CascadeExtractSupplyAirX2Setpt

CascadeExtractSupplyAirX2Setpt (FB)

FUNCTION_BLOCK CascadeExtractSupplyAirX2Setpt

Short description

Formation of two supply air setpoint temperatures using two cascade controllers (PI controllers) Additional functions: Limitation of the supply air setpoint temperatures Typical application: Supply air temperature control in a ventilation system with active cooling

Representation

Function description

General

This function block corresponds to the block ‘CascadeExtractSupplyAirTemperature’, which here is extended by another cascade controller to form a separate supply air setpoint temperature for the cooler in active cooling operation.

CascadeExtractSupplyAirTemperature

This function block is used to generate the supply air setpoint temperature of a ventilation system from

  1. Current setpoint temperature (exhaust or room temperature) in °C

2) Current actual temperature (exhaust or room temperature) in °C taking into account the relative (rMinSUPTemp and rMaxSUPTemp) and absolute (rMinSUP and rMaxSUP) limits. In addition, the special operating modes ‘Fast heating’ and ‘Free night cooling’ are taken into account when forming the supply air setpoint temperature. The formation of the supply air setpoint temperature takes place with a time delay (tDelayControl) after the release/locking of the controller (xEn = TRUE). The cascade controller is enabled if the following conditions described below are fulfilled simultaneously: 1) The special operating mode Fast heating is locked (xFastHeatEn = FALSE). 2) The special operating mode Free night cooling is locked (xFNCEn = FALSE). 3) The current actual temperature rActTemp does not violate its absolute limits (+5.0 - +50.0 °C). 4) The control is enabled (xEn = TRUE) and the start-up delay (time duration = tDelayControl) has ended. In all other situations the cascade controller is locked.

Control

The current actual temperature rActTemp is, with the cascade controller enabled (PI controller, xEn = TRUE, expiry of the time duration tDelayControl, no limit violation at the input rActTemp) continuously compared with the current setpoint temperature rSetPtTemp and depending on the magnitude/sign of the difference or depending on the controller settings (rPI_Kp or rPI_Tn) an offset temperature is generated in the cascade controller. In heating mode (rActTemp < rSetPtTemp) this produces a positive offset temperature in the range 0.0 - rMaxRelativeSUP K. In cooling mode ( rActTemp > rSetPtTemp ) thus a negative offset temperature arises in the range 0.0 - rMinRelativeSUP K. In the fully regulated state ( rActTemp = rSetPtTemp ) the offset temperature does not change. This offset temperature is then added to the current setpoint temperature and, if necessary, limited to the calculated limits rMinSUPTemp or rMaxSUPTemp . At the output rMinSUPTemp the calculated minimum supply air setpoint temperature is continuously shown (rActTemp + rMinRelativeSUP, absolutely limited to rMinSUP or rMaxSUP) . At the output rMaxSUPTemp the calculated maximum supply air setpoint temperature is continuously shown (rActTemp + rMaxRelativeSUP, absolutely limited to rMinSUP or rMaxSUP). The current actual temperature rActTemp is monitored for compliance with limits. On every limit violation (rActTemp < +5.0 °C or rActTemp > +50.0 °C) the cascade controller is deactivated.

Selection of the supply air setpoint temperature

The selection of the supply air setpoint temperature is carried out according to the following function table.

xFastHeatEn

xFNCEn

rActTemp within limit

xEn

Supply air setpoint temperature

Notes

TRUE

X

X

X

rMaxSUP

Special operating mode ‘Fast heating’

FALSE

TRUE

X

X

rMinSUP

Special operating mode ‘Free night cooling’

FALSE

FALSE

FALSE

X

rSetPtTemp

Limit violation actual temperature

FALSE

FALSE

X

FALSE

rSetPtTemp

Locking of the control

FALSE

FALSE

TRUE

TRUE

rSetPtTemp + Offset temperature

Normal operation

Legend: X = any

Formation of the current supply air setpoint temperature rSetPtSUPTemp

The current supply air setpoint temperature rSetPtSUPTemp is formed from the supply air setpoint temperature, extended by a manual override module.

Supply air setpoint temperature

eManModeN

rSetPtSUPTemp

Notes

X

eMANNUM.Auto

Supply air setpoint temperature

Manual override module in automatic

X

eMANNUM.Man

rManValue

Manual override module in manual operation

Legend: X = any

Cascade controller for active cooling operation (PI controller)

This cascade controller is used to form the supply air setpoint temperature for a cooling device from

  1. Current setpoint temperature (maximum value of (rSetPtTemp + 1) and rSetPtTempCool)

2) Current actual temperature (exhaust air or room temperature) in °C taking into account the following limits: Minimum value - output signal of the cascade controller: rMinSUPTemP - (maximum of (rSetPtTemp + 1) and rSetPtTempCool) Maximum value - output signal of the cascade controller: rMaxSUPTemP - (maximum of (rSetPtTemp + 1) and rSetPtTempCool) The formation of the supply air setpoint temperature takes place after enabling/disabling of the main cascade controller, provided the input xEnCool is active (= TRUE). The enabling of the cascade controller for active cooling occurs if the following conditions described below are all fulfilled simultaneously: 1) The special operating mode rapid heating is disabled (xFastHeatEn = FALSE). 2) The special operating mode free night cooling is disabled (xFNCEn = FALSE). 3) The current actual temperature rActTemp does not violate its absolute limits (+5.0 - +50.0 °C). 4) The control is enabled (xEn = TRUE) and the switch-on delay (duration = tDelayControl) has ended. 5) The input xEnCool is enabled (xEnCool = TRUE). In all other situations the cascade controller for active cooling is disabled.

Control

The current actual temperature rActTemp is, with the cascade controller for active cooling operation enabled, continuously compared with the current setpoint temperature (maximum value of (rSetPtTemp + 1) and rSetPtTempCool) and depending on the magnitude/sign of the difference or depending on the controller settings (rPI_Kp or rPI_Tn) an offset temperature for active cooling operation is generated in the cascade controller. In heating mode (rActTemp < current setpoint temperature) this produces a positive offset temperature in the range 0.0 - Minimum value - output signal of the cascade controller for active cooling operation K. In cooling mode (rActTemp > current setpoint temperature) this produces a negative offset temperature in the range 0.0 - Maximum value - output signal of the cascade controller for active cooling operation K. In the fully regulated state (rActTemp = current setpoint temperature) the offset temperature does not change. This offset temperature is then added to the current setpoint temperature and, if necessary, limited to the calculated limits rMinSUPTemp or rMaxSUPTemp limited. The current actual temperature rActTemp is monitored for compliance with limits. On every limit violation (rActTemp < +5.0 °C or rActTemp > +50.0 °C) the cascade controller is deactivated.

Selection of the supply air setpoint temperature

The selection of the supply air setpoint temperature is carried out according to the following function table.

Release cascade controller for active cooling operation

rActTemp within limit

Supply air setpoint temperature

Notes

FALSE

X

Maximum value of (rSetPtTemp + 1) and rSetPtTempCool

Controller locked

X

FALSE

Maximum value of (rSetPtTemp + 1) and rSetPtTempCool

Limit violation

TRUE

TRUE

Current setpoint temperature + offset temperature

Normal operation

Legend: X = any

Formation of the current supply air setpoint temperature rSetPtSUPTempCool

The current supply air setpoint temperature rSetPtSUPTempCool is formed from the supply air setpoint temperature, extended by a manual override module.

Supply air setpoint temperature

eManModeNCool

rSetPtSUPTempCool

Notes

X

eMANNUM.Auto

Supply air setpoint temperature

Manual override module in automatic

X

eMANNUM.Man

rManValueCool

Manual override module in manual operation

Legend: X = any

Codesys

InOut:

Scope
Name
Type
Initial

Input

xEn

BOOL

Input

rActX

REAL

9

Input

rSetPtminHum

REAL

40

Input

rSetPtmaxHum

REAL

70

Input

rSetPtTemp

REAL

21

Input

rSUPTemp

REAL

20

Output

rSetPtSUPxHumidify

REAL

Output

rSetPtSUPxDehumidify

REAL

Output

rMinSUPX

REAL

Output

rMaxSUPX

REAL

Output

rSetPtxHumidify

REAL

Output

rSetPtxDehumimdify

REAL

Output

xEnHum

BOOL

Output

xEnDehum

BOOL

Input Const

rPI_Tn

REAL

400

Input Const

rPI_Kp

REAL

1.4

Input Const

rMaxHumSUP

REAL

80

Input Const

rMinHumSUP

REAL

30

Input Const

tDelayControl

TIME

TIME#5m0s0ms

Input Const

rP

REAL

980.0

Input Const

rManValueDehum

REAL

Input Const

eManModeNDehum

eManNum

eManNum.Auto

Input Const

rManValueHum

REAL

Input Const

eManModeNHum

eManNum

eManNum.Auto

Last updated