DAIKIN_EKMBDXB7V1_IDU_FC04_2000_2383

DAIKIN_EKMBDXB7V1_IDU_FC04_2000_2383 (FB)

FUNCTION_BLOCK DAIKIN_EKMBDXB7V1_IDU_FC04_2000_2383

Short description

Recording of actual values - 1 of up to 64 Daikin - indoor units Typical application: Central control of Daikin - indoor units via the Daikin Modbus - interface EKMBDXB7V1\

Guidelines - Software creation

The following function codes (FC) are supported: 3, 4, 6 and 16 The following baud rates are supported: 9600 and 19200 bit/s For addressing, use the address values, not the register addresses (Address = Register - 1) Modbus addresses 1 - 15 can be set directly on the DIP switches in the interface. In FC03 a maximum of 32 registers may be requested in one query telegram (deviating from the Modbus standard) In FC04 a maximum of 32 registers may be requested in one query telegram (deviating from the Modbus standard) In FC16 a maximum of 30 registers may be written in one query telegram (deviating from the Modbus standard) The following transmission parameters were tested: 19200 Baud, 8-N-1 The interface supports the following exception codes: 0x81, 0x82 and 0x83 The number of control commands per indoor unit is limited to 7000 / year!!! Taking the tested transmission parameters into account, the time interval between the end of the response telegram and the next query telegram must be at least 22.5 ms All registers read with FC04 are always available up to date All registers read with FC03 are available up to date only once during each restart of the gateway &#xNAN;************** &#xNAN;* Functions * &#xNAN;************** In this FB the relevant actual values of all up to 64 indoor units are recorded and evaluated (FC04: addresses 2000 - 2383 ) They are available in the array ‘arstIndoorUnits_ActualValues_1’ separately for each indoor unit as a structure element. The structure element of an indoor unit is only updated if the corresponding read/write permission is present ( input ‘arxIndoorUnits_ReadWriteState’ ). Measurements - Synchronization: Class 4 \

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable of communication ( TRUE = enabled )

Input

byUnitId

BYTE

0

Device (interface) address (1 .. 15)

Input

xUpdateActual

BOOL

FALSE

Update of actual values ( on each rising edge )

Input

xResError

BOOL

FALSE

Reinitialization of the output ‘eErrorCodeCom’ (on each rising edge)

Input

arxIndoorUnits_ReadWriteState

ARRAY [1..4, 0..15] OF BOOL

Array with the read/write authorizations of the indoor units of all groups (1-00 … 4-15) 1st dimension: group, 2nd dimension: indoor unit number Array element = FALSE: no read/write authorization Array element = TRUE: read/write authorization

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

arstIndoorUnits_ActualValues_1

ARRAY [1..4, 0..15] OF EKMBDXB7V1_CURRENT_VALUES_1

Array with the actual values - 1 of the indoor units of all groups ( 1-00 … 4-15 ) 1st dimension: group, 2nd dimension: indoor unit number Array element = structure with the individual actual values

Output

xSensorOffsetInDevice

BOOL

Indication whether the calibration of the sensors of the indoor units must be performed in the indoor unit ( TRUE = calibration required in the device, FALSE = calibration required in the FB )

Output

xAlarm

BOOL

FALSE

Collective fault ( TRUE = fault )

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication ( TRUE = fault )

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication ( 0 = no error )

Output

xBusy

BOOL

Communication indicator ( TRUE = communication )

Input Const

tTimeUpdateActual

TIME

TIME#5s0ms

Update interval for the processes affected by the input ‘xUpdateActual’

Last updated