DAIKIN_EKMBDXB7V1_IDU_COM_STATES
DAIKIN_EKMBDXB7V1_IDU_COM_STATES (FB)
DAIKIN_EKMBDXB7V1_IDU_COM_STATES (FB)FUNCTION_BLOCK DAIKIN_EKMBDXB7V1_IDU_COM_STATES
Representation

Short description
Recording the communication states of up to 64 Daikin indoor units\n\nTypical application: Central control of Daikin indoor units via the Daikin Modbus interface EKMBDXB7V1\\
Guidelines - Software creation
The following function codes ( FC ) are supported: 3, 4, 6 and 16 The following transfer rates are supported: 9600 and 19200 bit/s For addressing, use the address values, not the register addresses ( address = register - 1 ) The Modbus addresses 1 - 15 can be set directly on the DIP switches in the interface. In FC03 a maximum of 32 registers may be requested in one request telegram ( deviating from the Modbus standard ) In FC04 a maximum of 32 registers may be requested in one request telegram ( deviating from the Modbus standard ) In FC16 a maximum of 30 registers may be written in one request telegram ( deviating from the Modbus standard ) The following transmission parameters were tested: 19200 Baud, 8-N-1 The interface supports the following exception codes: 0x81, 0x82 and 0x83 The number of control commands per indoor unit is limited to 7000 / year !!! Considering the tested transmission parameters, the time interval between the end of the response and the next request telegram must be at least 22.5 ms All registers read with FC04 are always available up to date All registers read with FC03 are available up to date only once during each restart of the gateway &#xNAN;************** &#xNAN;* Functions * &#xNAN;************** This FB records and evaluates the messages ‘Connected’ and ‘Communication error’ of all up to 64 indoor units.\nThe current states are available in the arrays ‘arxIndoorUnits_ConState’ (state ‘Connected’), ‘arxIndoorUnits_ComState’ (state ‘Communication error’)\nand ‘arxIndoorUnits_ReadWriteState’ (write and read permission) separately for each indoor unit.\n\\
InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Device address ( interface ) ( 1 .. 15 )
Input
xUpdateStates
BOOL
FALSE
Updating of states (on every rising edge )
Input
xResError
BOOL
FALSE
Reinitialization of the output 'eErrorCodeCom' ( on each rising edge )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
xInterfaceState
BOOL
FALSE
State of the interface
Output
xOtherDIIIUnitPresent
BOOL
FALSE
Information whether another DIII unit (in addition to\nthis interface) is present
Output
arxIndoorUnits_ConState
ARRAY [1..4, 0..15] OF BOOL
FALSE: No\nTRUE: Yes (default value)\nArray with the connection states of the indoor units of all groups (1-00 … 4-15)\n1st dimension: group, 2nd dimension: indoor unit number\nArray element = FALSE: no connection to the indoor unit\nArray element = TRUE: connection to the indoor unit
Output
arxIndoorUnits_ComState
ARRAY [1..4, 0..15] OF BOOL
Array with the communication states of the indoor units of all groups (1-00 … 4-15)\n1st dimension: group, 2nd dimension: indoor unit number\nArray element = FALSE: without communication error\nArray element = TRUE: with communication error
Output
arxIndoorUnits_ReadWriteState
ARRAY [1..4, 0..15] OF BOOL
Array with the read / write permissions of the indoor units of all groups ( 1-00 … 4-15 ) 1st dimension: group, 2nd dimension: indoor unit number Array element = FALSE: no read / write permission Array element = TRUE: read / write permission
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = Fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = Fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
xBusy
BOOL
Communication indicator ( TRUE = Communication )
Input Const
tTimeUpdateStates
TIME
TIME#3s0ms
Update interval for the operations influenced by the input ‘xUpdateStates’
Last updated

