DAIKIN_EKMBDXB7V1_IDU_COM_STATES

DAIKIN_EKMBDXB7V1_IDU_COM_STATES (FB)

FUNCTION_BLOCK DAIKIN_EKMBDXB7V1_IDU_COM_STATES

Short description

Detection of the communication states of up to 64 Daikin indoor units Typical application: Central control of Daikin indoor units via the Daikin Modbus interface EKMBDXB7V1\

Guidelines - Software creation

The following function codes (FC) are supported: 3, 4, 6 and 16 The following baud rates are supported: 9600 and 19200 bit/s For addressing, use the address values, not the register addresses (Address = Register - 1) Modbus addresses 1 - 15 can be set directly on the DIP switches in the interface. In FC03 a maximum of 32 registers may be requested in one query telegram (deviating from the Modbus standard) In FC04 a maximum of 32 registers may be requested in one query telegram (deviating from the Modbus standard) In FC16 a maximum of 30 registers may be written in one query telegram (deviating from the Modbus standard) The following transmission parameters were tested: 19200 Baud, 8-N-1 The interface supports the following exception codes: 0x81, 0x82 and 0x83 The number of control commands per indoor unit is limited to 7000 / year!!! Taking the tested transmission parameters into account, the time interval between the end of the response telegram and the next query telegram must be at least 22.5 ms All registers read with FC04 are always available up to date All registers read with FC03 are available up to date only once during each restart of the gateway &#xNAN;************** &#xNAN;* Functions * &#xNAN;************** This FB records and evaluates the messages 'Connected' and 'Communication error' of all up to 64 indoor units. The current states are available per indoor unit in the arrays 'arxIndoorUnits_ConState' (state 'Connected'), 'arxIndoorUnits_ComState' (state 'Communication error') and 'arxIndoorUnits_ReadWriteState' (write and read permission) separately. \

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable of communication ( TRUE = enabled )

Input

byUnitId

BYTE

0

Device (interface) address (1 .. 15)

Input

xUpdateStates

BOOL

FALSE

Update of states (on every rising edge )

Input

xResError

BOOL

FALSE

Reinitialization of the output ‘eErrorCodeCom’ (on each rising edge)

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

xInterfaceState

BOOL

FALSE

State of the interface

Output

xOtherDIIIUnitPresent

BOOL

FALSE

Information whether another DIII unit (in addition to this interface) is present

Output

arxIndoorUnits_ConState

ARRAY [1..4, 0..15] OF BOOL

FALSE: No TRUE: Yes (default value) Array with the connection states of the indoor units of all groups (1-00 … 4-15) 1st dimension: group, 2nd dimension: indoor unit number Array element = FALSE: no connection to the indoor unit Array element = TRUE: connection to the indoor unit

Output

arxIndoorUnits_ComState

ARRAY [1..4, 0..15] OF BOOL

Array with the communication states of the indoor units of all groups (1-00 … 4-15) 1st dimension: group, 2nd dimension: indoor unit number Array element = FALSE: without communication error Array element = TRUE: with communication error

Output

arxIndoorUnits_ReadWriteState

ARRAY [1..4, 0..15] OF BOOL

Array with the read/write authorizations of the indoor units of all groups (1-00 … 4-15) 1st dimension: group, 2nd dimension: indoor unit number Array element = FALSE: no read/write authorization Array element = TRUE: read/write authorization

Output

xAlarm

BOOL

FALSE

Collective fault ( TRUE = fault )

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication ( TRUE = fault )

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication ( 0 = no error )

Output

xBusy

BOOL

Communication indicator ( TRUE = communication )

Input Const

tTimeUpdateStates

TIME

TIME#3s0ms

Update interval for operations affected by the input ‘xUpdateStates’

Last updated