OPPERMANN_T_MOD_I_XXX
OPPERMANN_T_MOD_I_XXX (FB)
OPPERMANN_T_MOD_I_XXX (FB)FUNCTION_BLOCK OPPERMANN_T_MOD_I_XXX
General
This is a temperature transmitter for ventilation ducts and for measurement in pipes / tanks
XXX = 50: 50mm XXX = 100: 100mm XXX = 150: 150mm XXX = 200: 200mm XXX = 250: 250mm XXX = 300: 300mm XXX = 450: 450mm
The configuration of the Modbus interface and other parameters is performed via NFC and app when a display is present (variant 1) The configuration of the Modbus interface and other parameters is performed via buttons when a display is present (variant 2)
The measurement value offset can be set in 10 steps using a rotary switch on the device. A termination resistor (120 ohm) can be activated / deactivated.
The Modbus interface is parameterized as follows without further settings:
RTU 9600 baud 8 data bits even parity 1 stop bit device address = 1
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Device address (1 .. 127)
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on each rising edge ) (Range: operation)
Input
xResError
BOOL
FALSE
Reinitialization of the output 'eErrorCodeCom' (on each rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rTempCelsius
REAL
Temperature in XX.X degrees Celsius
Output
rTempFahrenheit
REAL
Temperature in XX.X degrees Fahrenheit
Output
xSensorOffsetInDevice
BOOL
Indicator whether the calibration of the sensors must be performed in the device (TRUE = calibration in device required, FALSE = calibration in FB required)
Output
xAlarm
BOOL
General fault ( TRUE = fault )
Output
xAlarmCom
BOOL
General fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for operations influenced by the input 'xUpdateActual'
Last updated

