OPPERMANN_PV_MOD_ADX
OPPERMANN_PV_MOD_ADX (FB)
OPPERMANN_PV_MOD_ADX (FB)FUNCTION_BLOCK OPPERMANN_PV_MOD_ADX
Representation

General
This is a differential pressure - volume flow - transmitter with different measuring ranges:
PV
MODAD1: 0 - 1000 Pa PVMODAD4: 0 - 4000 Pa
The Modbus interface and other parameters are configured via NFC and app when a display is present (variant 1). The Modbus interface and other parameters are configured via buttons when a display is present (variant 2).
The measured value offset can be set in 10 stages using a rotary switch on the device. A manual zero-point adjustment is possible on the device. A termination resistor (120 ohms) can be activated / deactivated.
The Modbus interface is parameterized as follows without any further settings:
RTU 9600 baud 8 data bits even parity 1 stop bit device address = 1
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
Input
byUnitId
BYTE
0
Device address (1 .. 127)
Input
xUpdateActual
BOOL
FALSE
Updating the actual values (at every rising edge ) (range: operation)
Input
xResError
BOOL
FALSE
Reinitialization of the output eErrorCodeCom (with every
rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rDifPressure
REAL
Differential pressure in Pa
Output
rVolumeFlow
REAL
Volume flow in m3/h
Output
rDevVoltage
REAL
Supply voltage for the device in volts
Output
xSensorOffsetInDevice
BOOL
Indication of whether the sensors must be calibrated in the device (TRUE = calibration in the device required, FALSE = calibration in the FB required)
Output
xAlarm
BOOL
Collective fault (TRUE = fault)
Output
xAlarmCom
BOOL
Collective fault - communication (TRUE = fault)
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
Output
xBusy
BOOL
Communication indicator (TRUE = communication)
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes influenced by the input
xUpdateActual influenced
Last updated

