THERMOKON_WRF06

THERMOKON_WRF06 (FB)

FUNCTION_BLOCK THERMOKON_WRF06

Representation

Short description

Control of the WRF06 device series from Thermokon

Typical application: room operating device in a zone

Guidelines - Software creation

The following function codes (FC) are supported: 1 - 6, 15 - 16 For addressing, the address specifications must be used, not the register addresses. This room operating device can be supplied in different device types (without / with integrated temperature controller). The maximum of four digital inputs and two analog outputs are supported by the function block. The two analog outputs can be accessed directly for writing. The four function keys F1 (right) - F4 (left) are supported by the function block. The function block supports exclusively use as a pure room operating device; the internal PI controller (present depending on device type) is not used. Calibration of the room temperature sensor is carried out either on the room operating device (parameter mode, see documentation) or via the configuration software WRF06-RS485_MODBUS_V_2_9. The ROD monitors Modbus communication. If no valid Modbus telegram is received for more than 90 s, the analog/digital outputs are set to default values (registers 53 and 54). Modbus addresses 1 - 32 can be set directly on the DIP switches in the ROD. The address range 1 - 247 can be used by a procedure described in the documentation. In the data area (ADR - FC - data area - CRC1 - CRC2), a maximum of 100 bytes (= 50 registers) may be transmitted (deviating from the Modbus standard). The following transmission parameters were tested: 19200 baud, 8-N-1 At present, only the device types AO2V and 4DI with print type 2 are supported. Setpoint temperature 1 can be changed using the UP / DOWN keys only during day operation (= comfort / occupied). (property of the room operating device)

The following values are used for the internal PI controller: Actual value: address 258 (= room temperature) Setpoint value: address 260 (= setpoint 1 effective) Control signal: The control signal is output directly to the outputs.

Measured values - calibration: Class 4

Configuration data

The data in the EEPROM (= configuration data) may be written a maximum of 10000 times!!!

Data in EEPROM:

Addresses 2 - 58: configuration registers Addresses 768 - 987: text message line 1 and 2 Addresses 1024 - 1080: unit line 1, 2 and 3 Coils 0 - 30: configuration bits

These configuration data can be read, backed up, modified, and written into a new room operating device from the room operating device using the software ''WRF06-RS485_MODBUS_V_2_9''. Therefore, no configuration data are present in the function block. In the function block, addresses 0 - 58 are read if the configuration (xUpdateConfig, tTimeUpdateConfig, once after restart) is read.

The device configuration cannot be reset to the factory state (neither via Modbus nor using the configuration software).

Register 528 (address 527) - fan stage specification (FC06 / FC16): If a manual fan stage (0 - 3) is specified, it is correctly displayed and reported back in the ROD. If an automatic fan stage (65280 - 65283) is specified, it is — briefly — correctly displayed and reported back in the ROD. However, writing with an automatic stage activates the internal automatic mode, which depends on the heating / cooling control signal (adjustable thresholds). Therefore, in this function block only the specifications of the manual fan stages are supported.

Interfaces

Inputs

Name
Data type
Value range
Initial value
Function

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enable)

byUnitId

BYTE

0

Device address (0 .. 255)

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge)

xUpdateSetp

BOOL

FALSE

Update of setpoints (on every rising edge)

xUpdateConfig

BOOL

FALSE

Update of the configuration (on every rising edge) (read access)

xUpdateStates

BOOL

FALSE

Update of states (on every rising edge)

xUpdateInfo

BOOL

FALSE

Update of the information (on every rising edge)

rAO1Manual

REAL

0.0

State of analog output 1 (eAnalogOutputsMode = THERMOKON_WRF06_ANALOG_OUTP_MODE.MANUAL_MODE) (0.0 - 100.0% = 0.0 - 10.0 V) (address 534, FC16)

rAO2Manual

REAL

0.0

State of analog output 2 (eAnalogOutputsMode = THERMOKON_WRF06_ANALOG_OUTP_MODE.MANUAL_MODE) (0.0 - 100.0% = 0.0 - 10.0 V) (address 535, FC16)

xDsplSymb_Alarm

BOOL

FALSE

Enable / disable the display of the symbol 'Fault' (TRUE = display) (Coil 256, FC15)

xDsplSymb_Heat

BOOL

FALSE

Enable / disable the display of the symbol 'Heating, controller heating mode' (TRUE = display) (Coil 257, FC15)

xDsplSymb_Cool

BOOL

FALSE

Enable / disable the display of the symbol 'Cooling, controller cooling mode' (TRUE = display) (Coil 258, FC15)

xDsplSymb_Wind

BOOL

FALSE

Enable / disable the display of the symbol 'Window, energy lockout' (TRUE = display) (Coil 259, FC15)

xDsplSymb_DewP

BOOL

FALSE

Enable / disable the display of the symbol 'Dew point, dew point alarm' (TRUE = display) (Coil 260, FC15)

xDsplSymb_Off

BOOL

FALSE

Enable / disable the display of the symbol 'Off, controller off' (TRUE = display) (Coil 261, FC15)

xUpdateDateTime

BOOL

FALSE

Update of the device date / time (on each rising edge)

rExtValue1

REAL

0.0

External measured value 1 for display on the ROD (Modbus register content = rExtValue1 * rExtValue1Mult) (address 519, FC16)

rExtValue2

REAL

0.0

External measured value 2 for display on the ROD (Modbus register content = rExtValue1 * rExtValue1Mult) (address 520, FC16)

rExtValue3

REAL

0.0

External measured value 3 for display on the ROD (Modbus register content = rExtValue1 * rExtValue1Mult) (address 521, FC16)

rExtValue4

REAL

0.0

External measured value 4 for display on the ROD (Modbus register content = rExtValue1 * rExtValue1Mult) (address 522, FC16)

wAutoFanStages

WORD

0

Input for automatic specification of the fan stage

eRegMode

THERMOKON_WRF06_REGULATION_MODE

THERMOKON_WRF06_REGULATION_MODE.NO_REGULATION

Current controller mode on the device (address 533, FC16)

rExtRoomTemp

REAL

0.0

External temperature as a replacement for the internal room temperature (address 536, FC16) (eRoomTempMode = THERMOKON_WRF06_ROOM_TEMP_MODE.EXTERNAL_VALUE)

xMode

BOOL

FALSE

Current room occupancy of the device (TRUE = occupied, comfort mode, day mode, FALSE = unoccupied, setback mode, night mode) (address 528, FC16)

rSetpTemp1BaseDay

REAL

22.0

Setpoint temperature 1: base setpoint temperature in day mode (degrees Celsius)

rSetpTemp1Night

REAL

18.0

Setpoint temperature 1: setpoint temperature in night mode (degrees Celsius)

rSetpTemp2BaseDay

REAL

22.0

Setpoint temperature 2: base setpoint temperature in day mode (degrees Celsius)

rSetpTemp2Night

REAL

18.0

Setpoint temperature 2: setpoint temperature in night mode (degrees Celsius)

xResError

BOOL

FALSE

Input for resetting the output eErrorCodeCom (on every rising edge)

Outputs

Name
Data type
Value range
Initial value
Function

wDeviceCode

WORD

0

Device identifier (address 0, FC03)

wFirmwareVer

WORD

0

Firmware version of the device (address 1, FC03)

eDeviceType

THERMOKON_WRF06_DEVICE_TYPE

Device configuration (address 2, FC03)

rRoomTemp

REAL

0.0

Current room temperature in the selected unit (address 258, FC03)

rRelHumidity

REAL

0.0

Relative room humidity in percent (if sensor available) (address 270, FC03)

rAO1

REAL

0.0

Current state at analog output 1 (0.0 - 100.0% = 0.0 - 10.0 V)

rAO2

REAL

0.0

Current state at analog output 2 (0.0 - 100.0% = 0.0 - 10.0 V)

eRegModeDev

THERMOKON_WRF06_REGULATION_MODE_DEVICE

Current controller mode from the device (address 269, FC03)

rSetpTemp1OffMaxFb

REAL

0.0

Temperature setpoint 1: maximum value - adjustment of the base setpoint temperature — feedback (address 17, FC03)

rSetpTemp1OffMinFb

REAL

0.0

Temperature setpoint 1: minimum value - adjustment of the base setpoint temperature — feedback (address 18, FC03)

rSetpTemp1StepFb

REAL

0.0

Temperature setpoint 1: +/- - adjustment value on a key press — feedback (address 19, FC03)

rSetpTemp1ResetFb

REAL

0.0

Temperature setpoint 1: base setpoint after a reset operation — feedback (address 20, FC03)

rSetpTemp2OffMaxFb

REAL

0.0

Temperature setpoint 2: maximum value - adjustment of the base setpoint temperature — feedback (address 21, FC03)

rSetpTemp2OffMinFb

REAL

0.0

Temperature setpoint 2: minimum value - adjustment of the base setpoint temperature — feedback (address 22, FC03)

rSetpTemp2StepFb

REAL

0.0

Temperature setpoint 2: +/- - adjustment value on a key press — feedback (address 23, FC03)

rSetpTemp2ResetFb

REAL

0.0

Temperature setpoint 2: base setpoint after a reset operation — feedback (address 24, FC03)

rSetpTemp1Off

REAL

0.0

Temperature setpoint 1: current adjustment of the base setpoint temperature (address 259, FC03) (actual values_1)

rSetpTemp1

REAL

0.0

Temperature setpoint 1: current setpoint temperature (address 260, FC03) (actual values_1)

rSetpTemp2Off

REAL

0.0

Temperature setpoint 2: current adjustment of the base setpoint temperature (address 261, FC03) (actual values_1)

rSetpTemp2

REAL

0.0

Temperature setpoint 2: current setpoint temperature (address 262, FC03) (actual values_1)

xButtonSetpTempUp

BOOL

FALSE

Generation of an impulse with duration tTimeButtonPulse, if the setpoint temperature is increased

xButtonSetpTempDown

BOOL

FALSE

Generation of an impulse with duration tTimeButtonPulse, if the setpoint temperature is reduced

xModeDev

BOOL

FALSE

Current room occupancy from the device (TRUE = occupied, comfort mode, day mode) (address 264, FC03)

xButtonPresence

BOOL

FALSE

Generation of an impulse with duration tTimeButtonPulse, if the presence status has changed

eFanModeDev

THERMOKON_WRF06_FAN_OP_MODE

Current operating mode of the fan (address 263, FC03)

wNbrOfFanStages

WORD

0

Number of available fan stages

xAutoFanStages

BOOL

FALSE

Display of automatic mode for the fan stages (FALSE: manual correction active, TRUE = automatic mode active)

xButtonFanStages

BOOL

FALSE

Generation of an impulse with duration tTimeButtonPulse, if the fan stage is changed

xButton1

BOOL

FALSE

Pressing key 1 (right) (modes: RAW, pulse with duration tTimeButtonPulse) (addresses 256 & 257, FC03)

eFunctionButton1Fb

THERMOKON_WRF06_BUTTON_FUNCTION

Function of key 1 — feedback (address 6, FC03)

xButton2

BOOL

FALSE

Pressing key 2 (middle right) (RAW, pulse with duration tTimeButtonPulse) (addresses 256 & 257, FC03)

eFunctionButton2Fb

THERMOKON_WRF06_BUTTON_FUNCTION

Function of key 2 — feedback (address 7, FC03)

xButton3

BOOL

FALSE

Pressing key 3 (middle left) (RAW, pulse with duration tTimeButtonPulse) (addresses 256 & 257, FC03)

eFunctionButton3Fb

THERMOKON_WRF06_BUTTON_FUNCTION

Function of key 3 — feedback (address 8, FC03)

xButton4

BOOL

FALSE

Pressing key 4 (left) (RAW, pulse with duration tTimeButtonPulse) (addresses 256 & 257, FC03)

eFunctionButton4Fb

THERMOKON_WRF06_BUTTON_FUNCTION

Function of key 4 — feedback (address 9, FC03)

xDI1

BOOL

FALSE

State of digital input 1 (assignment depending on function) (FALSE = open, TRUE = closed) (address 265, FC03)

eFunctionDI1Fb

THERMOKON_WRF06_DIGITAL_INPUT_FUNCTION

Function of digital input 1 — feedback (address 26, FC03)

xDI2

BOOL

FALSE

State of digital input 2 (assignment depending on function) (FALSE = open, TRUE = closed) (address 266, FC03)

eFunctionDI2Fb

THERMOKON_WRF06_DIGITAL_INPUT_FUNCTION

Function of digital input 2 — feedback (address 27, FC03)

xDI3

BOOL

FALSE

State of digital input 3 (assignment depending on function) (FALSE = open, TRUE = closed) (address 267, FC03)

eFunctionDI3Fb

THERMOKON_WRF06_DIGITAL_INPUT_FUNCTION

Function of digital input 3 — feedback (address 28, FC03)

xDI4

BOOL

FALSE

State of digital input 4 (assignment depending on function) (FALSE = open, TRUE = closed) (address 268, FC03)

eFunctionDI4Fb

THERMOKON_WRF06_DIGITAL_INPUT_FUNCTION

Function of digital input 4 — feedback (address 29, FC03)

xSensorOffsetInDevice

BOOL

Display whether the sensors must be calibrated in the device (TRUE = calibration required in the device, FALSE = calibration required in the FB)

xAlarm

BOOL

FALSE

Collective fault (TRUE = fault)

xAlarmCom

BOOL

FALSE

Collective fault - communication (TRUE = fault)

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

xBusy

BOOL

Communication indicator (TRUE = communication)

Inputs and outputs

Name
Data type
Value range
Initial value
Function

ModbusClient

ModbusClientBase

Client of the device

Setpoints / parameters

Name
Data type
Value range
Initial value
Address
Function

tTimeUpdateActual

TIME

T#3s

Update interval for the processes influenced by the input xUpdateActual are affected (0 = no automatic update, > 0 cyclical update)

tTimeUpdateSetp

TIME

T#0s

Update interval for the processes influenced by the input xUpdateSetp are affected (0 = no automatic update, > 0 cyclical update)

tTimeUpdateConfig

TIME

T#0s

Update interval for the processes influenced by the input xUpdateConfig are affected (0 = no automatic update, > 0 cyclical update)

tTimeUpdateStates

TIME

T#500ms

Update interval for the processes influenced by the input xUpdateStates are affected (0 = no automatic update, > 0 cyclical update)

tTimeUpdateInfo

TIME

T#0s

Update interval for the processes influenced by the input xUpdateInfo are affected (0 = no automatic update, > 0 cyclical update)

tTimeButtonPulse

TIME

T#1s

Duration of the pulse at the outputs xButtonX, xButtonPresence, xBiuttonFanStages', xButtonSetpTempUp' and xButtonSetpTempDown

eButton1OutpMode

THERMOKON_WRF06_BUTTON_OUTP_MODE

THERMOKON_WRF06_BUTTON_OUTP_MODE.RAW

Operating mode of the output xButton1 (RAW, PULSE)

eButton2OutpMode

THERMOKON_WRF06_BUTTON_OUTP_MODE

THERMOKON_WRF06_BUTTON_OUTP_MODE.RAW

Operating mode of the output xButton2 (RAW, PULSE)

eButton3OutpMode

THERMOKON_WRF06_BUTTON_OUTP_MODE

THERMOKON_WRF06_BUTTON_OUTP_MODE.RAW

Operating mode of the output xButton3 (RAW, PULSE)

eButton4OutpMode

THERMOKON_WRF06_BUTTON_OUTP_MODE

THERMOKON_WRF06_BUTTON_OUTP_MODE.RAW

Operating mode of the output xButton4 (RAW, PULSE)

wDateTime_Seconds

WORD

0

Date / time update: current second of the minute (0 - 59)

wDateTime_Minutes

WORD

0

Date / time update: current minute of the hour (0 - 59)

wDateTime_Hours

WORD

0

Date / time update: current hour of the day (0 - 23)

wDateTime_DayOfMonth

WORD

1

Date / time update: current day of the month (1 - 31)

wDateTime_Month

WORD

1

Date / time update: current month (1 - 12)

wDateTime_Year

WORD

2024

Date / time update: current year (2000 - 2099)

eAnalogOutputsMode

THERMOKON_WRF06_ANALOG_OUTP_MODE

THERMOKON_WRF06_ANALOG_OUTP_MODE.MANUAL_MODE;

Mode for analog outputs AO1 and AO2 (MANUAL_MODE: <br/>*<br/> rAO1' and rAO2 define the current states of the analog outputs)

xDsplAlarm1

BOOL

FALSE

Enable / disable display of alarm message 1 on the ROD (TRUE = display)

xDsplAlarm2

BOOL

FALSE

Enable / disable display of alarm message 2 on the ROD (TRUE = display)

xDsplAlarm3

BOOL

FALSE

Enable / disable display of alarm message 3 on the ROD (TRUE = display)

xDsplAlarm4

BOOL

FALSE

Enable / disable display of alarm message 4 on the ROD (TRUE = display)

eRoomTempMode

THERMOKON_WRF06_ROOM_TEMP_MODE

THERMOKON_WRF06_ROOM_TEMP_MODE.INTERNAL_SENSOR

Mode for the source of the room temperature (EXTERNAL_VALUE: <br/>*<br/> rExtRoomTemp' defines the room temperature)

rExtValue1Mult

REAL

10.0

Multiplier for external measured value 1 for display on the ROD (address 519 = rExtValue1 * rExtValue1Mult)

rExtValue2Mult

REAL

10.0

Multiplier for external measured value 2 for display on the ROD (address 520 = rExtValue2 * rExtValue2Mult)

rExtValue3Mult

REAL

10.0

Multiplier for external measured value 3 for display on the ROD (address 521 = rExtValue3 * rExtValue3Mult)

rExtValue4Mult

REAL

10.0

Multiplier for external measured value 4 for display on the ROD (address 522 = rExtValue4 * rExtValue4Mult)

xVisuPresence

BOOL

FALSE

Visualization: pressing the presence button (on each rising edge)

xVisuFanStages

BOOL

FALSE

Visualization: pressing the button for the fan stages (on each rising edge)

xVisuSetpTempUp

BOOL

FALSE

Visualization: pressing the button to increase the setpoint temperature in day mode (on each rising edge)

xVisuSetpTempDown

BOOL

FALSE

Visualization: pressing the button to decrease the setpoint temperature in day mode (on each rising edge)

eButtonSelectionForPresence

THERMOKON_WRF06_BUTTON_SELECTION

THERMOKON_WRF06_BUTTON_SELECTION.BUTTON_4

Selection of the button (1 - 4) for the presence function (output xButtonPresence)

eButtonSelectionForFanStages

THERMOKON_WRF06_BUTTON_SELECTION

THERMOKON_WRF06_BUTTON_SELECTION.BUTTON_3

Selection of the button (1 - 4) for selecting the fan stages (output xButtonFanStages)

eButtonSelectionForSetpTempUp

THERMOKON_WRF06_BUTTON_SELECTION

THERMOKON_WRF06_BUTTON_SELECTION.BUTTON_1

Selection of the button (1 - 4) for selecting the button to increase the setpoint temperature (output xButtonSetpTempUp)

eButtonSelectionForSetpTempDown

THERMOKON_WRF06_BUTTON_SELECTION

THERMOKON_WRF06_BUTTON_SELECTION.BUTTON_2

Selection of the button (1 - 4) for selecting the button to reduce the setpoint temperature (output xButtonSetpTempDown)

eSetpTempOpMode

THERMOKON_WRF06_SETP_TEMP_OPERATION_MODE

THERMOKON_WRF06_SETP_TEMP_OPERATION_MODE.SETPOINT_1

Selection of the setpoint (1, 2) for adjustment via the keys on the room operating device

Function description

General

This function block controls room operating devices of the WRF06 device series from Thermokon via Modbus communication. Configuration is external, e.g. by using the configuration software WRF06-RS485_MODBUS_V_2_9. At present, only the device types AO2V and 4DI with print type 2 are supported. The function block supports exclusively use as a pure room operating device; the internal PI controller (present depending on device type) is not used.

Analog outputs AO1 and AO2 (if present)

The current states of the analog outputs (0.0 - 10.0 V) are determined either by the internal PI controller (eAnalogOutputsMode = AUTOMATIC_MODE) or by the inputs rAO1Manual or rAO1Manua2 (0.0 - 100.0 %) (eAnalogOutputsMode = MANUAL_MODE).

Display of symbols on the room operating device

Various symbols on the display of the room operating device can be represented by the assigned inputs with the prefix xDsplSymb_X (FALSE = off, TRUE = on). Update of the date / time on the room operating device

On each rising edge at the input xUpdateDateTime the parameters with the prefix wDateTime_X are transferred to the room operating device. The parameters are checked for compliance with the limit values.

Display of external measured values

A maximum of four different external measured values can be transferred to the room operating device via the inputs rExtValueX (X = 1 .. 4), multiplied by the respective parameter rExtValueXMultand displayed there (see configuration).

Fan stages

The number of switchable fan stages is defined in the configuration (output wNbrOfFanStages). The current operating mode is displayed at output eFanModeDev . The fan stage is primarily determined in night or day mode by input wAutoFanStages in the range 0 - wNbrOfFanStages .

Manual correction (day mode only): On each pulse at output xButtonFanStages the fan stage in day mode is increased step by step from the lower limit wMinFanStageManDay to the upper limit wMaxFanStageManDay taking output wNbrOfFanStages into account. On the next pulse, it then switches back to the lower limit wMinFanStageManDay before the sequence starts again. The manually specified fan stage in day mode is not stored when transitioning to night mode.

Switching from manual correction to automatic mode takes place:

  1. when transitioning from night mode to day mode

  2. when transitioning from day mode to night mode

  3. if the key for changing the fan stage (parameter eButtonSelectionForFanStages) on the ROD is pressed continuously for more than 3 s.

  4. if the key for switching to automatic mode xVisuAutoFanStages was pressed

Mode (night and day mode)

The input xMode is monitored for changes. On each rising edge, switching to day mode takes place; on each falling edge, switching to night mode takes place. The current mode is displayed at output xModeDev .

Setpoints on the room operating device

The room operating device contains two setpoints (1, 2) that can be displayed and used for temperature control. Each setpoint consists of a base value and an offset (effective setpoint = base value + offset). In this function block, setpoint 1 is primarily used. The assigned inputs and outputs are each marked with the prefix rSetpTempX (X = 1 .. 2). The outputs rSetpTempXOffMaxFb, rSetpTempXOffMinFb, rSetpTempXStepFb and rSetpTempXResetFb are read from the configuration and displayed. The respective current values on the ROD can be read at the outputs rSetpTempX or rSetpTempXOFF .

Setpoint temperatures in day and night mode

On each transition to day mode, the current setpoint temperatures 1 and 2 for day mode are transferred to the room operating device.

At the first transition or after parameter changes, the following is transferred: Base value = 'rSetpTempXBaseDay, Offset = 0.0 For the following transitions, the following is transferred: Base value = last current base value, Offset = last current offset

On each transition to night mode, the current setpoint temperatures 1 and 2 for night mode are transferred to the room operating device. Base value = 'rSetpTempXNight, Offset = 0.0

Adjustment of the setpoint temperatures in day mode

The parameter eSetpTempOpMode also determines which setpoint the adjustment in day mode applies to.

In day mode, the current setpoint temperature is increased by the step size xButtonSetpTempUp on each rising edge at output rSetpTempXStepFb if the assigned limit rSetpTempXOffMaxFb has not yet been exceeded.

In day mode, the current setpoint temperature is increased by the step size xButtonSetpTempDown on each rising edge at output rSetpTempXStepFb reduced, if the assigned limit rSetpTempXOffMinFb has not yet been undershot. Output xButtonPresence

At this output, an impulse with duration tTimeButtonPulse is generated, if

  1. at the parameter xVisuPresence OR

  2. at the output of the selected button xButtonX (X = 1 .. 4) (selection via eSelectButtonForPresence)

a rising edge is detected (= actuation).

This output can be linked with the input xButton of the function block HVAC.Button1 to implement the extension of the occupancy time.

Output xButtonFanStages

At this output, an impulse with duration tTimeButtonPulse is generated, if

  1. at the parameter xVisuFanStages OR

  2. at the output of the selected button xButtonX (selection via eSelectButtonForFanStages)

a rising edge is detected (= actuation).

Manual correction (day mode only): On each pulse at output xButtonFanStages the fan stage in day mode is increased step by step from the lower limit wMinFanStageManDay to the upper limit wMaxFanStageManDay taking output wNbrOfFanStages into account. On the next pulse, it then switches back to the lower limit wMinFanStageManDay before the sequence starts again. The manually specified fan stage in day mode is not stored when transitioning to night mode.

Switching from manual correction to automatic mode takes place: 1) when transitioning from night to day mode 2) when transitioning from day to night mode 3) if the key for changing the fan stage (parameter eButtonSelectionForFanStages) on the ROD is pressed continuously for more than 3 s. 4) if the key for switching to automatic mode xVisuAutoFanStages was pressed

Output xButtonSetpTempUp

At this output, an impulse with duration tTimeButtonPulse is generated, if

  1. at the parameter xVisuSetpTempUp OR

  2. at the output of the selected button xButtonX (selection via eSelectButtonForSetpTempUp)

a rising edge is detected (= actuation).

Two operating modes are distinguished (parameter eSetpTempOpMode):

1) SETPOINT_1: on each pulse at output xButtonSetpTempUp the adjustment of setpoint temperature 1 in day mode is increased by the step size for setpoint temperature 1 2) SETPOINT_2: on each pulse at output xButtonSetpTempUp the adjustment of setpoint temperature 2 in day mode is increased by the step size for setpoint temperature 2

Output xButtonSetpTempDown

At this output, an impulse with duration tTimeButtonPulse is generated, if

  1. at the parameter xVisuSetpTempDown OR

  2. at the output of the selected button xButtonX (selection via eSelectButtonForSetpTempDown)

a rising edge is detected (= actuation).

Two operating modes are distinguished (parameter eSetpTempOpMode):

1) SETPOINT_1: on each pulse at output xButtonSetpTempDown the adjustment of setpoint temperature 1 in day mode is reduced by the step size for setpoint temperature 1 1) SETPOINT_2: on each pulse at output xButtonSetpTempDown the adjustment of setpoint temperature 2 in day mode is reduced by the step size for setpoint temperature 2

Buttons 1 - 4 (Button 1 = right, Button 4 = left)

A defined function can be assigned to each button in the configuration, which is displayed at the assigned output eFunctionButtonXFb (X = 1 .. 4). Independently of this, every actuation of button X is recorded and, depending on the operating mode (parameter eButtonXOutpMode) at the output xButtonX .

  1. eButtonXOutpMode = RAW: The output is active in parallel with pressing the button.

  2. eButtonXOutpMode = PULSE: At the output, a pulse with duration tTimeButtonPulse is generated on each new actuation of the button

Digital inputs 1 - 4 (depending on version)

A defined function can be assigned to each digital input in the configuration, which is displayed at the assigned output eFunctionDIXFb (X = 1 .. 4). Independently of this, the current state of each input X is recorded and displayed at output xDIX (FALSE = open, TRUE = closed).

Display of faults

Faults are displayed at the collective output xAlarm (= TRUE). It includes communication faults (time delay: gc_Parameters.gc_tOnDelayxAlarmCom, default = 60s) and device faults (direct). At output eErrorCodeCom in the event of a communication error, an explanatory text for the cause is available. The cause of the last communication error is always displayed there.

Codesys

InOut:

Scope
Name
Type
Initial
Comment

Input

xEn

BOOL

TRUE

Enable / disable communication (TRUE = enable)

Input

byUnitId

BYTE

0

Device address (1 .. 247) (1 .. 31 via DIP switch, 1 .. 247 via Modbus commands)

Input

xUpdateActual

BOOL

FALSE

Update of actual values (on every rising edge )

Input

xUpdateSetp

BOOL

FALSE

Update of setpoints (on every rising edge )

Input

xUpdateConfig

BOOL

FALSE

Update of the configuration (on every rising edge) (read access)

Input

xUpdateStates

BOOL

FALSE

Update of the states (on each rising edge)

Input

xUpdateInfo

BOOL

FALSE

Update of the information (on every rising edge)

Input

rAO1Manual

REAL

0.0

State of analog output 1 (eAnalogOutputsMode = THERMOKON_WRF06_ANALOG_OUTP_MODE.MANUAL_MODE) (0.0 - 100.0% = 0.0 - 10.0 V) (address 534, FC16)

Input

rAO2Manual

REAL

0.0

State of analog output 2 (eAnalogOutputsMode = THERMOKON_WRF06_ANALOG_OUTP_MODE.MANUAL_MODE) (0.0 - 100.0% = 0.0 - 10.0 V) (address 535, FC16)

Input

xDsplSymb_Alarm

BOOL

FALSE

Enable / disable display of the symbol 'Fault' (TRUE = display) (Coil 256, FC15)

Input

xDsplSymb_Heat

BOOL

FALSE

Enable / disable display of the symbol 'Heating, controller heating mode' (TRUE = display) (Coil 257, FC15)

Input

xDsplSymb_Cool

BOOL

FALSE

Enable / disable display of the symbol 'Cooling, controller cooling mode' (TRUE = display) (Coil 258, FC15)

Input

xDsplSymb_Wind

BOOL

FALSE

Enable / disable display of the symbol 'Window, energy lockout' (TRUE = display) (Coil 259, FC15)

Input

xDsplSymb_DewP

BOOL

FALSE

Enable / disable display of the symbol 'Dew point, dew point alarm' (TRUE = display) (Coil 260, FC15)

Input

xDsplSymb_Off

BOOL

FALSE

Enable / disable display of the symbol 'Off, controller off' (TRUE = display) (Coil 261, FC15)

Input

xUpdateDateTime

BOOL

FALSE

Update of the device date / time (on each rising edge)

Input

rExtValue1

REAL

0.0

External measured value 1 for display on the ROD (Modbus register content = rExtValue1 * rExtValue1Mult) (address 519, FC16)

Input

rExtValue2

REAL

0.0

External measured value 2 for display on the ROD (Modbus register content = rExtValue2 * rExtValue2Mult) (address 520, FC16)

Input

rExtValue3

REAL

0.0

External measured value 3 for display on the ROD (Modbus register content = rExtValue3 * rExtValue3Mult) (address 521, FC16)

Input

rExtValue4

REAL

0.0

External measured value 4 for display on the ROD (Modbus register content = rExtValue4 * rExtValue4Mult) (address 522, FC16)

Input

wAutoFanStages

WORD

0

Input for automatic specification of the fan stage

Input

eRegMode

THERMOKON_WRF06_REGULATION_MODE

THERMOKON_WRF06_REGULATION_MODE.NO_REGULATION

Current controller mode on the device (address 533, FC16)

Input

rExtRoomTemp

REAL

0.0

External temperature as a replacement for the internal room temperature (address 536, FC16) (eRoomTempMode = THERMOKON_WRF06_ROOM_TEMP_MODE.EXTERNAL_VALUE)

Input

xMode

BOOL

FALSE

Current room occupancy of the device (TRUE = occupied, comfort mode, day mode, FALSE = unoccupied, setback mode, night mode) (address 528, FC16)

Input

rSetpTemp1BaseDay

REAL

22.0

Setpoint temperature 1: base setpoint temperature in day mode ( degrees Celsius)

Input

rSetpTemp1Night

REAL

18.0

Setpoint temperature 1: setpoint temperature in night mode (degrees Celsius)

Input

rSetpTemp2BaseDay

REAL

22.0

Setpoint temperature 2: base setpoint temperature in day mode ( degrees Celsius)

Input

rSetpTemp2Night

REAL

18.0

Setpoint temperature 2: setpoint temperature in night mode (degrees Celsius)

Input

xResError

BOOL

FALSE

Reinitialization of the output eErrorCodeCom (with every rising edge)

Inout

ModbusClient

ModbusClientBase

Client of the device

Output

wDeviceCode

WORD

0

Device identifier (address 0, FC03)

Output

wFirmwareVer

WORD

0

Firmware version of the device (address 1, FC03)

Output

eDeviceType

THERMOKON_WRF06_DEVICE_TYPE

Device configuration (address 2, FC03)

Output

rRoomTemp

REAL

0.0

Current room temperature in the selected unit ( address 258, FC03)

Output

rRelHumidity

REAL

0.0

Relative room humidity in percent (if sensor available) (address 270, FC03)

Output

rAO1

REAL

0.0

Current state at analog output 1 (0.0 - 100.0% = 0.0 - 10.0 V)

Output

rAO2

REAL

0.0

Current state at analog output 2 (0.0 - 100.0% = 0.0 - 10.0 V)

Output

eRegModeDev

THERMOKON_WRF06_REGULATION_MODE_DEVICE

THERMOKON_WRF06_ANALOG_OUTP_MODE.AUTOMATIC_MODE: address 268, FC03 THERMOKON_WRF06_ANALOG_OUTP_MODE.MANUAL_MODE: address 535, FC03 Current controller mode from the device (address 269, FC03)

Output

rSetpTemp1OffMaxFb

REAL

0.0

Temperature setpoint 1: maximum value - adjustment of the base setpoint temperature — feedback (address 17, FC03)

Output

rSetpTemp1OffMinFb

REAL

0.0

Temperature setpoint 1: minimum value - adjustment of the base setpoint temperature — feedback (address 18, FC03)

Output

rSetpTemp1StepFb

REAL

0.0

Temperature setpoint 1: +/- - adjustment value on a button press — feedback (address 19, FC03)

Output

rSetpTemp1ResetFb

REAL

0.0

Temperature setpoint 1: base setpoint after a reset operation — feedback (address 20, FC03)

Output

rSetpTemp2OffMaxFb

REAL

0.0

Temperature setpoint 2: maximum value - adjustment of the base setpoint temperature — feedback (address 21, FC03)

Output

rSetpTemp2OffMinFb

REAL

0.0

Temperature setpoint 2: minimum value - adjustment of the base setpoint temperature — feedback (address 22, FC03)

Output

rSetpTemp2StepFb

REAL

0.0

Temperature setpoint 2: +/- - adjustment value on a button press — feedback (address 23, FC03)

Output

rSetpTemp2ResetFb

REAL

0.0

Temperature setpoint 2: base setpoint after a reset operation — feedback (address 24, FC03)

Output

rSetpTemp1Off

REAL

0.0

Temperature setpoint 1: current adjustment of the base setpoint temperature (address 259, FC03) (actual values_1)

Output

rSetpTemp1

REAL

0.0

Temperature setpoint 1: current setpoint temperature (address 260, FC03) (actual values_1)

Output

rSetpTemp2Off

REAL

0.0

Temperature setpoint 2: current adjustment of the base setpoint temperature (address 261, FC03) (actual values_1)

Output

rSetpTemp2

REAL

0.0

Temperature setpoint 2: current setpoint temperature (address 262, FC03) (actual values_1)

Output

xButtonSetpTempUp

BOOL

FALSE

Generation of an impulse with duration tTimeButtonPulse, if

Output

xButtonSetpTempDown

BOOL

FALSE

Generation of an impulse with duration tTimeButtonPulse, if

Output

xModeDev

BOOL

FALSE

Current room occupancy from the device (TRUE = occupied, comfort mode, day mode) (address 264, FC03)

Output

xButtonPresence

BOOL

FALSE

Generation of an impulse with duration tTimeButtonPulse, if

Output

eFanModeDev

THERMOKON_WRF06_FAN_OP_MODE

1. at the parameter xVisuPresence OR 2. at the output of the selected button xButtonX (selection via eSelectButtonForPresence) a rising edge is detected (= actuation) Current operating mode of the fan (address 263, FC03)

Output

wNbrOfFanStages

WORD

0

Number of fan stages

Output

xAutoFanStages

BOOL

FALSE

Display of automatic mode for the fan stages (FALSE: manual correction active, TRUE = automatic mode active)

Output

xButtonFanStages

BOOL

FALSE

Generation of an impulse with duration tTimeButtonPulse, if

Output

xButton1

BOOL

FALSE

Pressing key 1 (right) (RAW, pulse with duration tTimeButtonPulse) (addresses 256 & 257, FC03)

Output

eFunctionButton1Fb

THERMOKON_WRF06_BUTTON_FUNCTION

Function of key 1 — feedback (address 6, FC03)

Output

xButton2

BOOL

FALSE

Pressing key 2 (middle right) (RAW, pulse with duration tTimeButtonPulse) (addresses 256 & 257, FC03)

Output

eFunctionButton2Fb

THERMOKON_WRF06_BUTTON_FUNCTION

Function of key 2 — feedback (address 7, FC03)

Output

xButton3

BOOL

FALSE

Pressing key 3 (middle left) (RAW, pulse with duration tTimeButtonPulse) (addresses 256 & 257, FC03)

Output

eFunctionButton3Fb

THERMOKON_WRF06_BUTTON_FUNCTION

Function of key 3 — feedback (address 8, FC03)

Output

xButton4

BOOL

FALSE

Pressing key 4 (left) (RAW, pulse with duration tTimeButtonPulse) (addresses 256 & 257, FC03)

Output

eFunctionButton4Fb

THERMOKON_WRF06_BUTTON_FUNCTION

Function of key 4 — feedback (address 9, FC03)

Output

xDI1

BOOL

FALSE

State of digital input 1 (assignment depending on function) (FALSE = open, TRUE = closed) (address 265, FC03)

Output

eFunctionDI1Fb

THERMOKON_WRF06_DIGITAL_INPUT_FUNCTION

Function of digital input 1 — feedback (address 26, FC03)

Output

xDI2

BOOL

FALSE

State of digital input 2 (assignment depending on function) (FALSE = open, TRUE = closed) (address 266, FC03)

Output

eFunctionDI2Fb

THERMOKON_WRF06_DIGITAL_INPUT_FUNCTION

Function of digital input 2 — feedback (address 27, FC03)

Output

xDI3

BOOL

FALSE

State of digital input 3 (assignment depending on function) (FALSE = open, TRUE = closed) (address 267, FC03)

Output

eFunctionDI3Fb

THERMOKON_WRF06_DIGITAL_INPUT_FUNCTION

Function of digital input 3 — feedback (address 28, FC03)

Output

xDI4

BOOL

FALSE

State of digital input 4 (assignment depending on function) (FALSE = open, TRUE = closed) (address 268, FC03)

Output

eFunctionDI4Fb

THERMOKON_WRF06_DIGITAL_INPUT_FUNCTION

Function of digital input 4 — feedback (address 29, FC03)

Output

xSensorOffsetInDevice

BOOL

Indication of whether the sensors must be calibrated in the device (TRUE = calibration in the device required, FALSE = calibration in the FB required)

Output

xAlarm

BOOL

FALSE

Collective fault (TRUE = fault)

Output

xAlarmCom

BOOL

FALSE

Collective fault - communication (TRUE = fault)

Output

eErrorCodeCom

ModbusErrorCode

Error code - communication (0 = no error)

Output

xBusy

BOOL

Communication indicator (TRUE = communication)

Input Const

wMaxFanStageManDay

WORD

2

Maximum fan stage for manual correction in day mode

Input Const

wMinFanStageManDay

WORD

0

Minimum fan stage for manual correction in day mode

Input Const

eSetpTempOpMode

THERMOKON_WRF06_SETP_TEMP_OPERATION_MODE

THERMOKON_WRF06_SETP_TEMP_OPERATION_MODE.SETPOINT_1

Selection of the setpoint (1, 2) for adjustment via the keys on the room operating device

Input Const

eButtonSelectionForSetpTempDown

THERMOKON_WRF06_BUTTON_SELECTION

THERMOKON_WRF06_BUTTON_SELECTION.BUTTON_2

Selection of the button (1 - 4) for selecting the button to reduce the setpoint temperature (output xButtonSetpTempDown)

Input Const

eButtonSelectionForSetpTempUp

THERMOKON_WRF06_BUTTON_SELECTION

THERMOKON_WRF06_BUTTON_SELECTION.BUTTON_1

Selection of the button (1 - 4) for selecting the button to increase the setpoint temperature (output xButtonSetpTempUp)

Input Const

eButtonSelectionForFanStages

THERMOKON_WRF06_BUTTON_SELECTION

THERMOKON_WRF06_BUTTON_SELECTION.BUTTON_3

Selection of the button (1 - 4) for selecting the fan stages (output xButtonFanStages)

Input Const

eButtonSelectionForPresence

THERMOKON_WRF06_BUTTON_SELECTION

THERMOKON_WRF06_BUTTON_SELECTION.BUTTON_4

Selection of the button (1 - 4) for the presence function ( output xButtonPresence)

Input Const

xVisuSetpTempDown

BOOL

FALSE

Visualization: pressing the button to reduce the setpoint temperature in day mode (on each rising edge )

Input Const

xVisuSetpTempUp

BOOL

FALSE

Visualization: pressing the button to increase the setpoint temperature in day mode (on each rising edge )

Input Const

xVisuAutoFanStages

BOOL

FALSE

Visualization: pressing the button to switch to automatic mode for the fan stages (on each rising edge)

Input Const

xVisuFanStages

BOOL

FALSE

Visualization: pressing the button for the fan stages ( on each rising edge)

Input Const

xVisuPresence

BOOL

FALSE

Visualization: pressing the presence button (on each rising edge)

Input Const

rExtValue4Mult

REAL

10.0

Multiplier for external measured value 4 for display on the ROD (address 522 = rExtValue4 * rExtValue4Mult)

Input Const

rExtValue3Mult

REAL

10.0

Multiplier for external measured value 3 for display on the ROD (address 521 = rExtValue3 * rExtValue3Mult)

Input Const

rExtValue2Mult

REAL

10.0

Multiplier for external measured value 2 for display on the ROD (address 520 = rExtValue2 * rExtValue2Mult)

Input Const

rExtValue1Mult

REAL

10.0

Multiplier for external measured value 1 for display on the ROD (address 519 = rExtValue1 * rExtValue1Mult)

Input Const

eRoomTempMode

THERMOKON_WRF06_ROOM_TEMP_MODE

THERMOKON_WRF06_ROOM_TEMP_MODE.INTERNAL_SENSOR

Mode for the source of the room temperature (EXTERNAL_VALUE: <br/>*<br/> rExtRoomTemp' defines the room temperature)

Input Const

xDsplAlarm4

BOOL

FALSE

Enable / disable display of alarm message 4 on the ROD ( TRUE = display)

Input Const

xDsplAlarm3

BOOL

FALSE

Enable / disable display of alarm message 3 on the ROD ( TRUE = display)

Input Const

xDsplAlarm2

BOOL

FALSE

Enable / disable display of alarm message 2 on the ROD ( TRUE = display)

Input Const

xDsplAlarm1

BOOL

FALSE

Enable / disable display of alarm message 1 on the ROD ( TRUE = display)

Input Const

eAnalogOutputsMode

THERMOKON_WRF06_ANALOG_OUTP_MODE

THERMOKON_WRF06_ANALOG_OUTP_MODE.MANUAL_MODE

Mode for analog outputs AO1 and AO2 (MANUAL_MODE: <br/>*<br/> rAO1Manual' and rAO2Manual define the current states of the analog outputs)

Input Const

wDateTime_Year

WORD

2024

Date / time update: current year (2000 - 2099)

Input Const

wDateTime_Month

WORD

1

Date / time update: current month (1 - 12 )

Input Const

wDateTime_DayOfMonth

WORD

1

Date / time update: current day of the month (1 - 31)

Input Const

wDateTime_Hours

WORD

0

Date / time update: current hour of the day (0 - 23)

Input Const

wDateTime_Minutes

WORD

0

Date / time update: current minute of the hour (0 - 59)

Input Const

wDateTime_Seconds

WORD

0

Date / time update: current second of the minute (0 - 59)

Input Const

eButton4OutpMode

THERMOKON_WRF06_BUTTON_OUTP_MODE

THERMOKON_WRF06_BUTTON_OUTP_MODE.RAW

Operating mode of the output xButton4 (RAW, PULSE)

Input Const

eButton3OutpMode

THERMOKON_WRF06_BUTTON_OUTP_MODE

THERMOKON_WRF06_BUTTON_OUTP_MODE.RAW

Operating mode of the output xButton3 (RAW, PULSE)

Input Const

eButton2OutpMode

THERMOKON_WRF06_BUTTON_OUTP_MODE

THERMOKON_WRF06_BUTTON_OUTP_MODE.RAW

Operating mode of the output xButton2 (RAW, PULSE)

Input Const

eButton1OutpMode

THERMOKON_WRF06_BUTTON_OUTP_MODE

THERMOKON_WRF06_BUTTON_OUTP_MODE.RAW

Operating mode of the output xButton1 (RAW, PULSE)

Input Const

tTimeButtonPulse

TIME

TIME#1s0ms

Duration of the pulse at the output, if the assigned button was pressed

Input Const

tTimeUpdateInfo

TIME

TIME#0ms

Update interval for the processes influenced by the input xUpdateInfo influenced

Input Const

tTimeUpdateStates

TIME

TIME#500ms

Update interval for the processes influenced by the input xUpdateStates influenced

Input Const

tTimeUpdateConfig

TIME

TIME#0ms

Update interval for the processes influenced by the input xUpdateConfig influenced

Input Const

tTimeUpdateSetp

TIME

TIME#45s0ms

Update interval for the processes influenced by the input xUpdateSetp influenced

Input Const

tTimeUpdateActual

TIME

TIME#3s0ms

Update interval for the processes influenced by the input xUpdateActual influenced

Last updated