# BELIMO\_VRU\_D3\_BAC\_EASY

## `BELIMO_VRU_D3_BAC_EASY` (FB)

`FUNCTION_BLOCK` BELIMO\_VRU\_D3\_BAC\_EASY

### Darstellung

<figure><img src="/files/8ZvVsQ1dhnIuttQd3Khq" alt=""><figcaption></figcaption></figure>

InOut:

| Scope       | Name                    | Type                                | Initial                                          | Comment                                                                                                                                                                                                                                                 |
| ----------- | ----------------------- | ----------------------------------- | ------------------------------------------------ | ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
| Input       | `xEn`                   | `BOOL`                              | TRUE                                             | Freigabe / Sperrung der Kommunikation (TRUE = Freigabe)                                                                                                                                                                                                 |
| Input       | `byUnitId`              | `BYTE`                              | 0                                                | Adresse des Geräts                                                                                                                                                                                                                                      |
| Input       | `xUpdateActual`         | `BOOL`                              | FALSE                                            | <p>Aktualisierung der Istwerte (bei jeder ansteigenden Flanke<br>)</p>                                                                                                                                                                                  |
| Input       | `xUpdateSetp`           | `BOOL`                              | FALSE                                            | <p>Aktualisierung der Sollwerte (bei jeder ansteigenden Flanke<br>)</p>                                                                                                                                                                                 |
| Input       | `xResError`             | `BOOL`                              | FALSE                                            | <p>Reinitialisierung der Ausgänge <code>eErrorCodeCom</code> bzw.<br><code>stErrorCodeDev</code> auf dem fehlerfreien Zustand (bei jeder<br>ansteigenden Flanke)</p>                                                                                    |
| Input       | `rSetpPerc`             | `REAL`                              | 0.0                                              | Sollwert in % (0.0 - 100.0 %) je nach Applikation                                                                                                                                                                                                       |
| Input       | `eOverrideCon`          | BELIMO\_VRU\_D3\_BAC\_OVERRIDE\_CON | BELIMO\_VRU\_D3\_BAC\_OVERRIDE\_CON.NO\_OVERRIDE | <p>Volumenstromregelung: Sollwert - Volumenstrom in % (0.0 - 100.0 %) (0.0 % = Vmin, 100.0 % = Vmax)<br>Zwangsübersteuerung des Luftklappe (0 = keine)</p>                                                                                              |
| Inout       | `ModbusClient`          | `ModbusClientBase`                  |                                                  | Client des Geräts                                                                                                                                                                                                                                       |
| Output      | `rVminM3H`              | `REAL`                              |                                                  | Minimalwert - Volumenstrom in m3/h                                                                                                                                                                                                                      |
| Output      | `rVmaxM3H`              | `REAL`                              |                                                  | Maximalwert - Volumenstrom in m3/h                                                                                                                                                                                                                      |
| Output      | `rVnomM3H`              | `REAL`                              |                                                  | Nennvolumenstrom in m3/h                                                                                                                                                                                                                                |
| Output      | `rVolFlowM3H`           | `REAL`                              |                                                  | Istwert des Volumenstroms in m3/h                                                                                                                                                                                                                       |
| Output      | `rSetpPercFb`           | `REAL`                              |                                                  | Rückmeldung des Sollwerts in % (0.0 - 100.0 %)                                                                                                                                                                                                          |
| Output      | `eCommandFb`            | BELIMO\_VRU\_D3\_BAC\_COMMAND       |                                                  | Rückmeldung der Auslösung von Testfunktionen (0 = keine)                                                                                                                                                                                                |
| Output      | `eOverrideConFb`        | BELIMO\_VRU\_D3\_BAC\_OVERRIDE\_CON |                                                  | <p>Rückmeldung der Zwangsübersteuerung des Luftklappe (0 =<br>keine)</p>                                                                                                                                                                                |
| Output      | `xAlarm`                | `BOOL`                              | FALSE                                            | Sammelstörung (TRUE = Störung)                                                                                                                                                                                                                          |
| Output      | `xAlarmCom`             | `BOOL`                              | FALSE                                            | Sammelstörung - Kommunikation (TRUE = Störung)                                                                                                                                                                                                          |
| Output      | `eErrorCodeCom`         | ModbusErrorCode                     |                                                  | Fehlercode - Kommunikation (0 = kein Fehler)                                                                                                                                                                                                            |
| Output      | `stErrorCodeDev`        | `STRING`                            |                                                  | String mir den Nummern der aktiven Gerätefehler                                                                                                                                                                                                         |
| Output      | `xBusy`                 | `BOOL`                              |                                                  | Kommunikationsanzeige (TRUE = Kommunikation)                                                                                                                                                                                                            |
| Input Const | `eCommand`              | BELIMO\_VRU\_D3\_BAC\_COMMAND       | BELIMO\_VRU\_D3\_BAC\_COMMAND.NO\_COMMAND        | Auslösung von Testfunktionen (0 = keine)                                                                                                                                                                                                                |
| Input Const | `xSetpVolumeFlowMinMax` | `BOOL`                              | FALSE                                            | <p>Auslösung der Übertragung der Parameter <code>rSetpVolumeFlowMin</code><br>bzw. <code>rSetpVolumeFlowMax</code> (bei jeder ansteigenden Flanke)</p>                                                                                                  |
| Input Const | `rSetpVolumeFlowMax`    | `REAL`                              | 2000.0                                           | <p>Sollwert für den maximalen Volumenstrom in der ausgewählten<br>Volumenstromeinheit (bei rSetpVolFlowPerc = 100.0 %)</p>                                                                                                                              |
| Input Const | `rSetpVolumeFlowMin`    | `REAL`                              | 500.0                                            | <p>Sollwert für den minimalen Volumenstrom in der ausgewählten<br>Volumenstromeinheit (bei rSetpVolFlowPerc = 0.0 %)</p>                                                                                                                                |
| Input Const | `tBusFailureTimeOut`    | `TIME`                              | TIME#10s0ms                                      | <p>Zeitdauer für die Aktivierung des Zustands<br><code>Kommunikationsfehler</code> (t = 0s = deaktiviert, bei t >= 10s<br>(mindestens 10 s) muss der Parameter <code>rSetpVolFlowPerc</code><br>zyklisch mit einem Zeitdazer < t übertragen werden)</p> |
| Input Const | `rBusFailurePos`        | `REAL`                              | 100.0                                            | <p>Position der Klappe bei einem Busausfall (in %, 100% =<br>offen)</p>                                                                                                                                                                                 |
| Input Const | `tTimeUpdateSetp`       | `TIME`                              | TIME#45s0ms                                      | <p>Updateintervall für die Vorgänge, die durch den Eingang<br><code>xUpdateSetp</code> beeinflusst werden</p>                                                                                                                                           |
| Input Const | `tTimeUpdateActual`     | `TIME`                              | TIME#3s0ms                                       | <p>Updateintervall für die Vorgänge, die durch den Eingang<br><code>xUpdateActual</code> beeinflusst werden</p>                                                                                                                                         |


---

# Agent Instructions: Querying This Documentation

If you need additional information that is not directly available in this page, you can query the documentation dynamically by asking a question.

Perform an HTTP GET request on the current page URL with the `ask` query parameter:

```
GET https://support.powerio.com/hub/codesys-hvac/hvac-modbus-library/functionblocks/belimo/belimo_vru_d3_bac_easy.md?ask=<question>
```

The question should be specific, self-contained, and written in natural language.
The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.