SOLVIMUS_GE20M_GATEWAY
SOLVIMUS_GE20M_GATEWAY (FB)
SOLVIMUS_GE20M_GATEWAY (FB)FUNCTION_BLOCK SOLVIMUS_GE20M_GATEWAY
InOut:
Input
xEn
BOOL
TRUE
Enable / disable communication ( TRUE = enabled )
Input
byUnitId
BYTE
255
Address of the device (set by IP address)
Input
xUpdateActual
BOOL
FALSE
Update of actual values (on every rising edge )
Input
wBaseAdressGateway
WORD
0
Modbus - base register for the gateway information
Input
xResError
BOOL
FALSE
Reinitialization of the outputs ‘eErrorCodeCom’ to the no-error state (on each rising edge)
Inout
ModbusClient
ModbusClientBase
Client of the device
Output
dwSerialNum
DWORD
Gateway serial number
Output
wMBUSProtocolVer
WORD
Protocol version of the Modbus data
Output
wSoftwareVer
WORD
Gateway software version
Output
dtSysTime
DT
Gateway timestamp (UTC, in Germany UTC +1 / +2 h depending on summer / winter time)
Output
xAlarm
BOOL
FALSE
General fault ( TRUE = fault )
Output
xAlarmCom
BOOL
FALSE
General fault - communication ( TRUE = fault )
Output
eErrorCodeCom
ModbusErrorCode
Error code - communication ( 0 = no error )
Output
xBusy
BOOL
Communication indicator ( TRUE = communication )
Input Const
diAdrOffset
DINT
0
Offset for calculating Modbus addresses (from the Modbus registers) (permissible range: -1, 0, +1)
Input Const
tTimeUpdateActual
TIME
TIME#1m0s0ms
Update interval for operations influenced by the input 'xUpdateActual'
Last updated

