Skip to content
For the complete documentation index, see llms.txt. This page is also available as Markdown.

CascadeExtractSupplyAirX2Setpt

CascadeExtractSupplyAirX2Setpt (FB)

FUNCTION_BLOCK CascadeExtractSupplyAirX2Setpt

Short description

Generation of two supply air setpoint temperatures using two cascade controllers (PI controllers) Additional functions: Limitation of the supply air setpoint temperatures Typical application: Supply air temperature control in an air-handling unit with active cooling

Representation

Functional description

General

This function block corresponds to the block ‘CascadeExtractSupplyAirTemperature’, which is extended here by an additional cascade controller for generating a separate supply air setpoint temperature for the cooler in active cooling mode.

CascadeExtractSupplyAirTemperature

This function block is used to generate the supply air setpoint temperature of a ventilation system from

  1. Current setpoint temperature (exhaust air or room temperature) in °C

2) Current actual temperature (exhaust air or room temperature) in °C taking into account the relative (rMinSUPTemp or rMaxSUPTemp) and absolute (rMinSUP or rMaxSUP) limits. In addition, when forming the supply air setpoint, the special operating modes ‘Rapid heating’ and ‘Free night cooling’ are taken into account. The supply air setpoint is formed with a delay (tDelayControl) after the controller is enabled / disabled (xEn = TRUE). The cascade controller is enabled if the following conditions described below are all met at the same time: 1) The special operating mode Rapid heating is disabled (xFastHeatEn = FALSE). 2) The special operating mode Free night cooling is disabled (xFNCEn = FALSE). 3) The current actual temperature rActTemp does not violate its absolute limit values (+5.0 - +50.0 °C). 4) Control is enabled (xEn = TRUE) and the switch-on delay (duration = tDelayControl) has ended. In all other situations, the cascade controller is disabled.

Control

The current actual temperature rActTemp is permanently compared with the current setpoint temperature when the cascade controller is enabled (PI controller, xEn = TRUE, expiration of the duration tDelayControl, no limit value violation at the input rActTemp) and depending on the amount / sign of the difference or on the controller settings ( rSetPtTemp compared and depending on the magnitude / sign of the difference or depending on the controller settings (rPI_Kp or rPI_Tn) a displacement temperature is generated in the cascade controller. In heating mode (rActTemp < rSetPtTemp) a positive displacement temperature is thus generated in the range 0.0 - rMaxRelativeSUP K. In cooling mode ( rActTemp > rSetPtTemp ) thus a negative offset temperature is created in the range 0.0 - rMinRelativeSUP K. In the fully regulated state ( rActTemp = rSetPtTemp ) the displacement temperature does not change. This displacement temperature is then added to the current setpoint temperature and, if necessary, limited to the calculated limits rMinSUPTemp or rMaxSUPTemp . At output rMinSUPTemp the calculated minimum supply air setpoint temperature (rActTemp + rMinRelativeSUP, absolutely limited to rMinSUP or rMaxSUP) is permanently displayed. At output rMaxSUPTemp the calculated maximum supply air setpoint temperature (rActTemp + rMaxRelativeSUP, absolutely limited to rMinSUP or rMaxSUP) is permanently displayed. The current actual temperature rActTemp is monitored for compliance with limit values. At every limit violation (rActTemp < +5.0 °C or rActTemp > +50.0 °C) the cascade controller is deactivated.

Selection of the supply air setpoint temperature

The selection of the supply air setpoint temperature is carried out according to the following function table.

xFastHeatEn

xFNCEn

rActTemp within limit values

xEn

Supply air setpoint temperature

Notes

TRUE

X

X

X

rMaxSUP

Special operating mode ‘Rapid heating’

FALSE

TRUE

X

X

rMinSUP

Special operating mode ‘Free night cooling’

FALSE

FALSE

FALSE

X

rSetPtTemp

Actual temperature limit violation

FALSE

FALSE

X

FALSE

rSetPtTemp

Control lockout

FALSE

FALSE

TRUE

TRUE

rSetPtTemp + displacement temperature

Normal operation

Legend: X = any

Formation of the current supply air setpoint temperature rSetPtSUPTemp

The current supply air setpoint temperature rSetPtSUPTemp is formed from the supply air setpoint temperature, extended by a manual override module.

Supply air setpoint temperature

eManModeN

rSetPtSUPTemp

Notes

X

eMANNUM.Auto

Supply air setpoint temperature

Manual override module in automatic mode

X

eMANNUM.Man

rManValue

Manual override module in manual mode

Legend: X = any

Cascade controller for active cooling mode (PI controller)

This cascade controller is used to generate the supply air setpoint temperature for a cooling unit from

  1. Current setpoint temperature (maximum value of (rSetPtTemp + 1) and rSetPtTempCool)

2) Current actual temperature (exhaust air or room temperature) in °C taking into account the following limits: Minimum value - output signal of the cascade controller: rMinSUPTemP - (maximum value of (rSetPtTemp + 1) and rSetPtTempCool) Maximum value - output signal of the cascade controller: rMaxSUPTemP - (maximum value of (rSetPtTemp + 1) and rSetPtTempCool) The supply air setpoint temperature is generated after the enabling / disabling of the main cascade controller, provided that input xEnCool is active (= TRUE). The cascade controller for active cooling mode is enabled if the following conditions described below are all met at the same time: 1) The special operating mode rapid heat-up is blocked (xFastHeatEn = FALSE). 2) The special operating mode free night cooling is blocked (xFNCEn = FALSE). 3) The current actual temperature rActTemp does not violate its absolute limits (+5.0 - +50.0 °C). 4) The control is enabled (xEn = TRUE) and the switch-on delay (duration = tDelayControl) has ended. 5) The input xEnCool is enabled (xEnCool = TRUE). In all other situations, the cascade controller for active cooling mode is blocked.

Control

The current actual temperature rActTemp is, when enabled, continuously compared with the current setpoint temperature (maximum value of (rSetPtTemp + 1) and rSetPtTempCool) and, depending on the magnitude/sign of the difference or depending on the controller settings (rPI_Kp or rPI_Tn) an offset temperature for active cooling mode is generated in the cascade controller. In the heating case (rActTemp < current setpoint temperature) a positive offset temperature is created in the range 0.0 - minimum value - output signal of the cascade controller for active cooling mode K. In the cooling case (rActTemp > current setpoint temperature) a negative offset temperature is created in the range 0.0 - maximum value - output signal of the cascade controller for active cooling mode K. In the fully regulated state (rActTemp = current setpoint temperature) the offset temperature does not change. This offset temperature is then added to the current setpoint temperature and, if necessary, limited to the calculated limits rMinSUPTemp or rMaxSUPTemp limited. The current actual temperature rActTemp is monitored for compliance with limit values. At every limit violation (rActTemp < +5.0 °C or rActTemp > +50.0 °C) the cascade controller is deactivated.

Selection of the supply air setpoint temperature

The selection of the supply air setpoint temperature is carried out according to the following function table.

Enable cascade controller for active cooling mode

rActTemp within limit values

Supply air setpoint temperature

Notes

FALSE

X

Maximum value of (rSetPtTemp + 1) and rSetPtTempCool

Controller blocked

X

FALSE

Maximum value of (rSetPtTemp + 1) and rSetPtTempCool

limit violation

TRUE

TRUE

Current setpoint temperature + offset temperature

Normal operation

Legend: X = any

Formation of the current supply air setpoint temperature rSetPtSUPTempCool

The current supply air setpoint temperature rSetPtSUPTempCool is formed from the supply air setpoint temperature, extended by a manual override module.

Supply air setpoint temperature

eManModeNCool

rSetPtSUPTempCool

Notes

X

eMANNUM.Auto

Supply air setpoint temperature

Manual override module in automatic mode

X

eMANNUM.Man

rManValueCool

Manual override module in manual mode

Legend: X = any

Codesys

InOut:

Scope
Name
Type
Initial

Input

xEn

BOOL

Input

rActX

REAL

9

Input

rSetPtminHum

REAL

40

Input

rSetPtmaxHum

REAL

70

Input

rSetPtTemp

REAL

21

Input

rSUPTemp

REAL

20

Output

rSetPtSUPxHumidify

REAL

Output

rSetPtSUPxDehumidify

REAL

Output

rMinSUPX

REAL

Output

rMaxSUPX

REAL

Output

rSetPtxHumidify

REAL

Output

rSetPtxDehumimdify

REAL

Output

xEnHum

BOOL

Output

xEnDehum

BOOL

Input Const

rPI_Tn

REAL

400

Input Const

rPI_Kp

REAL

1.4

Input Const

rMaxHumSUP

REAL

80

Input Const

rMinHumSUP

REAL

30

Input Const

tDelayControl

TIME

TIME#5m0s0ms

Input Const

rP

REAL

980.0

Input Const

rManValueDehum

REAL

Input Const

eManModeNDehum

eManNum

eManNum.Auto

Input Const

rManValueHum

REAL

Input Const

eManModeNHum

eManNum

eManNum.Auto

Last updated