CascadeExtractSupplyAirTemp2Setpt

CascadeExtractSupplyAirTemp2Setpt (FB)

CascadeExtractSupplyAirTemp2Setpt (FB)FUNCTION_BLOCK CascadeExtractSupplyAirTemp2Setpt
Short description
Formation of two supply air setpoint temperatures using two cascade controllers (PI controllers) Additional functions: Limitation of the supply air setpoint temperatures Typical application: Supply air temperature control in a ventilation unit with active cooling\
Representation

Function description
General
This function block corresponds to the block ‘CascadeExtractSupplyAirTemperature’, which here is extended by an additional cascade controller to form a separate supply air setpoint temperature for the cooler in active cooling operation.\
CascadeExtractSupplyAirTemperature
This function block is used to form the supply air setpoint temperature of a ventilation unit from \
Current setpoint temperature (exhaust air or room temperature) in °C\
2) Current actual temperature (exhaust air or room temperature) in °C taking into account the relative (*rMinSUPTemp* and *rMaxSUPTemp*) and absolute (**rMinSUP** and **rMaxSUP**) limits. In addition, the special operating modes ‘Rapid heating’ and ‘Free night cooling’ are taken into account when forming the supply air setpoint temperature. The formation of the supply air setpoint temperature is time-delayed (**tDelayControl**) after the enabling / disabling of the controller (*xEn* = TRUE). The cascade controller is enabled if the following conditions described below are simultaneously met: 1) The special operating mode *Rapid heating* is disabled (*xFastHeatEn* = FALSE). 2) The special operating mode *Free night cooling* is disabled (*xFNCEn* = FALSE). 3) The current actual temperature *rActTemp* does not violate its absolute limits (+5.0 - +50.0 °C). 4) The control is enabled (*xEn* = TRUE) and the start delay (duration = **tDelayControl**) has ended. In all other situations the cascade controller is disabled.\
Control
The current actual temperature rActTemp is, when the cascade controller is enabled (PI controller, xEn = TRUE, expiry of the time duration tDelayControl, no limit violation at the input rActTemp ) continuously compared with the current setpoint temperature rSetPtTemp and depending on the magnitude / sign of the difference or depending on the controller settings ( rPI_Kp or rPI_Tn ) a offset temperature is generated in the cascade controller. In the heating case ( rActTemp < rSetPtTemp ) a positive offset temperature thus arises in the range 0.0 - rMaxRelativeSUP K. In the cooling case ( rActTemp > rSetPtTemp ) a negative offset temperature thus arises in the range 0.0 - rMinRelativeSUP K. In the fully regulated state ( rActTemp = rSetPtTemp ) the offset temperature does not change. This offset temperature is then added to the current setpoint temperature and, if necessary, limited to the calculated limits &#xNAN;rMinSUPTemp or rMaxSUPTemp limited. At the output rMinSUPTemp the calculated minimum supply air setpoint temperature is continuously displayed ( rActTemp + rMinRelativeSUP, absolutely limited to rMinSUP or rMaxSUP ) . At the output rMaxSUPTemp the calculated maximum supply air setpoint temperature is continuously displayed ( rActTemp + rMaxRelativeSUP, absolutely limited to rMinSUP or rMaxSUP ). The current actual temperature rActTemp is monitored for compliance with limits. On every limit violation ( rActTemp < +5.0 °C or rActTemp > +50.0 °C ) the cascade controller is deactivated.\
Selection of the supply air setpoint temperature
The selection of the supply air setpoint temperature is made according to the following function table.\
xFastHeatEn
xFNCEn
rActTemp within limit
xEn
Supply air setpoint temperature
Notes
TRUE
X
X
X
rMaxSUP
Special operating mode ‘Rapid heating’
FALSE
TRUE
X
X
rMinSUP
Special operating mode ‘Free night cooling’
FALSE
FALSE
FALSE
X
rSetPtTemp
Limit violation actual temperature
FALSE
FALSE
X
FALSE
rSetPtTemp
Locking of the control
FALSE
FALSE
TRUE
TRUE
rSetPtTemp + Offset temperature
Normal operation
Legend: X = any\
Formation of the current supply air setpoint temperature rSetPtSUPTemp
The current supply air setpoint temperature rSetPtSUPTemp is formed from the supply air setpoint temperature, extended by a manual override module.\
Supply air setpoint temperature
eManModeN
rSetPtSUPTemp
Notes
X
eMANNUM.Auto
Supply air setpoint temperature
Manual override module in automatic
X
eMANNUM.Man
rManValue
Manual override module in manual operation
Legend: X = any\
Cascade controller for active cooling operation (PI controller)
This cascade controller is used to form the supply air setpoint temperature for a cooling device from \
Current setpoint temperature (maximum value of ( rSetPtTemp + 1) and rSetPtTempCool )\
2) Current actual temperature (exhaust air or room temperature) in °C taking into account the following limits: Minimum value - output signal of the cascade controller: *rMinSUPTemP* - (maximum value of (*rSetPtTemp* + 1) and *rSetPtTempCool*) Maximum value - output signal of the cascade controller: *rMaxSUPTemP* - (maximum value of (*rSetPtTemp* + 1) and *rSetPtTempCool*) The formation of the supply air setpoint temperature takes place after enabling / disabling of the main cascade controller, provided the input *xEnCool* is active (= TRUE). The cascade controller for active cooling operation is enabled if the following conditions described below are simultaneously met: 1) The special operating mode *Rapid heating* is disabled (*xFastHeatEn* = FALSE). 2) The special operating mode *Free night cooling* is disabled (*xFNCEn* = FALSE). 3) The current actual temperature *rActTemp* does not violate its absolute limits (+5.0 - +50.0 °C). 4) The control is enabled (*xEn* = TRUE) and the start delay (duration = **tDelayControl**) has ended. 5) The input *xEnCool* is enabled (*xEnCool* = TRUE). In all other situations the cascade controller for active cooling operation is disabled.\
Control
The current actual temperature rActTemp is, when the cascade controller for active cooling operation is enabled, continuously compared with the current setpoint temperature (maximum value of ( rSetPtTemp + 1) and rSetPtTempCool ) and depending on the magnitude / sign of the difference or depending on the controller settings ( rPI_Kp or rPI_Tn ) an offset temperature for active cooling operation is generated in the cascade controller. In the heating case ( rActTemp < current setpoint temperature ) a positive offset temperature thus arises in the range 0.0 - Minimum value - output signal of the cascade controller for active cooling operation K. In the cooling case ( rActTemp > current setpoint temperature ) a negative offset temperature thus arises in the range 0.0 - Maximum value - output signal of the cascade controller for active cooling operation K. In the fully regulated state ( rActTemp = current setpoint temperature ) the offset temperature does not change. This offset temperature is then added to the current setpoint temperature and, if necessary, limited to the calculated limits &#xNAN;rMinSUPTemp or rMaxSUPTemp limited. The current actual temperature rActTemp is monitored for compliance with limits. On every limit violation ( rActTemp < +5.0 °C or rActTemp > +50.0 °C ) the cascade controller is deactivated.\
Selection of the supply air setpoint temperature
The selection of the supply air setpoint temperature is made according to the following function table.\
Enable cascade controller for active cooling operation
rActTemp within limit
Supply air setpoint temperature
Notes
FALSE
X
Maximum value of ( rSetPtTemp + 1) and rSetPtTempCool
Controller disabled
X
FALSE
Maximum value of ( rSetPtTemp + 1) and rSetPtTempCool
Limit violation
TRUE
TRUE
Current setpoint temperature + offset temperature
Normal operation
Legend: X = any\
Formation of the current supply air setpoint temperature rSetPtSUPTempCool
The current supply air setpoint temperature rSetPtSUPTempCool is formed from the supply air setpoint temperature, extended by a manual override module.\
Supply air setpoint temperature
eManModeNCool
rSetPtSUPTempCool
Notes
X
eMANNUM.Auto
Supply air setpoint temperature
Manual override module in automatic
X
eMANNUM.Man
rManValueCool
Manual override module in manual operation
Legend: X = any\
CODESYS
InOut:
Input
xEn
BOOL
Input
rActTemp
REAL
0
Input
rSetPtTemp
REAL
21
Input
rSetPtTempCool
REAL
24
Input
xEnCool
BOOL
Input
xFastHeatEn
BOOL
FALSE
Input
xFNCEn
BOOL
FALSE
Output
rSetPtSUPTemp
REAL
Output
rSetPtSUPTempCool
REAL
Output
rMinSUPTemp
REAL
Output
rMaxSUPTemp
REAL
Input Const
rPI_Tn
REAL
600
Input Const
rPI_Kp
REAL
1
Input Const
rMaxSUP
REAL
26
Input Const
rMaxRelativeSUP
REAL
6
Input Const
rMinSUP
REAL
16
Input Const
rMinRelativeSUP
REAL
-8
Input Const
tDelayControl
TIME
TIME#5m0s0ms
Input Const
rManValueCool
REAL
Input Const
eManModeNCool
eManNum
eManNum.Auto
Input Const
rManValue
REAL
Input Const
eManModeN
eManNum
eManNum.Auto
Last updated

