DAIKIN_EKMBDXB7V1_IDU_FC04_1000_1191

DAIKIN_EKMBDXB7V1_IDU_FC04_1000_1191 (FB)

FUNCTION_BLOCK DAIKIN_EKMBDXB7V1_IDU_FC04_1000_1191

Short description

Acquisition of configuration values - 1 of up to 64 Daikin - indoor units Typical application: Central control of Daikin - indoor units via the Daikin Modbus - interface EKMBDXB7V1\

Guidelines - Software creation

The following function codes (FC) are supported: 3, 4, 6 and 16 The following baud rates are supported: 9600 and 19200 bit/s For addressing use the address values, not the register addresses (address = register - 1) Modbus addresses 1 - 15 can be set directly on the DIP switches in the interface. In FC03 a maximum of 32 registers may be requested in one request telegram (deviating from the Modbus standard) In FC04 a maximum of 32 registers may be requested in one request telegram (deviating from the Modbus standard) In FC16 a maximum of 30 registers may be written in one request telegram (deviating from the Modbus standard) The following transmission parameters were tested: 19200 baud, 8-N-1 The interface supports the following exception codes: 0x81, 0x82 and 0x83 The number of control commands per indoor unit is limited to 7000 / year !!! Considering the tested transmission parameters, the time interval between the end of the response and the next request telegram must be at least 22.5 ms All registers read with FC04 are always available up to date All registers read with FC03 are available up to date only once during each gateway restart &#xNAN;************** &#xNAN;* Functions * &#xNAN;************** This FB collects and evaluates the relevant configuration values of all up to 64 indoor units (FC04: addresses 1000 - 1191) They are available in the array ‘arstIndoorUnits_ConfigValues_1’ separated for each indoor unit as a structure element. The structure element of an indoor unit is only updated if the corresponding read/write permission exists (input ‘arxIndoorUnits_ReadWriteState’). \

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable communication ( TRUE = enabled )

Input

byUnitId

BYTE

0

Address of the device (interface) (1 .. 15)

Input

xUpdateConfig

BOOL

FALSE

Update of the configuration (on each rising edge) (read access)

Input

xResError

BOOL

FALSE

Reinitialization of the output 'eErrorCodeCom' (on each rising edge)

Input

arxIndoorUnits_ReadWriteState

ARRAY [1..4, 0..15] OF BOOL

Array with the read/write permissions of the indoor units of all groups (1-00 … 4-15) 1st dimension: group, 2nd dimension: indoor unit number Array element = FALSE: no read/write permission Array element = TRUE: read/write permission

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

arstIndoorUnits_ConfigValues_1

ARRAY [1..4, 0..15] OF EKMBDXB7V1_CONFIG_VALUES_1

Array with configuration values - 1 of the indoor units of all groups (1-00 … 4-15) 1st dimension: group, 2nd dimension: indoor unit number Array element = structure with the individual configuration values

Output

xAlarm

BOOL

FALSE

General fault ( TRUE = fault )

Output

xAlarmCom

BOOL

FALSE

General fault - communication ( TRUE = fault )

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication ( 0 = no error )

Output

xBusy

BOOL

Communication indicator ( TRUE = communication )

Input Const

tTimeUpdateConfig

TIME

TIME#0ms

Update interval for the processes influenced by the input ‘xUpdateConfig’