DAIKIN_EKMBDXB7V1_IDU_FC04_1000_1191
DAIKIN_EKMBDXB7V1_IDU_FC04_1000_1191 (FB)
DAIKIN_EKMBDXB7V1_IDU_FC04_1000_1191 (FB)FUNCTION_BLOCK DAIKIN_EKMBDXB7V1_IDU_FC04_1000_1191
Short description
Acquisition of configuration values - 1 of up to 64 Daikin - indoor units Typical application: Central control of Daikin - indoor units via the Daikin Modbus - interface EKMBDXB7V1\
Guidelines - Software creation
The following function codes (FC) are supported: 3, 4, 6 and 16 The following baud rates are supported: 9600 and 19200 bit/s For addressing use the address values, not the register addresses (address = register - 1) Modbus addresses 1 - 15 can be set directly on the DIP switches in the interface. In FC03 a maximum of 32 registers may be requested in one request telegram (deviating from the Modbus standard) In FC04 a maximum of 32 registers may be requested in one request telegram (deviating from the Modbus standard) In FC16 a maximum of 30 registers may be written in one request telegram (deviating from the Modbus standard) The following transmission parameters were tested: 19200 baud, 8-N-1 The interface supports the following exception codes: 0x81, 0x82 and 0x83 The number of control commands per indoor unit is limited to 7000 / year !!! Considering the tested transmission parameters, the time interval between the end of the response and the next request telegram must be at least 22.5 ms All registers read with FC04 are always available up to date All registers read with FC03 are available up to date only once during each gateway restart &#xNAN;************** &#xNAN;* Functions * &#xNAN;************** This FB collects and evaluates the relevant configuration values of all up to 64 indoor units (FC04: addresses 1000 - 1191) They are available in the array ‘arstIndoorUnits_ConfigValues_1’ separated for each indoor unit as a structure element. The structure element of an indoor unit is only updated if the corresponding read/write permission exists (input ‘arxIndoorUnits_ReadWriteState’). \
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Address of the device (interface) (1 .. 15)
Input
xUpdateConfig
BOOL
FALSE
Update of the configuration (on each rising edge) (read access)
Input
xResError
BOOL
FALSE
Reinitialization of the output 'eErrorCodeCom' (on each rising edge)
Input
arxIndoorUnits_ReadWriteState
ARRAY [1..4, 0..15] OF BOOL
Array with the read/write permissions of the indoor units of all groups (1-00 … 4-15) 1st dimension: group, 2nd dimension: indoor unit number Array element = FALSE: no read/write permission Array element = TRUE: read/write permission
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
arstIndoorUnits_ConfigValues_1
ARRAY [1..4, 0..15] OF EKMBDXB7V1_CONFIG_VALUES_1
Array with configuration values - 1 of the indoor units of all groups (1-00 … 4-15) 1st dimension: group, 2nd dimension: indoor unit number Array element = structure with the individual configuration values
Output
xAlarm
BOOL
FALSE
General fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
General fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
tTimeUpdateConfig
TIME
TIME#0ms
Update interval for the processes influenced by the input ‘xUpdateConfig’