERIO_T1_BSK1_XXX_EASY

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable communication ( TRUE = enabled )

Input

byUnitId

BYTE

0

Address of the device

Input

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge )

Input

xUpdateSetp

BOOL

FALSE

Update of setpoint values (on every rising edge )

Input

xResError

BOOL

FALSE

Reinitialization of the output 'eErrorCodeCom' to the error-free state / reset of the fault status of the fire dampers (on every rising edge )

Input

xFD1

BOOL

FALSE

Set the state of the output for fire damper 1 ( FALSE = closed )

Input

xResAutoFDx

BOOL

FALSE

Switch the manual override of the outputs for the fire dampers to automatic mode (on every rising edge )

Input

xSendSysCommand

BOOL

FALSE

Activate transmission of the system command ( register 6 ) ( on every rising edge AND wSysCommand > 0 )

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

xFD1_Open

BOOL

Feedback - fire damper 1 open ( TRUE = open )

Output

xFD1_Closed

BOOL

Feedback - fire damper 1 closed ( TRUE = closed )

Output

xFD1_Fb

BOOL

Feedback - state of the output of fire damper 1 ( FALSE = closed )

Output

eAOO_FD1

eManBin

State of the manual override at the output of fire damper 1

Output

xAlarm

BOOL

FALSE

General fault ( TRUE = fault )

Output

xAlarmCom

BOOL

FALSE

General fault - communication ( TRUE = fault )

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication ( 0 = no error )

Output

stErrorCodeFD1

STRING

String with the bit numbers of the active errors of fire damper 1 ( '' = no error )

Output

xBusy

BOOL

Communication indicator ( TRUE = communication )

Input Const

xDIxInversion

BOOL

FALSE

Set the inversion of the digital inputs DIx ( FALSE: no inversion // TRUE = inversion )

Input Const

wSysCommand

WORD

0

Value of the system command to be transmitted ( FC06 - register 6 ) ( 0 = no function, values > 0 see documentation T1_BSK1_XXX )

Input Const

xFD1_SafeState_Sta

BOOL

TRUE

State of the digital output for fire damper 1 in safestate operation ( TRUE = open )

Input Const

xFD1_SafeState_En

BOOL

FALSE

Enable / disable the digital output for fire damper 1 for safestate operation ( TRUE = enabled )

Input Const

tTimeSafeState

TIME

TIME#0ms

Duration for activation of the 'Safestate' condition in case of communication failure ( 0 = no timeout/safe-state function, integer multiples of 1s, minimum 5s )

Input Const

tTimeUpdateSetp

TIME

TIME#0ms

Update interval for operations influenced by the input 'xUpdateSetp'

Input Const

tTimeUpdateActual

TIME

TIME#3s0ms

Update interval for operations influenced by the input 'xUpdateActual'