DAIKIN_EKMBDXB7V1_IDU_COM_STATES
DAIKIN_EKMBDXB7V1_IDU_COM_STATES (FB)
DAIKIN_EKMBDXB7V1_IDU_COM_STATES (FB)FUNCTION_BLOCK DAIKIN_EKMBDXB7V1_IDU_COM_STATES
Short description
Detection of the communication states of up to 64 Daikin indoor units Typical application: Central control of Daikin indoor units via the Daikin Modbus interface EKMBDXB7V1\
Guidelines - Software creation
The following function codes (FC) are supported: 3, 4, 6 and 16 The following baud rates are supported: 9600 and 19200 bit/s For addressing, use the address values, not the register addresses (Address = Register - 1) Modbus addresses 1 - 15 can be set directly on the DIP switches in the interface. In FC03 a maximum of 32 registers may be requested in one query telegram (deviating from the Modbus standard) In FC04 a maximum of 32 registers may be requested in one query telegram (deviating from the Modbus standard) In FC16 a maximum of 30 registers may be written in one query telegram (deviating from the Modbus standard) The following transmission parameters were tested: 19200 Baud, 8-N-1 The interface supports the following exception codes: 0x81, 0x82 and 0x83 The number of control commands per indoor unit is limited to 7000 / year!!! Taking the tested transmission parameters into account, the time interval between the end of the response telegram and the next query telegram must be at least 22.5 ms All registers read with FC04 are always available up to date All registers read with FC03 are available up to date only once during each restart of the gateway &#xNAN;************** &#xNAN;* Functions * &#xNAN;************** This FB records and evaluates the messages 'Connected' and 'Communication error' of all up to 64 indoor units. The current states are available per indoor unit in the arrays 'arxIndoorUnits_ConState' (state 'Connected'), 'arxIndoorUnits_ComState' (state 'Communication error') and 'arxIndoorUnits_ReadWriteState' (write and read permission) separately. \
InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Device (interface) address (1 .. 15)
Input
xUpdateStates
BOOL
FALSE
Update of states (on every rising edge )
Input
xResError
BOOL
FALSE
Reinitialization of the output ‘eErrorCodeCom’ (on each rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
xInterfaceState
BOOL
FALSE
State of the interface
Output
xOtherDIIIUnitPresent
BOOL
FALSE
Information whether another DIII unit (in addition to this interface) is present
Output
arxIndoorUnits_ConState
ARRAY [1..4, 0..15] OF BOOL
FALSE: No TRUE: Yes (default value) Array with the connection states of the indoor units of all groups (1-00 … 4-15) 1st dimension: group, 2nd dimension: indoor unit number Array element = FALSE: no connection to the indoor unit Array element = TRUE: connection to the indoor unit
Output
arxIndoorUnits_ComState
ARRAY [1..4, 0..15] OF BOOL
Array with the communication states of the indoor units of all groups (1-00 … 4-15) 1st dimension: group, 2nd dimension: indoor unit number Array element = FALSE: without communication error Array element = TRUE: with communication error
Output
arxIndoorUnits_ReadWriteState
ARRAY [1..4, 0..15] OF BOOL
Array with the read/write authorizations of the indoor units of all groups (1-00 … 4-15) 1st dimension: group, 2nd dimension: indoor unit number Array element = FALSE: no read/write authorization Array element = TRUE: read/write authorization
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
tTimeUpdateStates
TIME
TIME#3s0ms
Update interval for operations affected by the input ‘xUpdateStates’
Last updated

