THERMOKON_WRF07
THERMOKON_WRF07 (FB)
THERMOKON_WRF07 (FB)FUNCTION_BLOCK THERMOKON_WRF07
Representation

General
Notes:
By the setpoint / parameter
eModecurrently (16.05.2022) only the formation of the room setpoint temperaturerSetpTempas well as the setpoint temperature offsetrOffsetis influenced.
The configuration registers (R0 - R69) or coils (C0 - C5) are always set for operation of the WRF07 as a pure room operating device (i.e. without its own internal control).
* Device configuration *
In registers 0 - 69 or in coils 0 - 5, the current configuration of the device is stored. This is read once at restart / once on every rising edge (xUpdateConfigRead) / cyclically (tTimeUpdateConfigRead) and stored in the arrays
_arwKonfiguration_0orarbyKonfiguration_1stored.
During operation, registers 2 - 69 or coils 0 - 3 are rewritten once at restart / when values change (
_arwKonfiguration_2orarbyKonfiguration_3). In addition, this write access can be triggered by a rising edge at inputxUpdateConfigWriteThis write access must not occur cyclically, as the number of write accesses is limited (EEPROM).
The device configuration cannot be reset to the factory state; in the arrays
_arwKonfiguration_4and_arbyKonfiguration_5the default values are stored and can be loaded / written into the device via inputxResDefault.
Setpoint / Parameter
rOffsetRange: A change is transmitted immediately without error, but the new offset is only used after a cold start of the WRF07.
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication (TRUE = enable)
Input
byUnitId
BYTE
0
Device address (1 .. 247) (1 .. 63 via DIP switch, 1 .. 247 via Modbus commands)
Input
xUpdateActual
BOOL
FALSE
Updating the actual values (at every rising edge ) (range: operation)
Input
xUpdateSetp
BOOL
FALSE
Update of setpoints (on every rising edge )
Input
xUpdateConfigRead
BOOL
FALSE
Update configuration (read access) (on every rising edge)
Input
xUpdateConfigWrite
BOOL
FALSE
Configuration update (write access) ( with every rising edge)
Input
xUpdateStates
BOOL
FALSE
Update states (registers 256 - 257) (on every rising edge)
Input
xResDefault
BOOL
FALSE
Reset configuration to default state ( registers 0 - 69) (coils 0 - 5) (on every rising edge)
Input
rSetpTempBase
REAL
22.0
Base setpoint temperature (degrees Celsius)
Input
xLED9
BOOL
FALSE
Control of LED9 (TRUE = On)
Input
xEnOffset
BOOL
FALSE
Enable / disable the influence of the setpoint adjuster (
rOffset) on the setpoint temperature (rSetpTemp)
Input
xResError
BOOL
FALSE
Reinitialization of the output eErrorCodeCom (with every
rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
eDeviceType
THERMOKON_WRF07_DEVICE_TYPE
Device type
Output
eUnitFb
THERMOKON_WRF07_UNIT
Current unit system of the device — feedback
Output
eRegulationModeFb
THERMOKON_WRF07_REGULATION_MODE_FEEDBACK
Current controller mode of the device
Output
rRoomTemp
REAL
Current room temperature in degrees Celsius
Output
rSetpTempBaseFb
REAL
Base setpoint temperature (degrees Celsius) — feedback
Output
rOffset
REAL
Current offset of the room setpoint temperature in K
Output
rSetpTemp
REAL
Current setpoint temperature in degrees Celsius
Output
rRelHumidity
REAL
Relative room humidity in percent
Output
xSensorOffsetInDevice
BOOL
Indication of whether the sensors must be calibrated in the device (TRUE = calibration in the device required, FALSE = calibration in the FB required)
Output
rDewPointTemp
REAL
Dew point temperature in degrees Celsius or Fahrenheit
Output
rAbsHumidity
REAL
Absolute room humidity in g/m3 or grain/ft3
Output
rEnthalpy
REAL
Enthalpy in kJ/kg or BTU/lb3
Output
xButton1
BOOL
FALSE
Activation of button 1 (RAW, pulse with duration
tTimeButtonPulse)
Output
eFunctionButton1Fb
THERMOKON_WRF07_BUTTON_FUNCTION
Function of button 1 — feedback
Output
xLED9Fb
BOOL
FALSE
State of LED 9 — feedback (TRUE = On)
Output
eFunctionLED9Fb
THERMOKON_WRF07_LED_FUNCTION
Function of LED 9 — feedback
Output
xDI1
BOOL
FALSE
State of digital input 1 (assignment depending on
function eFunctionDI1) (FALSE = Open, TRUE =
Closed)
Output
eFunctionDI1Fb
THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION
Function of digital input 1 — feedback
Output
xDI2
BOOL
FALSE
State of digital input 2 (assignment depending on
function eFunctionDI2) (FALSE = Open, TRUE =
Closed)
Output
eFunctionDI2Fb
THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION
Function of digital input 2 — feedback
Output
xDI3
BOOL
FALSE
State of digital input 3 (assignment depending on
function eFunctionDI1) (FALSE = Open, TRUE =
Closed)
Output
eFunctionDI3Fb
THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION
Function of digital input 3 — feedback
Output
xDI4
BOOL
FALSE
State of digital input 4 (assignment depending on
function eFunctionDI2) (FALSE = Open, TRUE =
Closed)
Output
eFunctionDI4Fb
THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION
Function of digital input 4 — feedback
Output
xAlarm
BOOL
FALSE
Collective fault (TRUE = fault)
Output
xAlarmCom
BOOL
FALSE
Collective fault - communication (TRUE = fault)
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication (0 = no error)
Output
xBusy
BOOL
Communication indicator (TRUE = communication)
Input Const
eUnit
THERMOKON_WRF07_UNIT
THERMOKON_WRF07_UNIT.SI
Current unit system of the device
Input Const
rRoomHumityOffset
REAL
0.0
Offset of the room humidity (for calibration of the humidity sensor ) in percent
Input Const
eFunctionLED9
THERMOKON_WRF07_LED_FUNCTION
THERMOKON_WRF07_LED_FUNCTION.EXTERNAL_CONTROL
Function of LED 9
Input Const
eFunctionDI4
THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION
THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION.NORMALLY_OPEN_CONTACT
Function of digital input 4
Input Const
eFunctionDI3
THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION
THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION.NORMALLY_OPEN_CONTACT
Function of digital input 3
Input Const
eFunctionDI2
THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION
THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION.NORMALLY_OPEN_CONTACT
Function of digital input 2
Input Const
eFunctionDI1
THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION
THERMOKON_WRF07_DIGITAL_INPUT_FUNCTION.NORMALLY_OPEN_CONTACT
Function of digital input 1
Input Const
eFunctionButton1
THERMOKON_WRF07_BUTTON_FUNCTION
Function of button 1
Input Const
rSetpTempMax
REAL
26.0
Absolute maximum value - setpoint temperature (degrees Celsius)
Input Const
rSetpTempMin
REAL
18.0
Absolute minimum value - setpoint temperature (degrees Celsius)
Input Const
rSetpTempBaseReset
REAL
22.0
Base setpoint temperature in degrees Celsius after a reset
Input Const
rOffsetRange
REAL
3.0
Adjustment range of the setpoint potentiometer (symmetrical, 3.0 = +/. 3.0K)
Input Const
rRoomTempOffset
REAL
0.0
Offset of the room temperature (for calibration of the temperature sensor) in K
Input Const
eButton1OutpMode
THERMOKON_WRF07_BUTTON_OUTP_MODE
THERMOKON_WRF07_BUTTON_OUTP_MODE.RAW
Operating mode of the output xButton1 (RAW, PULSE)
Input Const
eMode
THERMOKON_WRF07_MODE
THERMOKON_WRF07_MODE.ROOM_CONTROL_UNIT
General operating mode of the device (ROOM_CONTROL_UNIT: device serves as RBG, INTERNAL_REGULATION: setpoint formation / temperature control in the device)
Input Const
tTimeButtonPulse
TIME
TIME#1s0ms
Duration of the pulse at the output, if the assigned button was pressed
Input Const
tTimeUpdateStates
TIME
TIME#500ms
Update interval for the processes influenced by the input
xUpdateStates influenced
Input Const
tTimeUpdateConfig
TIME
TIME#0ms
Update interval for the processes influenced by the input
xUpdateConfig influenced
Input Const
tTimeUpdateSetp
TIME
TIME#45s0ms
Update interval for the processes influenced by the input
xUpdateSetp influenced
Input Const
tTimeUpdateActual
TIME
TIME#3s0ms
Update interval for the processes influenced by the input
xUpdateActual influenced
Last updated

