DAIKIN_EKMBDXB7V1_IDU_ERROR_STATES

DAIKIN_EKMBDXB7V1_IDU_ERROR_STATES (FB)

FUNCTION_BLOCK DAIKIN_EKMBDXB7V1_IDU_ERROR_STATES

Representation

Short description

Collection of the error states of up to 64 Daikin indoor units

Typical application: Central control of Daikin indoor units via the Daikin Modbus interface EKMBDXB7V1

Guidelines - Software creation

The following function codes (FC) are supported: 3, 4, 6 and 16. The following transmission rates are supported: 9600 and 19200 bit/s. For addressing, use the address specifications, not the register addresses (address = register - 1). The Modbus addresses 1 - 15 can be set directly on the DIP switches in the interface. In FC03, a maximum of 32 registers may be requested in one request telegram (deviating from the Modbus standard). In FC04, a maximum of 32 registers may be requested in one request telegram (deviating from the Modbus standard). In FC16, a maximum of 30 registers may be written in one request telegram (deviating from the Modbus standard). The following transmission parameters were tested: 19200 baud, 8-N-1. The interface supports the following exception codes: 0x81, 0x82 and 0x83. The number of control commands per indoor unit is limited to 7000/year!!! Taking the tested transmission parameters into account, the time between the end of the response telegram and the next request telegram must be at least 22.5 ms

All registers read with FC04 are always available up to date. All registers read with FC03 are only available once up to date during each restart of the gateway. Procedure for changing a setpoint (FC06 or FC16):

&#xNAN;************** &#xNAN;* Functions * &#xNAN;**************

In this FB, the error states of all up to 64 indoor units are collected and evaluated (FC04: addresses 3600 - 3727). They are available in the array arstIndoorUnits_ErrorStates separately for each indoor unit as a structure element. The structure element of an indoor unit is updated only if the corresponding write/read permission is present (input arxIndoorUnits_ReadWriteState).

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enable)

Input

byUnitId

BYTE

0

Address of the device (interface) (1 .. 15)

Input

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge )

Input

xResError

BOOL

FALSE

Reinitialization of the output eErrorCodeCom (with every rising edge)

Input

arxIndoorUnits_ReadWriteState

ARRAY [1 .. 4, 0 .. 15] OF BOOL

Array with the read/write permissions of the indoor units of all groups (1-00 … 4-15) 1st dimension: group, 2nd dimension: number of the indoor unit Array element = FALSE: no read/write permission Array element = TRUE: read/write permission

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

arstIndoorUnits_ErrorStates

ARRAY [1 .. 4, 0 .. 15] OF EKMBDXB7V1_ERROR_STATES

Array with the error states of the indoor units of all groups (1-00 … 4-15) 1st dimension: group, 2nd dimension: number of the indoor unit Array element = structure with the individual error states

Output

xAlarm

BOOL

FALSE

Collective fault (TRUE = fault)

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication (TRUE = fault)

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

Output

xBusy

BOOL

Communication indicator (TRUE = communication)

Input Const

tTimeUpdateActual

TIME

TIME#3s0ms

Update interval for the processes influenced by the input xUpdateActual influenced

Last updated