TROX_FSL_CONTROL_3

TROX_FSL_CONTROL_3 (FB)

FUNCTION_BLOCK TROX_FSL_CONTROL_3

Representation

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enable)

Input

byUnitId

BYTE

0

Device address

Input

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge )

Input

xUpdateSetp

BOOL

FALSE

Update of setpoints (on every rising edge )

Input

eOpMode

TROX_FSL_CONTROL_3_OP_MODE

TROX_FSL_CONTROL_3_OP_MODE.OFF

Operating mode of the device — preset

Input

eOpType

TROX_FSL_CONTROL_3_OP_TYPE

TROX_FSL_CONTROL_3_OP_TYPE.STANDBY

Operating mode of the device — default

Input

eOpTypeOverride

TROX_FSL_CONTROL_3_OP_TYPE_OVERRIDE

TROX_FSL_CONTROL_3_OP_TYPE_OVERRIDE.NO_OVERRIDE

Operating mode override of the device — default

Input

rTempOda

REAL

0.0

Current outdoor temperature in degrees Celsius — default

Input

rTempLimitCoolPresence

REAL

22.2

Upper room temperature limit for cooling in degrees Celsius in presence mode — default

Input

rTempLimitHeatPresence

REAL

21.8

Lower room temperature limit for heating in degrees Celsius in presence mode — default

Input

rTempRoom

REAL

20.0

Current room temperature in degrees Celsius — default

Input

rSpTempRoom

REAL

22.0

Current room setpoint temperature in degrees Celsius — default

Input

rSpTempRoomOffset

REAL

0.0

Current room setpoint temperature offset in degrees Celsius — default

Input

rSpTempSupply

REAL

22.0

Current supply air setpoint temperature in degrees Celsius — default

Input

rSpTempSupplyOffset

REAL

0.0

Current supply air setpoint temperature offset in degrees Celsius — default

Input

rRoomHumidity

REAL

50.0

Relative room humidity in percent — default

Input

xChangeOver

BOOL

FALSE

Notification of the connected medium (FALSE = heating medium, TRUE = cooling medium) — default

Input

rSpFanLevel

REAL

3.0

Setpoint for fan speed (1.0 = level 1, 2.0 = level 2, … 5.0 = level 5) — default

Input

rRoomAirQuality

REAL

700.0

Room air quality in ppm — default

Input

rOutsAirQuality

REAL

400.0

Outdoor air quality in ppm — default

Input

rVolumeFlowDiff

REAL

0.0

Volume flow difference in m3/h

Input

xFire

BOOL

FALSE

Status of fire alarm (TRUE = active) — default

Input

xWindow

BOOL

FALSE

Status of window contact (TRUE = active) — default

Input

xExtraTime

BOOL

FALSE

Status of overtime activation (TRUE = active) — default

Input

xFilterReset

BOOL

FALSE

Status of filter reset (TRUE = active) — default

Input

xResError

BOOL

FALSE

Reinitialization of the outputs eErrorCodeCom in the fault-free state (on each rising edge)

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

eOpModeFb

TROX_FSL_CONTROL_3_OP_MODE

Operating mode of the device — feedback

Output

eOpTypeFb

TROX_FSL_CONTROL_3_OP_TYPE

Operating mode of the device — feedback

Output

eOpTypeOverrideFb

TROX_FSL_CONTROL_3_OP_TYPE_OVERRIDE

Operating mode override of the device — feedback

Output

eOpStateFB

TROX_FSL_CONTROL_3_OP_STATE

Operating status of the device — feedback

Output

eVentTypeFb

TROX_FSL_CONTROL_3_VENT_TYPE

Ventilation type of the device — feedback

Output

rTempSupplyFb

REAL

Current supply air temperature in degrees Celsius — feedback

Output

rTempOdaFb

REAL

Current outdoor temperature in degrees Celsius — feedback

Output

rTempRoomFb

REAL

Current room temperature in degrees Celsius — feedback

Output

rTempReturnFlowFb

REAL

Current return temperature in degrees Celsius — feedback

Output

rTempFlowFb

REAL

Current flow temperature in degrees Celsius — feedback

Output

rTempOffsetFb

REAL

Current room/supply air temperature offset in degrees Celsius — feedback

Output

xExtraTimeFb

BOOL

Status of overtime activation (TRUE = active) — feedback

Output

rTempLimitCoolFb

REAL

Upper room temperature limit for cooling in degrees Celsius — feedback

Output

rTempLimitHeatFb

REAL

Lower room temperature limit for heating in degrees Celsius — feedback

Output

rTempSetpSupplyFb

REAL

Supply air setpoint temperature in degrees Celsius — feedback

Output

eFanLevelFb

TROX_FSL_CONTROL_3_FAN_LEVEL

Fan speed of the device — feedback

Output

rRoomHumidityFb

REAL

Relative room humidity in percent — feedback

Output

rRoomAirQualityFb

REAL

Room air quality in ppm — feedback

Output

rVolumeFlowOdaFb

REAL

Volume flow in outdoor air in m3/h — feedback

Output

rVolumeFlowExhFb

REAL

Volume flow in exhaust air in m3/h — feedback

Output

xWindowFb

BOOL

Status of window contact (TRUE = active) — feedback

Output

xFireFb

BOOL

Status of fire alarm (TRUE = active) — feedback

Output

rSystemDevices

REAL

Number of devices in the network (1x master and 1x slave = 2 devices)

Output

eDemandRoom

TROX_FSL_CONTROL_3_DEMAND_ROOM

Display of the room heating / cooling demand

Output

eDemandSupply

TROX_FSL_CONTROL_3_DEMAND_SUPPLY

Display of the supply air heating / cooling demand

Output

rValvePosHeatMas

REAL

Control - heating valve - master in percent

Output

rValvePosCoolMas

REAL

Control - cooling valve - master in percent

Output

arrTempSupplySla

ARRAY [1 .. 10] OF REAL

Current supply air temperatures of the slaves [ Slave 1 - Slave 10 ] in degrees Celsius

Output

arrValvePosHeatSla

ARRAY [1 .. 10] OF REAL

Current control signals for the heating valves of the slaves [ Slave 1 - Slave 10 ] in degrees Celsius

Output

arrValvePosCoolSla

ARRAY [1 .. 10] OF REAL

Current control signals for the cooling valves of the slaves [ Slave 1 - Slave 10 ] in degrees Celsius

Output

sAlarmA

STRING

Collective fault - Alarm A (partially shut down)

Output

sAlarmB

STRING

Collective fault - Alarm B (non-shut-down)

Output

xAlarm

BOOL

FALSE

Collective fault (TRUE = fault)

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication (TRUE = fault)

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

Output

xBusy

BOOL

Communication indicator (TRUE = communication)

Input Const

diAdrOffset

DINT

0

Offset for calculating the Modbus addresses (from the Modbus registers) (permitted range: -1, 0, +1)

Input Const

tTimeUpdateSetp

TIME

TIME#45s0ms

Update interval for the processes influenced by the input xUpdateSetp influenced

Input Const

tTimeUpdateActual

TIME

TIME#3s0ms

Update interval for the processes influenced by the input xUpdateActual influenced

Last updated