CascadeExtractSupplyAirTemp2Setpt

../../../_images/CascadeExtractSupplyAirTemp2Setpt_FB.pngCascadeExtractSupplyAirTemp2Setpt (FB)

FUNCTION_BLOCK CascadeExtractSupplyAirTemp2Setpt

Short description

Formation of two supply air setpoint temperatures using two cascade controllers (PI controllers) Additional functions: Limitation of the supply air setpoint temperatures Typical application: Supply air temperature control in a ventilation unit with active cooling\

Representation

Function description

General

This function block corresponds to the block ‘CascadeExtractSupplyAirTemperature’, which here is extended by an additional cascade controller to form a separate supply air setpoint temperature for the cooler in active cooling operation.\

CascadeExtractSupplyAirTemperature

This function block is used to form the supply air setpoint temperature of a ventilation unit from \

  1. Current setpoint temperature (exhaust air or room temperature) in °C\

2) Current actual temperature (exhaust air or room temperature) in °C taking into account the relative (*rMinSUPTemp* and *rMaxSUPTemp*) and absolute (**rMinSUP** and **rMaxSUP**) limits. In addition, the special operating modes ‘Rapid heating’ and ‘Free night cooling’ are taken into account when forming the supply air setpoint temperature. The formation of the supply air setpoint temperature is time-delayed (**tDelayControl**) after the enabling / disabling of the controller (*xEn* = TRUE). The cascade controller is enabled if the following conditions described below are simultaneously met: 1) The special operating mode *Rapid heating* is disabled (*xFastHeatEn* = FALSE). 2) The special operating mode *Free night cooling* is disabled (*xFNCEn* = FALSE). 3) The current actual temperature *rActTemp* does not violate its absolute limits (+5.0 - +50.0 °C). 4) The control is enabled (*xEn* = TRUE) and the start delay (duration = **tDelayControl**) has ended. In all other situations the cascade controller is disabled.\

Control

The current actual temperature rActTemp is, when the cascade controller is enabled (PI controller, xEn = TRUE, expiry of the time duration tDelayControl, no limit violation at the input rActTemp ) continuously compared with the current setpoint temperature rSetPtTemp and depending on the magnitude / sign of the difference or depending on the controller settings ( rPI_Kp or rPI_Tn ) a offset temperature is generated in the cascade controller. In the heating case ( rActTemp < rSetPtTemp ) a positive offset temperature thus arises in the range 0.0 - rMaxRelativeSUP K. In the cooling case ( rActTemp > rSetPtTemp ) a negative offset temperature thus arises in the range 0.0 - rMinRelativeSUP K. In the fully regulated state ( rActTemp = rSetPtTemp ) the offset temperature does not change. This offset temperature is then added to the current setpoint temperature and, if necessary, limited to the calculated limits &#xNAN;rMinSUPTemp or rMaxSUPTemp limited. At the output rMinSUPTemp the calculated minimum supply air setpoint temperature is continuously displayed ( rActTemp + rMinRelativeSUP, absolutely limited to rMinSUP or rMaxSUP ) . At the output rMaxSUPTemp the calculated maximum supply air setpoint temperature is continuously displayed ( rActTemp + rMaxRelativeSUP, absolutely limited to rMinSUP or rMaxSUP ). The current actual temperature rActTemp is monitored for compliance with limits. On every limit violation ( rActTemp < +5.0 °C or rActTemp > +50.0 °C ) the cascade controller is deactivated.\

Selection of the supply air setpoint temperature

The selection of the supply air setpoint temperature is made according to the following function table.\

xFastHeatEn

xFNCEn

rActTemp within limit

xEn

Supply air setpoint temperature

Notes

TRUE

X

X

X

rMaxSUP

Special operating mode ‘Rapid heating’

FALSE

TRUE

X

X

rMinSUP

Special operating mode ‘Free night cooling’

FALSE

FALSE

FALSE

X

rSetPtTemp

Limit violation actual temperature

FALSE

FALSE

X

FALSE

rSetPtTemp

Locking of the control

FALSE

FALSE

TRUE

TRUE

rSetPtTemp + Offset temperature

Normal operation

Legend: X = any\

Formation of the current supply air setpoint temperature rSetPtSUPTemp

The current supply air setpoint temperature rSetPtSUPTemp is formed from the supply air setpoint temperature, extended by a manual override module.\

Supply air setpoint temperature

eManModeN

rSetPtSUPTemp

Notes

X

eMANNUM.Auto

Supply air setpoint temperature

Manual override module in automatic

X

eMANNUM.Man

rManValue

Manual override module in manual operation

Legend: X = any\

Cascade controller for active cooling operation (PI controller)

This cascade controller is used to form the supply air setpoint temperature for a cooling device from \

  1. Current setpoint temperature (maximum value of ( rSetPtTemp + 1) and rSetPtTempCool )\

2) Current actual temperature (exhaust air or room temperature) in °C taking into account the following limits: Minimum value - output signal of the cascade controller: *rMinSUPTemP* - (maximum value of (*rSetPtTemp* + 1) and *rSetPtTempCool*) Maximum value - output signal of the cascade controller: *rMaxSUPTemP* - (maximum value of (*rSetPtTemp* + 1) and *rSetPtTempCool*) The formation of the supply air setpoint temperature takes place after enabling / disabling of the main cascade controller, provided the input *xEnCool* is active (= TRUE). The cascade controller for active cooling operation is enabled if the following conditions described below are simultaneously met: 1) The special operating mode *Rapid heating* is disabled (*xFastHeatEn* = FALSE). 2) The special operating mode *Free night cooling* is disabled (*xFNCEn* = FALSE). 3) The current actual temperature *rActTemp* does not violate its absolute limits (+5.0 - +50.0 °C). 4) The control is enabled (*xEn* = TRUE) and the start delay (duration = **tDelayControl**) has ended. 5) The input *xEnCool* is enabled (*xEnCool* = TRUE). In all other situations the cascade controller for active cooling operation is disabled.\

Control

The current actual temperature rActTemp is, when the cascade controller for active cooling operation is enabled, continuously compared with the current setpoint temperature (maximum value of ( rSetPtTemp + 1) and rSetPtTempCool ) and depending on the magnitude / sign of the difference or depending on the controller settings ( rPI_Kp or rPI_Tn ) an offset temperature for active cooling operation is generated in the cascade controller. In the heating case ( rActTemp < current setpoint temperature ) a positive offset temperature thus arises in the range 0.0 - Minimum value - output signal of the cascade controller for active cooling operation K. In the cooling case ( rActTemp > current setpoint temperature ) a negative offset temperature thus arises in the range 0.0 - Maximum value - output signal of the cascade controller for active cooling operation K. In the fully regulated state ( rActTemp = current setpoint temperature ) the offset temperature does not change. This offset temperature is then added to the current setpoint temperature and, if necessary, limited to the calculated limits &#xNAN;rMinSUPTemp or rMaxSUPTemp limited. The current actual temperature rActTemp is monitored for compliance with limits. On every limit violation ( rActTemp < +5.0 °C or rActTemp > +50.0 °C ) the cascade controller is deactivated.\

Selection of the supply air setpoint temperature

The selection of the supply air setpoint temperature is made according to the following function table.\

Enable cascade controller for active cooling operation

rActTemp within limit

Supply air setpoint temperature

Notes

FALSE

X

Maximum value of ( rSetPtTemp + 1) and rSetPtTempCool

Controller disabled

X

FALSE

Maximum value of ( rSetPtTemp + 1) and rSetPtTempCool

Limit violation

TRUE

TRUE

Current setpoint temperature + offset temperature

Normal operation

Legend: X = any\

Formation of the current supply air setpoint temperature rSetPtSUPTempCool

The current supply air setpoint temperature rSetPtSUPTempCool is formed from the supply air setpoint temperature, extended by a manual override module.\

Supply air setpoint temperature

eManModeNCool

rSetPtSUPTempCool

Notes

X

eMANNUM.Auto

Supply air setpoint temperature

Manual override module in automatic

X

eMANNUM.Man

rManValueCool

Manual override module in manual operation

Legend: X = any\

CODESYS

InOut:

Scope
Name
Type
Initial

Input

xEn

BOOL

Input

rActTemp

REAL

0

Input

rSetPtTemp

REAL

21

Input

rSetPtTempCool

REAL

24

Input

xEnCool

BOOL

Input

xFastHeatEn

BOOL

FALSE

Input

xFNCEn

BOOL

FALSE

Output

rSetPtSUPTemp

REAL

Output

rSetPtSUPTempCool

REAL

Output

rMinSUPTemp

REAL

Output

rMaxSUPTemp

REAL

Input Const

rPI_Tn

REAL

600

Input Const

rPI_Kp

REAL

1

Input Const

rMaxSUP

REAL

26

Input Const

rMaxRelativeSUP

REAL

6

Input Const

rMinSUP

REAL

16

Input Const

rMinRelativeSUP

REAL

-8

Input Const

tDelayControl

TIME

TIME#5m0s0ms

Input Const

rManValueCool

REAL

Input Const

eManModeNCool

eManNum

eManNum.Auto

Input Const

rManValue

REAL

Input Const

eManModeN

eManNum

eManNum.Auto

Last updated