DAIKIN_EKMBDXB7V1_IDU_COM_STATES
DAIKIN_EKMBDXB7V1_IDU_COM_STATES (FB)
FUNCTION_BLOCK DAIKIN_EKMBDXB7V1_IDU_COM_STATES
Representation

Short description
Recording of the communication states of up to 64 Daikin indoor units
Typical application: Central control of Daikin indoor units via the Daikin Modbus interface EKMBDXB7V1
Guidelines - Software creation
The following function codes (FC) are supported: 3, 4, 6 and 16 The following transmission rates are supported: 9600 and 19200 bit/s For addressing, the address specifications are to be used, not the register addresses (address = register - 1) Modbus addresses 1 - 15 can be set directly on the DIP switches in the interface. In FC03, a maximum of 32 registers may be requested in a request telegram (deviating from the Modbus standard) In FC04, a maximum of 32 registers may be requested in a request telegram (deviating from the Modbus standard) In FC16, a maximum of 30 registers may be written in a request telegram (deviating from the Modbus standard) The following transmission parameters were tested: 19200 baud, 8-N-1 The following exception codes are supported by the interface: 0x81, 0x82 and 0x83 The number of control commands per indoor unit is limited to 7000 / year !!! Taking into account the tested transmission parameters, the time between the end of the response and the next request telegram must be at least 22.5 ms
All registers read with FC04 are always available with current data All registers read with FC03 are only updated once during each restart of the gateway
&#xNAN;************** &#xNAN;* Functions * &#xNAN;**************
In this FB, the messages Connected and Communication error of all up to 64 indoor units are recorded and evaluated. The current states are available in the arrays arxIndoorUnits_ConState (State Connected), arxIndoorUnits_ComState (State Communication error) and arxIndoorUnits_ReadWriteState (write and read permission) available separately for each indoor unit.
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
Input
byUnitId
BYTE
0
Address of the device (interface) (1 .. 15)
Input
xUpdateStates
BOOL
FALSE
State update (on every rising edge )
Input
xResError
BOOL
FALSE
Reinitialization of the output eErrorCodeCom (with every
rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
xInterfaceState
BOOL
FALSE
Interface state
Output
xOtherDIIIUnitPresent
BOOL
FALSE
Information whether another DIII unit (in addition to this interface) is present
Output
arxIndoorUnits_ConState
ARRAY [1 .. 4, 0 .. 15] OF
BOOL
FALSE: No TRUE: Yes (default value) Array with the connection states of the indoor units of all groups (1-00 … 4-15) 1st dimension: group, 2nd dimension: indoor unit number Array element = FALSE: no connection to the indoor unit Array element = TRUE: connection to the indoor unit
Output
arxIndoorUnits_ComState
ARRAY [1 .. 4, 0 .. 15] OF
BOOL
Array with the communication states of the indoor units of all groups (1-00 … 4-15) 1st dimension: group, 2nd dimension: indoor unit number Array element = FALSE: no communication error Array element = TRUE: with communication error
Output
arxIndoorUnits_ReadWriteState
ARRAY [1 .. 4, 0 .. 15] OF
BOOL
Array with the read/write permissions of the indoor units of all groups (1-00 … 4-15) 1st dimension: group, 2nd dimension: number of the indoor unit Array element = FALSE: no read/write permission Array element = TRUE: read/write permission
Output
xAlarm
BOOL
FALSE
Collective fault (TRUE = fault)
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication (TRUE = fault)
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
Output
xBusy
BOOL
Communication indicator (TRUE = communication)
Input Const
tTimeUpdateStates
TIME
TIME#3s0ms
Update interval for the operations that are influenced by the input
xUpdateStates influenced
Last updated

