OPPERMANN_PV_MOD_ADX
OPPERMANN_PV_MOD_ADX (FB)
OPPERMANN_PV_MOD_ADX (FB)FUNCTION_BLOCK OPPERMANN_PV_MOD_ADX
Representation

General
This is a differential pressure - volume flow - transmitter with different measurement ranges:
PV MOD AD1: 0 - 1000 Pa PV MOD AD4: 0 - 4000 Pa
The configuration of the Modbus interface and other parameters is carried out via NFC and app when a display is present (variant 1). The configuration of the Modbus interface and other parameters is carried out via buttons when a display is present (variant 2).
The measurement value offset can be set in 10 steps using a rotary switch on the device. A manual zero-point adjustment is possible on the device. A terminating resistor (120 Ohm) can be activated / deactivated.
The Modbus interface is parameterized as follows without further settings:
RTU 9600 baud 8 data bits even parity 1 stop bit device address = 1
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enabled)
Input
byUnitId
BYTE
0
Device address (1 .. 127)
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge ) (range: operation)
Input
xResError
BOOL
FALSE
Reinitialization of the output ‘eErrorCodeCom’ ( on every rising edge )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rDifPressure
REAL
Differential pressure in Pa
Output
rVolumeFlow
REAL
Volume flow in m3/h
Output
rDevVoltage
REAL
Supply voltage for the device in volts
Output
xSensorOffsetInDevice
BOOL
Indicates whether sensor calibration must be performed in the device ( TRUE = calibration required in the device, FALSE = calibration required in the FB )
Output
xAlarm
BOOL
Collective fault (TRUE = fault)
Output
xAlarmCom
BOOL
Collective fault - communication (TRUE = fault)
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
Output
xBusy
BOOL
Communication indicator (TRUE = communication)
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the operations affected by the input 'xUpdateActual'
Last updated

