TROX_XM0
TROX_XM0 (FB)
TROX_XM0 (FB)FUNCTION_BLOCK TROX_XM0
Representation

InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
Input
byUnitId
BYTE
0
Device address
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints (on every rising edge )
Input
xResError
BOOL
FALSE
Reinitialization of the outputs eErrorCodeCom or
xErrorCodeDev to the fault-free state (on every rising edge)
Input
rSetpVolFlowPerc
REAL
0.0
Setpoint - volume flow in % (0.0 - 100.0 %) (0.0 % = Vmin, 100.0 % = Vmax)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rVnomUnit
REAL
Rated volume flow in the selected volume flow unit
Output
rVminUnit
REAL
Minimum value - volume flow in the selected volume flow unit
Output
rVmaxUnit
REAL
Maximum value - volume flow in the selected volume flow unit
Output
rDamperPosPerc
REAL
Absolute position of the air damper in percent (0.0% = Closed, 100.0% = Open)
Output
rDamperPosDegree
REAL
Absolute position of the air damper in degrees
Output
rVolFlowPerc
REAL
Actual value of the volume flow in percent of the rated volume flow
Output
rVolFlowUnit
REAL
Actual value of the volume flow in the selected volume flow unit
Output
eSetpSourceFb
TROX_XM0_SETP_SOURCE
Feedback of the source for the setpoint (2 = Bus)
Output
rSensorValue
REAL
Current actual value of the sensor in mV
Output
xSensorOffsetInDevice
BOOL
Indication of whether the sensors must be calibrated in the device (TRUE = calibration in the device required, FALSE = calibration in the FB required)
Output
xAlarm
BOOL
FALSE
Collective fault (TRUE = fault)
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication (TRUE = fault)
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
Output
stErrorCodeDev
STRING
String with the numbers of the active device errors
Output
xBusy
BOOL
Communication indicator (TRUE = communication)
Input Const
rSensorValueOffset
REAL
0.0
Constant measured value offset for the transmitted voltage - actual value
Input Const
eSetpSource
TROX_XM0_SETP_SOURCE
TROX_XM0_SETP_SOURCE.BUS_IN_BUS_OUT
Influence: Outputs: rSensorValue Source for the setpoint (2 = Bus)
Input Const
eOverrideCon
TROX_XM0_OVERRIDE_CON
TROX_XM0_OVERRIDE_CON.NO_OVERRIDE
Forced override of the air damper (0 = none)
Input Const
eCommand
TROX_XM0_COMMAND
TROX_XM0_COMMAND.NO_COMMAND
Triggering of test functions (0 = none)
Input Const
eVolumeFlowUnit
TROX_XM0_VOLUMEFLOW_UNIT
TROX_XM0_VOLUMEFLOW_UNIT.M3_PER_H
Unit for the specification of the absolute volume flows (1 = m3/h)
Input Const
xSetpVolumeFlowMinMax
BOOL
FALSE
Triggering the transfer of the parameters rSetpVolumeFlowMin
or rSetpVolumeFlowMax (on every rising edge)
Input Const
rSetpVolumeFlowMax
REAL
300.0
Setpoint for the maximum volume flow in the selected volume flow unit (at rSetpVolFlowPerc = 100.0 %)
Input Const
rSetpVolumeFlowMin
REAL
100.0
Setpoint for the minimum volume flow in the selected volume flow unit (at rSetpVolFlowPerc = 0.0 %)
Input Const
tTimeOut
TIME
TIME#10s0ms
Duration for activation of the state
Communication error
Input Const
eBusFailureCommand
TROX_XM0_BUS_FAILURE
TROX_XM0_BUS_FAILURE.NO_FAILURE
Definition of the behavior in the event of a bus failure (0 = no action)
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the processes influenced by the input
xUpdateSetp influenced
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes influenced by the input
xUpdateActual influenced
Last updated

