ControlP
ControlP (FB)
FUNCTION_BLOCK ControlP
Short description
Proportional controller (P controller) The action direction (inverted / direct) can also be set. Typical application: control loops with actuators that have a storage characteristic.
Representation

Interfaces
Inputs
rX
REAL
Analog actual value
rW
REAL
Analog setpoint value
xEn
BOOL
Controller enable
Outputs
rY
REAL
0.0
Controller output signal
rDiff
REAL
Control deviation
xLimitActive
BOOL
Status - limit exceedance
Setpoints / Parameters
rMax
REAL
100.0
Upper absolute limit value of the output signal
rMin
REAL
-100.0
Lower absolute limit value of the output signal
rKp
REAL
0.0 …
2.0
Gain factor
rOffset
REAL
0.0
Offset
rYDisabled
REAL
0.0
Switch-off value
eAction
eControlMode
eControlMode.Inverted
Action direction of the controller (Inverted, Direct)
eManModeN
eManNum
eManNum.Auto
Operating mode for the controller output signal
rManValue
REAL
Output signal in manual mode
Functional description
General
This function block contains a proportional controller (P controller). The controller output signal rY is calculated when the controller is enabled (xEn = TRUE) and in automatic mode of the controller (eManModeN = eManNum.Auto) as follows: rY = rKp * ((Actual value + Offset) - (Setpoint value)) Depending on the action direction of the controller eAction the actual and setpoint values are defined as follows:
eAction
Actual value
Setpoint
Formula
Function
eControlMode.Invertiert
rW
rX
rY = rKp * ((rW + rOffset) - (rX))
Action direction - Inverted
eControlMode.Direct
rX
rW
rY = rKp * ((rX + rOffset) - (rW))
Action direction - Direct
Enable input xEn
If the enable input is not active (xEn = FALSE) the switch-off value rYDisabled to the output rY is transferred (prerequisite: eManModeN = eManNum.Auto) and limited by the absolute limit values. If the enable input is active (xEn = TRUE) the output signal is calculated according to the formula above and to the output rY is transferred (prerequisite: eManModeN = eManNum.Auto) and limited by the absolute limit values.
Control deviation rDiff
The control deviation is calculated according to the following formula and to the output rDiff transferred. rDiff = Actual value - setpoint value
Absolute limit values rMin and rMax
The controller output signal rY is limited by the absolute limit values rMin downward and rMax upward. The absolute limit value rMin is set to the current value of rMax - 0.1, if it is >= the current value of rMax is. The only exception is manual mode for the controller output signal (eManModeN = eManNum.Man).
Status - limit exceedance xLimitActive
The limit exceedance status is activated (xLimitActive = TRUE) if a limit exceedance is present. The limit exceedance status is not activated (xLimitActive = FALSE) if no limit exceedance is present. A limit exceedance exists if the controller output signal rY the upper limit value rMax reaches / exceeds or the lower limit value rMin reaches / falls below.
Operating mode for the controller output signal eManModeN
The parameter eManModeN allows switching the output signal rY from automatic mode to manual mode and vice versa. In manual mode, the output signal takes over rY the output signal in manual mode rManValue. The setpoint / parameter rManValue is overwritten each time the system switches to automatic mode with the current value of the output signal rY overwritten.
eManModeN
rY
Function
eManNum.Auto
Signal according to formula / switch-off value
Automatic mode - output signal
eManNum.Man
rManValue
Manual mode - output signal
CODESYS
InOut:
Input
rX
REAL
Input
rW
REAL
Input
xEn
BOOL
Input Const
rYMax
REAL
100
Input Const
rYMin
REAL
-100
Input Const
rKp
REAL
2
Input Const
rOffset
REAL
0
Input Const
rYDisabled
REAL
0
Input Const
eAction
eControlMode
eControlMode.Inverted
Input Const
eManModeN
eManNum
eManNum.Auto
Input Const
rManValue
REAL
Output
rY
REAL
0
Output
rDiff
REAL
Output
xLimitActive
BOOL
Last updated

