TROX_BM0
TROX_BM0 (FB)
TROX_BM0 (FB)FUNCTION_BLOCK TROX_BM0
Representation

InOut:
Input
xEn
BOOL
TRUE
Enable / disable of communication ( TRUE = enabled )
Input
byUnitId
BYTE
0
Address of the device
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
xUpdateSetp
BOOL
FALSE
Update of setpoint values (on every rising edge )
Input
xResError
BOOL
FALSE
Reinitialization of the outputs ‘eErrorCodeCom’ and/or ‘stErrorCodeDev’ to the error-free state (on every rising edge )
Input
rSetpVolFlowPerc
REAL
0.0
Setpoint - volume flow in % ( 0.0 - 100.0 % ) ( 0.0 % = Vmin, 100.0 % = Vmax )
Input
xEnDevice
BOOL
FALSE
Enable / disable of the volume flow controller ( FALSE = forced control CLOSED, TRUE = forced control NONE )
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
rVminUnit
REAL
Minimum value - volume flow in the selected volume flow unit
Output
rVmaxUnit
REAL
Maximum value - volume flow in the selected volume flow unit
Output
rVnomUnit
REAL
Nominal volume flow in the selected volume flow unit
Output
rDamperPosPerc
REAL
Absolute position of the damper in percent ( 0.0% = Closed, 100.0% = Open )
Output
rDamperPosDegree
REAL
Absolute position of the damper in degrees
Output
rVolFlowPerc
REAL
Actual value of the volume flow in percent of the nominal volume flow
Output
rVolFlowUnit
REAL
Actual value of the volume flow in the selected volume flow unit
Output
rSetpVolFlowPercFb
REAL
Feedback of the setpoint - volume flow in % ( 0.0 - 100.0 % ) ( 0.0 % = Vmin, 100.0 % = Vmax )
Output
eCommandFb
TROX_BM0_COMMAND
Feedback of the triggering of test functions ( 0 = none )
Output
eOverrideConFb
TROX_BM0_OVERRIDE_CON
Feedback of the forced override of the damper ( 0 = none )
Output
eActuatorType
TROX_BM0_ACTUATOR_TYPE
Type of the actuator
Output
eVolumeFlowUnitFb
TROX_BM0_VOLUMEFLOW_UNIT
Feedback of the unit for the absolute volume flow values ( 1 = m3/h )
Output
eSetpSourceFb
TROX_BM0_SETP_SOURCE
Feedback of the source for the setpoint ( 0 = Analog, 1 = Bus )
Output
eBusTermin
TROX_BM0_BUS_TERMINATION
State of the Modbus termination resistor ( 1 = Active )
Output
eSensorTypeFb
TROX_BM0_SENSOR_TYPE
Feedback of the type of the connected sensor ( 0 = none )
Output
sSerialNum
STRING
Serial number of the device
Output
wFirmwareVer
WORD
Firmware version of the device
Output
rSensorValue
REAL
Current actual value of the sensor in mV
Output
xSensorOffsetInDevice
BOOL
Indication whether sensor calibration must be performed in the device ( TRUE = calibration in device required, FALSE = calibration in FB required )
Output
rSetpAnalog
REAL
Setpoint in XXX.X % ( 0.0 - 100.0 % ) based on the sensor
Output
xAlarm
BOOL
FALSE
Collective fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
stErrorCodeDev
STRING
String with the numbers of the active device errors
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
rSensorValueOffset
REAL
0.0
Constant measurement offset for the transmitted voltage actual value
Input Const
eSensorType
TROX_BM0_SENSOR_TYPE
TROX_BM0_SENSOR_TYPE.NO_SENSOR
Influence: Outputs: rSensorValue Type of the connected sensor ( 0 = none )
Input Const
eSetpSource
TROX_BM0_SETP_SOURCE
TROX_BM0_SETP_SOURCE.BUS
Source for the setpoint ( 0 = Analog, 1 = Bus )
Input Const
eControlMode
TROX_BM0_CONTROL_MODE
TROX_BM0_CONTROL_MODE.CLOSED_LOOP
Type of control / regulation ( 0 = Open Loop = Position control, 1 = Closed Loop = Volume flow control )
Input Const
eCommand
TROX_BM0_COMMAND
TROX_BM0_COMMAND.NO_COMMAND
Triggering of test functions ( 0 = none )
Input Const
eVolumeFlowUnit
TROX_BM0_VOLUMEFLOW_UNIT
TROX_BM0_VOLUMEFLOW_UNIT.M3_PER_H
Unit for the absolute volume flow values ( 1 = m3/h )
Input Const
xSetpVolumeFlowMinMax
BOOL
FALSE
Triggering of the transmission of the parameters ‘rSetpVolumeFlowMin’ or ‘rSetpVolumeFlowMax’ ( on every rising edge )
Input Const
rSetpVolumeFlowMax
REAL
180.0
Setpoint for the maximum volume flow in the selected volume flow unit ( when rSetpVolFlowPerc = 100.0 % )
Input Const
rSetpVolumeFlowMin
REAL
0.0
Setpoint for the minimum volume flow in the selected volume flow unit ( when rSetpVolFlowPerc = 0.0 % )
Input Const
tTimeOut
TIME
TIME#10s0ms
Duration for the activation of the state ‘communication error’ ( t = 0s = disabled, for t > 0s ( at least 10 s ) the parameter ‘rSetpVolFlowPerc’ must be transmitted cyclically with a time period < t )
Input Const
eBusFailureCommand
TROX_BM0_BUS_FAILURE
TROX_BM0_BUS_FAILURE.LAST_SETPOINT
Definition of the behavior in case of a bus failure ( 0 = last setpoint )
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the processes influenced by the input ‘xUpdateSetp’
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes influenced by the input ‘xUpdateActual’
Last updated

