OPPERMANN_P_MOD_W16
OPPERMANN_P_MOD_W16 (FB)
OPPERMANN_P_MOD_W16 (FB)FUNCTION_BLOCK OPPERMANN_P_MOD_W16
General
This is a pressure transmitter for measurement in pipes and tanks (0.0 - 16.0 bar overpressure)
The configuration of the Modbus interface and other parameters is performed via NFC and app when a display is present (variant 1) The configuration of the Modbus interface and other parameters is performed via buttons when a display is present (variant 2)
The measurement value offset can be set in 10 steps via a rotary switch on the device. A terminating resistor (120 ohm) can be enabled/disabled.
The Modbus interface is parameterized as follows without further settings:
RTU 9600 baud 8 data bits even parity 1 stop bit device address = 1
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Device address (1 .. 127)
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on each rising edge ) (Range: operation)
Input
xResError
BOOL
FALSE
Reinitialization of the output 'eErrorCodeCom' (on each rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rPressure
REAL
Differential pressure in XX.XX bar
Output
xSensorOffsetInDevice
BOOL
Indicator whether the calibration of the sensors must be performed in the device (TRUE = calibration in device required, FALSE = calibration in FB required)
Output
xAlarm
BOOL
General fault ( TRUE = fault )
Output
xAlarmCom
BOOL
General fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for operations influenced by the input 'xUpdateActual'
Last updated

