THERMOKON_WRF07

THERMOKON_WRF07 (FB)

FUNCTION_BLOCK THERMOKON_WRF07

General

Notes:

The setpoint / parameter 'eMode' currently (16.05.2022) only affects the formation of the room set temperature 'rSetpTemp' and the setpoint temperature offset 'rOffset'.

The configuration registers (R0 - R69) or coils (C0 - C5) are always set for operation of the WRF07 as a pure room control device (i.e. without its own internal regulation).

* Device configuration *

The current device configuration is stored in registers 0 - 69 and in coils 0 - 5. It is read once at restart / once at every rising edge (xUpdateConfigRead) / cyclically (tTimeUpdateConfigRead) and saved into the arrays '_arwKonfiguration_0' and 'arbyKonfiguration_1'.

During operation, registers 2 - 69 and coils 0 - 3 are rewritten upon a single restart / when values change ('_arwKonfiguration_2' and 'arbyKonfiguration_3'). Additionally, this write access can be triggered by a rising edge at the input 'xUpdateConfigWrite'. This write access must not occur cyclically because the number of write operations is limited (EEPROM).

The device configuration cannot be reset to factory defaults; the default values are stored in the arrays '_arwKonfiguration_4' and 'arbyKonfiguration_5' and can be loaded/written into the device via the input 'xResDefault'.

Setpoint / parameter 'rOffsetRange': A change is transmitted immediately without error, however the new offset is only used after a cold start of the WRF07.

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable communication ( TRUE = enabled )

Input

byUnitId

BYTE

0

Address of the device ( 1 .. 247 ) ( 1 .. 63 via DIP switch, 1 .. 247 via Modbus commands )

Input

xUpdateActual

BOOL

FALSE

Update of actual values (on each rising edge ) (Range: operation)

Input

xUpdateSetp

BOOL

FALSE

Update of setpoint values (on every rising edge )

Input

xUpdateConfigRead

BOOL

FALSE

Update of configuration (read access) (on each rising edge)

Input

xUpdateConfigWrite

BOOL

FALSE

Update of the configuration (write access) ( on each rising edge)

Input

xUpdateStates

BOOL

FALSE

Update of states (registers 256 - 257) (on each rising edge)

Input

xResDefault

BOOL

FALSE

Reset configuration to default state ( registers 0 - 69) (coils 0 - 5) (on each rising edge)

Input

rSetpTempBase

REAL

22.0

Base setpoint temperature ( degrees Celsius )

Input

xLED9

BOOL

FALSE

Control of LED9 ( TRUE = On )

Input

xEnOffset

BOOL

FALSE

Enable / disable the influence of the setpoint adjuster ‘rOffset’ on the setpoint temperature ( ‘rSetpTemp’ )

Input

xResError

BOOL

FALSE

Reinitialization of the output 'eErrorCodeCom' (on each rising edge)

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

eDeviceType

THERMOKON_WRF07_DEVICE_TYPE

Type of device

Output

eUnitFb

THERMOKON_WRF07_UNIT

Current unit system of the device — feedback

Output

eRegulationModeFb

THERMOKON_WRF07_REGULATION_MODE_FEEDBACK

Current controller mode of the device

Output

rRoomTemp

REAL

Current room temperature in degrees Celsius

Output

rSetpTempBaseFb

REAL

Base set temperature (degrees Celsius) — feedback

Output

rOffset

REAL

Current offset of the room set temperature in K

Output

rSetpTemp

REAL

Current setpoint temperature in degrees Celsius

Output

rRelHumidity

REAL

Relative room humidity in percent

Output

xSensorOffsetInDevice

BOOL

Indicator whether the calibration of the sensors must be performed in the device (TRUE = calibration in device required, FALSE = calibration in FB required)

Output

rDewPointTemp

REAL

Dew point temperature in degrees Celsius or Fahrenheit

Output

rAbsHumidity

REAL

Absolute room humidity in g/m3 or grain/ft3

Output

rEnthalpy

REAL

Enthalpy in kJ/kg or BTU/lb3

Output

xButton1

BOOL

FALSE

Actuation of button 1 ( RAW, pulse with duration ‘tTimeButtonPulse’ )

Output

eFunctionButton1Fb

THERMOKON_WRF07_BUTTON_FUNCTION

Function of button 1 — feedback

Output

xLED9Fb

BOOL

FALSE

State of LED 9 — feedback (TRUE = On)

Output

eFunctionLED9Fb

THERMOKON_WRF07_LED_FUNCTION

Function of LED 9 — feedback

Output

xDI1

BOOL

FALSE

State of digital input 1 (assignment depending on function 'eFunctionDI1') (FALSE = Open, TRUE = Closed)

Output

eFunctionDI1Fb

THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION

Function of digital input 1 — feedback

Output

xDI2

BOOL

FALSE

State of digital input 2 (assignment depending on function 'eFunctionDI2') (FALSE = Open, TRUE = Closed)

Output

eFunctionDI2Fb

THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION

Function of digital input 2 — feedback

Output

xDI3

BOOL

FALSE

State of digital input 3 (assignment depending on function 'eFunctionDI1') (FALSE = Open, TRUE = Closed)

Output

eFunctionDI3Fb

THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION

Function of digital input 3 — feedback

Output

xDI4

BOOL

FALSE

State of digital input 4 (assignment depending on function 'eFunctionDI2') (FALSE = Open, TRUE = Closed)

Output

eFunctionDI4Fb

THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION

Function of digital input 4 — feedback

Output

xAlarm

BOOL

FALSE

General fault ( TRUE = fault )

Output

xAlarmCom

BOOL

FALSE

General fault - communication ( TRUE = fault )

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication ( 0 = no error )

Output

xBusy

BOOL

Communication indicator ( TRUE = communication )

Input Const

eUnit

THERMOKON_WRF07_UNIT

THERMOKON_WRF07_UNIT.SI

Current unit system of the device

Input Const

rRoomHumityOffset

REAL

0.0

Offset of the room humidity ( for calibration of the humidity sensor ) in percent

Input Const

eFunctionLED9

THERMOKON_WRF07_LED_FUNCTION

THERMOKON_WRF07_LED_FUNCTION.EXTERNAL_CONTROL

Function of LED 9

Input Const

eFunctionDI4

THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION

THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION.NORMALLY_OPEN_CONTACT

Function of digital input 4

Input Const

eFunctionDI3

THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION

THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION.NORMALLY_OPEN_CONTACT

Function of digital input 3

Input Const

eFunctionDI2

THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION

THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION.NORMALLY_OPEN_CONTACT

Function of digital input 2

Input Const

eFunctionDI1

THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION

THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION.NORMALLY_OPEN_CONTACT

Function of digital input 1

Input Const

eFunctionButton1

THERMOKON_WRF07_BUTTON_FUNCTION

Function of button 1

Input Const

rSetpTempMax

REAL

26.0

Absolute maximum - setpoint temperature ( degrees Celsius )

Input Const

rSetpTempMin

REAL

18.0

Absolute minimum - setpoint temperature ( degrees Celsius )

Input Const

rSetpTempBaseReset

REAL

22.0

Base set temperature in degrees Celsius after a reset

Input Const

rOffsetRange

REAL

3.0

Adjustment range of the setpoint potentiometer (symmetric, 3.0 = +/- 3.0K)

Input Const

rRoomTempOffset

REAL

0.0

Offset of the room temperature ( for calibration of the temperature sensor ) in K

Input Const

eButton1OutpMode

THERMOKON_WRF07_BUTTON_OUTP_MODE

THERMOKON_WRF07_BUTTON_OUTP_MODE.RAW

Operating mode of the output ‘xButton1’ ( RAW, PULSE )

Input Const

eMode

THERMOKON_WRF07_MODE

THERMOKON_WRF07_MODE.ROOM_CONTROL_UNIT

General operating mode of the device (ROOM_CONTROL_UNIT: device serves as RBG, INTERNAL_REGULATION: setpoint formation / temperature regulation in the device)

Input Const

tTimeButtonPulse

TIME

TIME#1s0ms

Duration of the pulse at the output if the assigned button was actuated

Input Const

tTimeUpdateStates

TIME

TIME#500ms

Update interval for the processes influenced by the input ‘xUpdateStates’

Input Const

tTimeUpdateConfig

TIME

TIME#0ms

Update interval for the processes influenced by the input ‘xUpdateConfig’

Input Const

tTimeUpdateSetp

TIME

TIME#45s0ms

Update interval for operations influenced by the input 'xUpdateSetp'

Input Const

tTimeUpdateActual

TIME

TIME#3s0ms

Update interval for operations influenced by the input 'xUpdateActual'

Last updated